© 2015 Bel Power Solutions, Inc.
North America
+1
-866.513.2839
Asia-Pacific
+86.755.29885888
Europe
, Middle East
+353 61 225 977
tech.support@psbel.com
BCD20012-G_AB
RoHS compliant for all s
ix substances
40.5 to 72 VDC Input Range
12 V output
2000 VAC I/O electric s
trength test
Highly-efficient topology
High-density design
4" x 1.65" x 8.5" cassette
I
2
C interface
Supervisory signaling
Overtemperature, output o
vervoltage, and output
overcurrent protection
ORing diode included for true r
edundant operation
Safety approvals: UL6095
0-1/ CSA 60950-1, &
TUV EN60950-1
The
FND300-1012G
is
a
highly-efficient
bus
converter
with
one
high
current
output,
which
can
be
used
in
a
wide
range
of
applications
.
Passive
current
share
along
with
internal
ORing diod
es allow
this
unit
to be
also
used
in
redundant, hot-swap appli
cations.
The
FND300
meets
international
safety
standards
and
displays
the
CE
Mark
for
the
Low Voltage Directive.
Telecommunication Equip
ment
FND300-1012G
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD20012-G_AB
MODEL
NOMINAL OUTPUT
VOLTAGE
(VDC)
INPUT CURRENT
MAX
(ADC)
ADJUSTMENT
RANGE
(VDC)
OUTPUT RATED
CURRENT
I
RATED
(ADC)
OUTPUT
RIPPLE/NOISE,
m
V
p-p
TYPICAL
EFFICIENCY
@ I
RATED
%
FND300-
1012G
12
10
N/A
25
<120
>80
PARAMETER
CONDITIONS / DESCRIPTION
MIN
NOM
MAX
UNITS
Input Voltage
With full output power
40.5
48/60
72
VDC
Inrush Current Limitation
48 / 60 VDC
<12 / 15
A
Efficiency
V
i
nom,
I
o
nom
>80
%
PARAMETER
CONDITIONS / DESCRIPTION
MIN
NOM
M
AX
UNITS
Nominal Output Current
V1
V
i
min to
V
i
max
25
A
Output Voltage Setting
V1
V
i
nom, 12.5 A, Tc = 25
C
12.0
VDC
Static Line Regulation V1
V
i
min to
V
i
max,
V
i
nom,
5 to 100%
I
o
nom
±0.5
%
Static Load Regulation V1*
* (Droop Characteristic)
V
i
min to
V
i
max,
V
i
nom,
5 to 100%
I
o
nom
±5
%
Minimum Load
No minimum load requirements
Hold-
Up
Time
At full load, starting at
V
i
=
60 VDC
>8
ms
Dynamic Load Regulation
Settling Time
V1:
Δ
I
o
= 8A, d
I
o
/dt = 2A/µs
±2
400
%Vout
µs
Start-Up Time
V
i
nom,
I
o
nom
<1
s
Output Voltage Ripple And Noise
V
i
nom,
I
o
nom, 20 MHz BW
<120
mVp-p
PARAMETER
CONDITIONS / DESCRIPTION
MIN
NOM.
MAX
UNITS
Overvoltage Protection
Latch-style overvoltage protectio
n.
14.5
V
Overcurrent Protection
(Latch-style) 110 to 120%
I
o
nom
Overtemperature
Self-recovery;
shut down at Tc = 95
C
Input Fuses
15 AF, Not user-accessible
Input Transient Protection
VDR, reverse polarity protection
I
2
C Digital Bus
Reports information and monitors alarm
functions
PS
Seated Signal
Contact closure to GND
PS
Remote Shut Down
TTL
-compatible signal, inhibi
ted at High or TTL "1"
Power Fail
Indicates output voltage is out of regul
ation
Fan Fail
Indicates low fan speed
Current Share
Droop load characteristic
FND300-1012G
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD20012-G_AB
PARAMETER
CONDITIONS/DESCRIPTION
MIN
NOM
MAX
UNITS
Operating Temperature
V
i
min to
V
i
max,
I
o nom,
cooling by internal
fan
0
55
C
Storage Temperature
Ambient
-
40
85
C
Operating Humidity
Relative Humidity, Non-cond.
10
90
%
Storage Humidity
Relative Humidity, Non-cond.
5
95
%
Shock
IEC/EN 60068-2-
27, 11 ms
30
g
Sinusoidal Vibration
IEC/EN 60068-2-6
2 to 8 Hz
8 to 200 Hz
200 to 500 Hz
7.5
2
4
mm
g
n
g
n
Weight
1
kg
Dimensions
(Overall)
8.5 L
(215.9)
4.0 W
(101.6)
1.65 H
(41.9)
in
(mm)
MTBF
MIL-HDBK-217F Notice 2,
G
B
, 25
C
150'000
(calculated)
h
SAFETY AGENCY OR PARAM
ETER
STANDARD APPROVED TO:
MARKING OR RELATED TEST VALUE
UL/CSA
UL60950
-1 / CSA 60950-1
TUV Product Service
TUV EN60950-1
Electric Strength Test Voltage
Class I, I/case (basic insulation)
1.41 kVDC
Electric Strength Test Voltage
Class I, I/O (reinforced insulation)
2.82 kVDC
Electrostatic Discharge
IEC/EN 61000-4-2, level 4 (contac
t/air)
8/15 kV, criterion B
Electromagnetic Field
IEC/EN 61000-4-3, level 3
10 V/m, criterion A
Electrical Fast Transients / Bu
rst
IEC/EN 61000-4-4, level 4 (direct
capacitive)
4/2 kV, criterion B
Surge
IEC/EN 61000-4-5, level 2 (L/L, L/C)
0.5/1 kV, criterion B
Electromagnetic Emissions
CISPR 22/EN 55022/EN61204
conducted/radiated
Class B
PIN
SIGNAL NAME
DESCRIPTION
1-3,
13
-
15
V1 RTN
V1 Output Return
4-
6, 16
-
18
V1
V1 Output
7
-
Not Used
8
-
Not Used
9
PF
Power Fail
10
I
2
C
I
2
C Voltage Input/Output
11
SDA
Serial Data Line
12
SCL
Serial Clock Line
19
-
Not Used
20
-
Not Used
21
LSB
Address Input Line
22
RSD
Power Supply Remote Shut Down
23
PS_PRSNT_L
Power Supply Present signal
24
Fan Fail
Fan Fail signal
FND300-1012G
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD20012-G_AB
Power Supply:
Output
-
24
-Pin Molex connector 15-
06
-0241 with pre-plated tin over copper Molex terminals 39-
00
-0038
Mating Connections:
Output
-
24
-Pin Molex connector 15-
06
-0245 with pre-plated tin over copper Molex terminals 39-
00
-0040
0,2
0,25
0,3
0,35
0,4
0,45
0,5
0,55
0,6
0,65
0,7
0,75
0,8
0,85
0,9
0
5
10
15
20
25
30
Io
[A
]
Eta [-]
V
in=40
V
DC
V
in=60
V
DC
V
in=75
V
DC
AIRFLOW
FND300-1012G
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD20012-G_AB
Figure 1 - Efficiency vs. Output L
oad
Figure 2 - Efficiency vs. Input Voltage a
nd Ambient Temperature, Io=Ionom
PARAMETER
CONDITIONS / DESCRIPTION
Overall Dimensions (L x W x
H)
215.9 x 101.6 x 41.9 mm
(8.5 x 4.0
x 1.65 inches
)
Weight:
1 kg
Figure 3 - Front View
Figure
4
- Rear View
FND300-1012G
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD20012-G_AB
Figure 5 - Top View
Figure 6 - Side View
NUCLEAR AND MEDICAL APPLICATIONS
- Products are not d
esigned or intended for use as critical c
omponents in life support
systems, equipment used in hazardous environ
ments, or nuclear control systems.
TECHNICAL REVISIONS
- The a
ppearance of products, including safety agency certific
ations pictured on labels, may change depe
nding
on the date manufactured. Specifi
cations are subject to change without notice.
Suppliers Inquiry
Previous
Next
Link
Name *
Reason for Contact
General Inquiry
Place Order
Report Issue
Target Price (Option)
Email Address *
Message *
BOM / Attach Files (Option)
Maximum allowed file size is 10MB