BCD20012-G_AB
RoHS compliant for all six substances
40.5 to 72 VDC Input Range
12 V output
2000 VAC I/O electric strength test
Highly-efficient topology
High-density design
4" x 1.65" x 8.5" cassette
I2C interface
Supervisory signaling
Overtemperature, output overvoltage, and output
overcurrent protection
ORing diode included for true redundant operation
Safety approvals: UL60950-1/ CSA 60950-1, &
TUV EN60950-1
The FND300-1012G is a highly-efficient bus
converter with one high current output, which
can be used in a wide range of applications.
Passive current share along with internal
ORing diodes allow this unit to be also used in
redundant, hot-swap applications.
The FND300 meets international safety
standards and displays the CE Mark for the
Low Voltage Directive.
Telecommunication Equipment
FND300-1012G
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD20012-G_AB
MODEL
NOMINAL OUTPUT
VOLTAGE
INPUT CURRENT
MAX
(ADC)
ADJUSTMENT
RANGE
(VDC)
OUTPUT RATED
CURRENT
I RATED (ADC)
OUTPUT
RIPPLE/NOISE,
mV p-p
TYPICAL
EFFICIENCY
@ I RATED %
FND300-1012G
10
N/A
25
<120
>80
PARAMETER
CONDITIONS / DESCRIPTION
MIN
NOM
MAX
UNITS
Input Voltage
With full output power
40.5
48/60
72
VDC
Inrush Current Limitation
48 / 60 VDC
<12 / 15
A
Efficiency
V
i nom,
I
o nom
>80
%
PARAMETER
CONDITIONS / DESCRIPTION
MIN
NOM
MAX
UNITS
Nominal Output Current V1
V
i min to
V
i max
25
A
Output Voltage Setting V1
V
i nom, 12.5 A, Tc = 25 C
12.0
VDC
Static Line Regulation V1
V
i min to
V
i max,
V
i nom,
5 to 100%
I
o nom
±0.5
%
Static Load Regulation V1*
* (Droop Characteristic)
V
i min to
V
i max,
V
i nom,
5 to 100%
I
o nom
±5
%
Minimum Load
No minimum load requirements
Hold-Up Time
At full load, starting at
V
i = 60 VDC
>8
ms
Dynamic Load Regulation
Settling Time
V1: Δ
I
o = 8A, d
I
o/dt = 2A/µs
±2
400
%Vout
µs
Start-Up Time
V
i nom,
I
o nom
<1
s
Output Voltage Ripple And Noise
V
i nom,
I
o nom, 20 MHz BW
<120
mVp-p
PARAMETER
CONDITIONS / DESCRIPTION
MIN
NOM.
MAX
UNITS
Overvoltage Protection
Latch-style overvoltage protection.
14.5
V
Overcurrent Protection
(Latch-style) 110 to 120%
I
o nom
Overtemperature
Self-recovery;
shut down at Tc = 95 C
Input Fuses
15 AF, Not user-accessible
Input Transient Protection
VDR, reverse polarity protection
I2C Digital Bus
Reports information and monitors alarm functions
PS Seated Signal
Contact closure to GND
PS Remote Shut Down
TTL-compatible signal, inhibited at High or TTL "1"
Power Fail
Indicates output voltage is out of regulation
Fan Fail
Indicates low fan speed
Current Share
Droop load characteristic
FND300-1012G
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD20012-G_AB
PARAMETER
CONDITIONS/DESCRIPTION
MIN
NOM
MAX
UNITS
Operating Temperature
V
i min to
V
i max,
I
o nom,
cooling by internal fan
0
55
C
Storage Temperature
Ambient
-40
85
C
Operating Humidity
Relative Humidity, Non-cond.
10
90
%
Storage Humidity
Relative Humidity, Non-cond.
5
95
%
Shock
IEC/EN 60068-2-27, 11 ms
30
g
Sinusoidal Vibration
IEC/EN 60068-2-6
2 to 8 Hz
8 to 200 Hz
200 to 500 Hz
7.5
2
4
mm
gn
gn
Weight
1
kg
Dimensions
(Overall)
8.5 L
(215.9)
4.0 W
(101.6)
1.65 H
(41.9)
in
(mm)
MTBF
MIL-HDBK-217F Notice 2,
GB, 25 C
150'000
(calculated)
h
SAFETY AGENCY OR PARAMETER
STANDARD APPROVED TO:
MARKING OR RELATED TEST VALUE
UL/CSA
UL60950-1 / CSA 60950-1
TUV Product Service
TUV EN60950-1
Electric Strength Test Voltage
Class I, I/case (basic insulation)
1.41 kVDC
Electric Strength Test Voltage
Class I, I/O (reinforced insulation)
2.82 kVDC
Electrostatic Discharge
IEC/EN 61000-4-2, level 4 (contact/air)
8/15 kV, criterion B
Electromagnetic Field
IEC/EN 61000-4-3, level 3
10 V/m, criterion A
Electrical Fast Transients / Burst
IEC/EN 61000-4-4, level 4 (direct capacitive)
4/2 kV, criterion B
Surge
IEC/EN 61000-4-5, level 2 (L/L, L/C)
0.5/1 kV, criterion B
Electromagnetic Emissions
CISPR 22/EN 55022/EN61204
conducted/radiated
Class B
PIN
SIGNAL NAME
DESCRIPTION
1-3, 13-15
V1 RTN
V1 Output Return
4-6, 16-18
V1
V1 Output
7
-
Not Used
8
-
Not Used
9
PF
Power Fail
10
I2C
I2C Voltage Input/Output
11
SDA
Serial Data Line
12
SCL
Serial Clock Line
19
-
Not Used
20
-
Not Used
21
LSB
Address Input Line
22
RSD
Power Supply Remote Shut Down
23
PS_PRSNT_L
Power Supply Present signal
24
Fan Fail
Fan Fail signal
FND300-1012G
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD20012-G_AB
Power Supply:
Output - 24-Pin Molex connector 15-06-0241 with pre-plated tin over copper Molex terminals 39-00-0038
Mating Connections:
Output - 24-Pin Molex connector 15-06-0245 with pre-plated tin over copper Molex terminals 39-00-0040
0,2
0,25
0,3
0,35
0,4
0,45
0,5
0,55
0,6
0,65
0,7
0,75
0,8
0,85
0,9
0 5 10 15 20 25 30
Io [A]
Eta [-]
Vin=40VDC
Vin=60VDC
Vin=75VDC
AIRFLOW
FND300-1012G
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD20012-G_AB
Figure 1 - Efficiency vs. Output Load
Figure 2 - Efficiency vs. Input Voltage and Ambient Temperature, Io=Ionom
PARAMETER
CONDITIONS / DESCRIPTION
Overall Dimensions (L x W x H)
215.9 x 101.6 x 41.9 mm (8.5 x 4.0 x 1.65 inches)
Weight:
1 kg
Figure 3 - Front View
Figure 4 - Rear View
FND300-1012G
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD20012-G_AB
Figure 5 - Top View
Figure 6 - Side View
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support
systems, equipment used in hazardous environments, or nuclear control systems.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending
on the date manufactured. Specifications are subject to change without notice.