SmartPro 120V 2.2kVA 1.92kW Line-Interactive
Sine Wave UPS, 2U, Extended Run, Network
Card Options, LCD, USB, DB9
MODEL NUMBER: SMART2200RMXL2U
Description
Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power
protection for critical server, network and telecommunications equipment. Line Interactive Uninterruptible
Power Supply (UPS) with built-in Auto-Voltage Regulation (AVR) actively corrects brownouts and
overvoltages back to usable levels while maintaining a full battery charge in case of power failure. Tripp
Lite's unique configuration excels in exceptionally poor-power environments with two separate levels of
voltage boost to correct both slight undervoltages and severe brownout conditions. Interactive LCD
interface reports UPS operating mode, detailed UPS and site-power data, plus enables a variety of UPS
setup and configuration options. Super-fast switchover from line to battery power occurs within
milliseconds to maintain operation of connected equipment without interruption or reboot. 96% line-mode
efficiency offers reduced heat emissions and operating costs. Network management interfaces support
communications via USB, RS-232 and slot for optional Network Management Card. HID-compliant USB
port enables integration with built-in power management and auto shutdown features of Windows and
Mac OS X. Network communications ports enable detailed monitoring of equipment load levels, self-test
data and utility power conditions. PowerAlert UPS monitoring software is available via free download.
Switched output load banks enable scheduled and real-time remote reboot and load shedding of select
outlets. Emergency Power Off (EPO) interface. LCD display panel easily rotates for viewing in rackmount
or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode
configuration options. Programmable self-test. Field-replaceable, hot-swappable battery modules.
Features
Tripp Lite SMART2200RMXL2U line interactive 2U rack/tower UPS with 2200VA / 2.2kVA / 1920W
capacity and extended runtime options
Line interactive UPS with Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages
Highlights
2.2kVA / 2200VA / 1920W line
interactive 2U rack/tower UPS,
Sine Wave
120V output, Corrects
brownouts and overvoltages
from 83V to 145V
0.9 Power Factor, Interactive
LCD interface
Extended runtime options up to
1600W
4 post compatible mounting
accessories
96% line-mode efficiency, 2
switched load banks
USB, RS232, EPO and slot for
Network Management Card
options
120V NEMA 5-20P input, 4
NEMA 5-15R & 4 NEMA 5-
15/20R outlets
Package Includes
SMART2200RMXL2U UPS
system
USB, Serial & EPO cabling
4 post installation kit
Owner's manual
1 / 6
Specifications
from 83 to 145V
NEMA 5-20P input plug; 4 NEMA 5-15/20R and 4 5-15R output receptacles, Two independently
switched output load banks
Maintains uninterrupted operation of connected networking equipment during blackouts, surges,
brownouts and overvoltages
High 96% efficiency rating in line-power mode offers reduced power consumption and BTU emisssions
Internal batteries offer 12 minutes at 50% load (960W) and 4.5 minutes at 100% load (1920W)
Extended runtime is available with optional BP48V24-2U (limit 1), BP48V60RT-3U (multi-pack
compatible) and BP48V27-2US (multi-pack compatible), Output is reduced to 1600 watts maximum with
external battery packs
External battery configurations require the use of Tripp Lite's External Battery Configuration Software
(see manual)
Hot-swappable, user-replaceable internal batteries and external battery packs can be replaced with no
disruption to connected equipment
Intelligent battery management system extends battery life
Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar
battery charge graphic, plus 7 selectable screens of detailed UPS and site power information
LCD interface also supports a number of advanced user setup and operating preferences
Ships with 4 post rackmount installation hardware; Optional 2POSTRMKITWM enables 2 post
rackmount/wallmount installation; Optional 2-9USTAND enables tower placement
Built-in USB, RS-232 and slot for Network Management Card option; Compatible with Tripp Lite UPS
management card options TLNETCARD, WEBCARDLX and SNMPWEBCARD
HID-compliant USB port enables integration with built-in power management and auto shutdown
features of Windows and Mac OS X
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert
software, available via FREE download from www.tripplite.com/poweralert
Built-in Emergency Power Off (EPO) interface with cable
OUTPUT
Output Volt Amp Capacity (VA) 2200
Output kVA Capacity (kVA) 2.2
Output Watt Capacity (Watts) 1920
Output kW Capacity (kW) 1.92
Output Capacity Details Output is reduced to 1600 watts maximum when used with external battery packs
2 / 6
Power Factor 0.87
Nominal Output Voltage(s)
Supported 110V; 115V; 120V
Nominal Voltage Details 120v nominal output in battery mode
Frequency Compatibility 60 Hz
Output Voltage Regulation (Line
Mode) -14%, +6%
Output Voltage Regulation (Battery
Mode) +/- 5%
Output Receptacles (4) 5-15R; (4) 5-15/20R
Load Management Receptacles Two switched single outlet load banks (1 5-15/20R & 1 5-15R)
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery
Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 16.0A
Nominal Input Voltage(s) Supported 120V AC
UPS Input Connection Type 5-20P
UPS Input Cord Length (ft.) 10
UPS Input Cord Length (m) 3.0
Recommended Electrical Service 20A 120V
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 4.5 min. (1920w)
Half Load Runtime (min.) 12 min. (960w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs
External Battery Pack Compatibility BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27-2US (multi-pack compatible)
Expandable Runtime Description Maximum output capacity is 1600 watts when used with external battery packs
DC System Voltage (VDC) 48
Battery Recharge Rate (Included
Batteries) Less than 4.5 hours from 10% to 90% (typical, full load discharge)
Internal UPS Replacement Battery
Cartridge RBC94-2U
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, user replaceable batteries
Expandable Runtime Yes
3 / 6
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage Correction Voltage reduction of 12% applies when input is between 127 and 145
Undervoltage Correction Voltage boost of 12% applies when input voltage is between 96 and 108
Severe Undervoltage Correction Voltage boost of 24% applies when input voltage is between 83 and 95
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data,
plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for
detailed LCD configuration and monitoring options)
Switches 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Alarm Cancel Operation Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown
conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 570
UPS AC Suppression Response
Time Instantaneous
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Included Mounting Accessory
Description 4 post rackmount installation accessories included
Installation Form Factors Supported
with Optional Accessories 2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND); 2-4 post front rail
rackmount (UPSHDEARKIT)
Primary Form Factor Rackmount
UPS Power Module Dimensions
(hwd, in.) 3.46 x 17.32 x 19.29
UPS Power Module Dimensions
(hwd, cm) 8.79 x 43.99 x 49.00
Rack Height (U Spaces) 2
Minimum Required Rack Depth
(inches) 26.3
Minimum Required Rack Depth (cm) 66.80
UPS Power Module Weight (lbs.) 57.6
UPS Power Module Weight (kg) 26.13
UPS Shipping Dimensions (hwd /
in.) 9.1 x 22.44 x 24.2
4 / 6
UPS Shipping Dimensions (hwd /
cm) 23.11 x 57.00 x 61.47
Shipping Weight (lbs.) 68.8
Shipping Weight (kg) 31.2
Cooling Method Fan
UPS Housing Material Steel
Minimum Required Rack Depth
(mm) 668
Primary UPS Height (mm) 88
Primary UPS Width (mm) 440
Primary UPS Depth (mm) 490
Shipping Height (mm) 231
Shipping Width (mm) 570
Shipping Depth (mm) 615
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 306
Battery Mode BTU / Hr. (Full Load) 1157
AC Mode Efficiency Rating (100%
Load) 96%
COMMUNICATIONS
Communications Interface USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network Management Cards SNMPWEBCARD; TLNETCARD; WEBCARDLX
Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions
PowerAlert Software For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at
http://www.tripplite.com/poweralert
Communications Cable USB and DB9 cabling included
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network UPS Tools Compatibility NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at
http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite
LINE / BATTERY TRANSFER
Transfer Time 5 milliseconds (line to battery mode); 1 millisecond (battery to line mode)
5 / 6
© 2017 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
https://www.tripplite.com/products/product-certification-agencies
Low Voltage Transfer to Battery
Power (Setpoint) 83
High Voltage Transfer to Battery
Power (Setpoint) 145
SPECIAL FEATURES
Grounding Lug Back panel grounding lug
Cold Start (Startup in Battery Mode
During a Power Failure) Cold-start operation supported
High Availability UPS Features Hot swappable batteries
Green Energy-Saving Features Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
CERTIFICATIONS
UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A
(EMI); ROHS (Restriction of Hazardous Substances)
WARRANTY
Product Warranty Period
(Worldwide) 2-year warranty, 3 year with registration. Note: Registration is required for 3-year warranty.
Connected Equipment Insurance
(U.S., Canada & Puerto Rico) $250,000 Ultimate Lifetime Insurance
6 / 6
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Tripp Lite:
SMART2200RMXL2U