Specifications16, 25, 36,
Maximum leakage current, each6 Amps50 Amps
line-to-ground@ 120 VAC 60 Hz:2.9mA5.7 mA
@ 250 VAC 50 Hz:4.9mA9.8 mA
Hipot rating (one minute):
line-to-ground2250 VDC
line-to-line1450 VDC
Operating frequency:50/60 Hz
Rated voltage:440 VAC phase-to-phase
250 VACphase-to-neutral/ground
Rated current:@ 440 VAC phase-to-phase
6FCD6 Amps
16FCD16 Amps
25FCD25 Amps
36FCD36 Amps
50FCD50 Amps
Typicalinsertion loss in dB:
Line-to-ground in 50 ohm circuit
CurrentFrequency–MHz
Rating.01.03.05.1.5151030
6A21423395652484533
16A133036457575524535
25A133036457575524535
36A92632407575524535
50A92632407575524535
Line-to-line in 50 ohm circuit
CurrentFrequency–MHz
Rating.01.03.05.1.5151030
6A9 8 24406257504838
16A91324557575756560
25A91326557575756560
36A91326467575756560
50A91326467575756560
Libertyville, IL (847) 680-7400
FCD Series
Three Phase External
Power Line Filter
for Frequency Converters
FCD Series
The FCD filters provide three phase filtering for frequency
inverters and variable speed motor drives. Designed for
very noisy Delta applications, they attenuate conducted
interference at low and high frequency ranges and
protect programmable logic controllers from RF noise on
the AC power line. These filters perform best when
installed on the line side of the motor drive. The FCD
filters prevent noise from returning to the line, enabling
equipment to meet strict European regulations on RFI.
Suited for field wiring applications, these filters are ideal
for EMCtroubleshooting and field refurbishing. The FCD
filters feature side flanges for easy mounting and DIN
type terminals which eliminate live metal parts, allowing
safe and easy connection. They could also be sold as an
accessory to motor drives marketed into Europe.
Electrical Schematics
6 Amp
16, 25, 36 & 50 Amps
Resistor location for reference only.
FCD10