Du line
®
Fieldbus Installationbus
Specifications are subject to change without notice (05.05.03) 1
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Type: Dupline®
H4-Housing
Combined module
Interface type
DC supply
GE-Fanuc master
Plug and play: Automatic communication with specific
PLC/Controllers
Built-in normal Dupline®Channel Generator
128 I/O’s and DC power supply on 3 wires
RS232/RS422/RS485 port for interfacing to control
system
Split-I/O mode selectable (128 inputs and 128 outputs)
LED-indications for supply, Dupline carrier and Com-
port TX
Galvanically isolated Com-port supplied by internal
DC/DC converter
Product Description Ordering Key
G 3496 0002 is designed as a
cost-effective solution for
interfacing Dupline®I/O’s to a
GE-Fanuc PLC. It performs
three functions: Dupline®
channel generator, power
supply synchronization (en-
ables 3-wire system with sup-
ply) and RS232/RS422/
RS485 interface.
Type Selection
Supply PLC Interface Conformance Ordering no.
20-30 VDC GE-Fanuc Micro 90 & 90-30 G 3496 0002 700
G 3496 0002 700
Input/Output Specifications
Dupline®Plug & Play Master Module
Interface for GE-Fanuc PLC
Power output
Output voltage 20-30 VDC (pulsating)
Output current < 3.0 A @ 50ºC
Short circuit protection 4 A quick acting fuse
Output voltage drop < 1.0 V
Dupline®carrier
Output voltage 8.2 V (pulsating)
Current < 60 mA
Short circuit protection Yes
Scan time
128 channels 132.2 ms
64 channels 69.8 ms
Communication port
Standard RS232/RS422/RS485
Split I/O mode Yes, selectable
Normal Dupline mode Yes, selectable
Connection 9 pole female Sub-D
Dielectric voltage
Com-port Dupline®1 kVAC (rms)
Protocol SNP / Modbus-RTU
(Function code 01 & 15)
Baud rate 19200 (9600 for Modbus-
RTU protocol)
Data bits 8
Start bit 1
Stop bit 1
Parity Odd
Flow-control None
Type G 3496 0002
Input/Output Specifications (Cont.)
Pin assignment
2-wire RS 485
S/R Data line + (B) Pin 3
S/R Data line - (A) Pin 8
GND Pin 5
4-wire RS 485/RS 422
R Data line + (B) Pin 3
R Data line - (A) Pin 8
S Data line + (B) Pin 2
S Data line - (A) Pin 7
Direction Pin 4
(Connect to GND pin 5
when using 4-wire commu-
nication)
RS 232
TX Pin 1
RX Pin 9
GND Pin 5
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Operational voltage (Vin) 20-30 VDC
Reverse polarity protection None
Current consumption < 150 mA + Power load
Power dissipation < 5 W
Transient protection voltage 800 V
Dielectric voltage
Supply - Dupline®None
Supply - com-port 1 kVAC (rms)
Power ON delay 2 s
Indication for
Com-port Tx LED, red
Supply ON LED, green
Dupline®carrier LED, yellow
Environment
Pollution degree 3 (IEC 60664)
Operating temperature to +50°C (+32° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Du line
®
Fieldbus Installationbus
2Specifications are subject to change without notice (30.08.00)
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Mode of Operation
The Dupline
®
Master Module
(DMM) controls a 3-wire bus
with signal, DC-power and
common GND. The DMM is
connected to a standard DC-
supply, which it synchronizes
with the Dupline
®
carrier signal
before it is output to supply.
The synchronization is neces-
sary in order to enable the
Dupline
®
and DC-supply to
share the GND-wire.
The Dupline
®
Master Module is
a Dupline
®
Channel Generator
with the function of a master.
This means that the 128
Dupline
®
I/O’s will be read/writ-
ten by the DMM and then sent
to the PLC.
The DMM can run in two dif-
ferent modes – Normal mode
and split I/O mode. In Normal
mode, Dupline
®
operates as a
peer-to-peer system, where
the channel generator auto-
matically establishes a con-
nection between Dupline
®
inputs and Dupline
®
outputs
which are coded to the same
Dupline
®
address. If e.g. an
input coded for B5 is activat-
ed, the output(s) coded for B5
will also be activated.
Consequently, a Dupline
®
-out-
put can either be activated
through the output-data
received on DMM or by an
active Dupline
®
input coded
for the same Dupline
®
-
address. In “Split I/O” mode,
the channel generator treats
the Dupline
®
inputs and
Dupline
®
outputs indepen-
dently. If e.g. an input coded
for B5 is activated, the DMM
will make the information avail-
able for the PLC (like in normal
mode), but it will not automati-
cally activate the Dupline
®
out-
put(s) coded to B5. The
Dupline
®
outputs are con-
trolled exclusively through the
output data received from the
PLC. In this mode, up to 128
Dupline
®
inputs and 128
Dupline
®
outputs are available,
since an input and an output
coded to the same Dupline
®
address can operate indepen-
dently.
G 3496 0002
General Specifications
Humidity (non-condensing) 20 to 80%
Mechanical resistance
Shock 15 G (11 ms)
Vibration 2 G (6 to 55 Hz)
Dimensions H4-Housing
Material (see Technical information)
Weight 100 g
Dip-Switch Setting Memory Mapping
Dupline®GE-Fanuc Dupline®GE-Fanuc
Channel Channel
Read Write Read Write
A1 Q0257 Q0385 E1 Q0289 Q0417
A2 Q0258 Q0386 F1 Q0297 Q0425
A3 Q0259 Q0387 G1 Q0305 Q0433
A4 Q0260 Q0388 H1 Q0313 Q0441
A5 Q0261 Q0389 I1 Q0321 Q0449
A6 Q0262 Q0390 J1 Q0329 Q0457
A7 Q0263 Q0391 K1 Q0337 Q0465
A8 Q0264 Q0392 L1 Q0345 Q0473
B1 Q0265 Q0393 M1 Q0353 Q0481
B8 Q0272 Q0400 N1 Q0361 Q0489
C1 Q0273 Q0401 O1 Q0369 Q0497
D1 Q0281 Q0409 P1 Q0377 Q0505
Table of the memory mapping to the PLC
Sw.2 On: High PLC-memory Add, i.e. all address
numbers are increased by 256. This
selling is only used when two DMM are
connected to the same PLC.
Off:
Sw.3 On: Modbus-RTU Mode
Off: SNP Mode
Sw.4 On: Split I/O Channel Generator Mode
(See “Mode of Operation”)
Off: Normal Dupline
®
Monostable Channel
Generator Mode
Sw.5 On: 64 Dupline
®
channels
Off: 128 Dupline
®
channels
Wiring Diagram
1234
21 22 27 28
Supply in
20-30 V DC
24
23
678
5
26
25
+-
Power out
GND
Dupline Signal
RS 232
RS 485
3W
Du line
®
Fieldbus Installationbus
Specifications are subject to change without notice (30.08.00) 3
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Installation Hints
Interfacing to GE-Fanuc 90-30 PLC’s directly on the program-
ming–port (Switch 3 OFF & switch 2 OFF)
Interfacing to GE-Fanuc 90-30 PLC’s – CPU type 331 or higher,
equipped with communication coprocessor module CMM 311 in
Modbus-RTU mode (Switch 3 ON & switch 2 OFF)
Interfacing to GE-Fanuc 90-30 PLC’s – CPU type 350 or higher,
equipped with communication coprocessor module CMM 311 in
Modbus-RTU mode (Switch 3 ON & switch 2 ON)
No TX-LED
Configuration fault Check Dip-Switches check
configuration in PLC
Hardware fault Check the wiring.
No Dupline
®
Carrier-LED
Short circuit Short circuit between the
two Dupline
®
wires.
Accessories
GE-Fanuc 90-30 / 90 Micro
Cable Sub-D 9M/15M for 15p
Programming port RS-422-GE1
GE-Fanuc CMM311
Cable Sub-D 9M/25M for 25p
Communication port RS-422-GE2
Additional Information
Scope of supply
1 x Master Module G3496 0002 700
Pin Assignment
1
9
8
7
6
5
4
3
2
7
2
8
3
5
4
6
1
9
8
15
3K3
3K3
1
9
8
7
6
5
4
3
2
7
2
8
3
5
4
6
1
14
13
25
External
5 V DC-supply or
pin 5(+) and 7 (-) on
15-pin Programming port
-
+
Only for G 2196 0002
RS-422-GE2
RS-422-GE1
G 3496 0002