Technical Data 2044
Effective June 2017
Supersedes March 2008
Product features
Agency information
•UL Listed Card: MDQ-1⁄16 - 7A (Guide JDYX, File E19180)
•UL Recognition Card: MDQ-7.5 - 15A
(Guide JDYX2, File E19180)
•CSA Component Acceptance Card: MDQ-1⁄16 - 15 (Class
1422-01)
Ordering
•Specify packaging, product, and option code
(i.e., Bk-MDQ-BV-1)
MDQ
Dual-element time-delay glass fuses
•Dual-element, time-delay
•1⁄4" x 1 1⁄4" (6.3 x 32mm) physical size
•Glass tube, nickel-plated brass endcap construction
•UL Listed product meets standard 248-14
•Available with axial leads
Electrical Characteristics
Rated Current % of Amp Rating Opening Time
100% None
1⁄16 - 30A 135% 60 minutes maximum
200% 120 seconds maximum
Specications
Voltage Interrupting Typical DC Cold
Product Code Rating Rating Resistance
Vac Amps
MDQ-1/16 250 35 83.30000
MDQ-1/10 250 35 35.00000
MDQ-1/8 250 35 21.50000
MDQ-3/16 250 35 10.00000
MDQ-2/10 250 35 8.65000
MDQ-1/4 250 35 5.77500
MDQ-3/10 250 35 4.20000
MDQ-3/8 250 35 2.35000
MDQ-1/2 250 35 1.40000
MDQ-3/4 250 35 0.39685
MDQ-1 250 35 0.37400
MDQ-1-1/4 250 100 0.36000
MDQ-1-1/2 250 100 0.27000
MDQ-2 250 100 0.13250
MDQ-2-1/4 250 100 0.11450
MDQ-2-1/2 250 100 0.10050
MDQ-3 250 100 0.05715
MDQ-4 250 200 0.03510
MDQ-5 250 200 0.02650
MDQ-6 250 200 0.01715
MDQ-6-1/4 250 200 0.01690
MDQ-7 250 200 0.01375
MDQ-8 32 1,000 0.01200
MDQ-9 32 1,000 0.00888
MDQ-10 32 1,000 0.00720
MDQ-15 32 1,000 0.00410
** DC Cold Resistance (Measured at <10% of rated current)
(Ω)**