TECHNICAL DATA Fluke 1587 FC/1577 Insulation Multimeters The High-Performance 2-in-1 Insulation DMM The Fluke 1587 FC and 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true-rms digital multimeter in a single compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance. The Fluke 1587 FC Insulation Multimeter adds four powerful new diagnostic functions through the Fluke Connect(R) Measurements app: * PI/DAR timed ratio tests with TrendItTM graphs identifies moisture and contaminated insulation problems faster * Memory storage through Fluke Connect eliminates writing down results, reduces errors and saves data for historical tracking over time * Temperature Compensation through app for establishing accurate baselines and relevant historical comparisons * Historical tracking and trending of assets identifies degradation over time, allows real-time decisions to be made in the field with Fluke Connect(R) Assets (sold separately) FLUKE CONNECT COMPATIBLE (1587 FC ONLY) Download the free Fluke Connect (R) app from iTunes or Google Play to enable graphs within the Pi/DAR function, memory storage, and temperature compensation DISPLAY Large, 6000-count back-lit display VFD Low-pass filter for accurate motor drive measurements (1587 FC only) INSULATION TEST 1587 FC: 0.01 M to 2 G 1577: 0.1 M to 600 M INSULATION TEST VOLTAGES 1587 FC: 50 V, 100 V, 250 V, 500 V, 1000 V 1577: 500 V, 1000 V WARRANTY Three-year standard warranty; extendable to five-years through product registration within 45 days of purchase* Store and share data using the Fluke 1587 FC with Fluke Connect Measurements App. * Two-year additional warranty offer may be discontinued without notice Product Highlights * PI/DAR timed ratio tests (1587 FC only) * Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection * VFD low-pass filter for accurate motor drive measurements (1587 FC only) * Auto-discharge of capacitive voltage for added user protection * Insulation test (1587 FC: 0.01 M to 2 G) (1577: 0.1 M to 600 M) * Insulation test voltages (1587 FC: 50 V, 100 V, 250 V, 500 V, 1000 V),(1577: 500 V, 1000 V) for many applications * AC/DC voltage, DC millivolts, AC/DC milliamps, Resistance (), Continuity * Capacitance, diode test, temperature, Min/Max, frequency (Hz) (1587 FC only) Auto power off to save battery power CAT III 1000 V, CAT IV 600 V measurement category Large display with backlight Rugged, utility hard case allows you to bring everything you need for the job * Included accessories: Remote probe, test leads and probes, alligator clips, (K-type thermocouple, 1587 FC only) * Accepts optional Fluke TPAK Magnetic Meter Hanger for convenient hands free operation * Three-year standard warranty; extendable to five-years through product registration within 45 days of purchase* * * * * General Specifications Maximum voltage applied to any terminal and common 1000 V Storage temperature -40 C to 60 C (-40 F to 140 F) Operating temperature -20 C to 55 C (-4 F to 131 F) Temperature coefficient 0.05 x (specified accuracy) per C for temperatures <18 C or >28 C (<64 F or >82 F) Relative humidity Noncondensing 0 % to 95 % @ 10 C to 30 C (50 F to 86 F) 0 % to 75 % @ 30 C to 40 C (86 F to 104 F) 0 % to 40 % @ 40 C to 55 C (104 F to 131 F) Vibration Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument Radio frequency communication 2.4 GHz ISM Band Radio frequency certification FCC: T68-FBLE, IC: 6627A-FBLE Electromagnetic compatibility International IEC 61326-1: Portable Electromagnetic Environment; IEC 61326-2-2 CISPR 11: Group 1, Class A Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself. Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances. Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object. The equipment may not meet the immunity requirements of this standard when test leads and/or test probes are connected. 2 Fluke Corporation 1587 FC/1577 Insulation Multimeters General specifications cont. Korea (KCC) Class A Equipment (Industrial Broadcasting & Communication Equipment) Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes. USA (FCC) 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103. Enclosure protection IEC 60529: IP40 (non-operating) Safety IEC 61010-1 Pollution Degree 2 IEC 61010-2-033 CAT IV 600 V/CAT III 1000 V Batteries Four AA batteries (NEDA 15A or IEC LR6) Battery life Meter use 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 M with a duty cycle of 5 seconds on and 25 seconds off. Size 5.0 cm H x 10.0 cm W x 20.3 cm L (1.97 in H x 3.94 in W x 8.00 in L) Weight 550 g (1.2 lb) Altitude Operating 2000 m Storage 12,000 m Over-Range capability 110 % of range except for capacitance which is 100 % Frequency overload protection <107 V-Hz Fuse Protection for mA input 0.44A, 1000 V, IR 10 kA Electrical specifications AC voltage measurement Accuracy (1587 FC only) Range Resolution 50 Hz to 60 Hz (% of Rdg + counts) 60 Hz to 5000 Hz (% of Rdg + counts) 600.0 mV 0.1 mV (1 % + 3) (2 % + 3) 6.000 V 0.001 V (1 % + 3) (2 % + 3) 60.00 V 0.01 V (1 % + 3) (2 % + 3) 600.0 V 0.1 V (1 % + 3) (2 % + 3)1 1000 V 1V (2 % + 3) (2 % + 3)1 1 kHz bandwidth 1 Low-Pass Filter Voltage (1587 FC only) Range Resolution 50 Hz to 60 Hz (% of Rdg + Counts) 60 Hz to 400 Hz (% of Rdg + Counts) 600.0 mV 0.1 mV (1 % + 3) + (2 % + 3) - (6 % - 3) 6.000 V 0.001 V (1 % + 3) + (2 % + 3) - (6 % - 3) 60.00 V 0.01 V (1 % + 3) + (2 % + 3) - (6 % - 3) 600.0 V 0.1 V (1 % + 3) + (2 % + 3) - (6 % - 3) 1000 V 1V (2 % + 3) + (2 % + 3) - (6 % - 3) 3 Fluke Corporation 1587 FC/1577 Insulation Multimeters 1577 accuracy Range Resolution 50 Hz to 60 Hz (% of Rdg + Counts) 600.0 mV 0.1 mV (2 % + 3) 6.000 V 0.001 V (2 % + 3) 60.00 V 0.01 V (2 % + 3) 600.0 V 0.1 V (2 % + 3) 1000 V 1V (2 % + 3) AC Conversion Inputs are ac coupled true-rms responding and specified from 5 % to 100 % of range. Input signal crest factor can be up to 3 up to 500 V, decreasing linearly to a crest factor 1.5 at 1000 V. For non-sinusoidal waveforms add (2 % reading + 2 % FS) typical, for a crest factor up to 3. Input Impedance 10 M (nominal), <100 pF, ac-coupled Common mode rejection ratio (1 k unbalanced) >60 dB at dc, 50 or 60 Hz DC voltage measurement Range Resolution Accuracy 1587 FC 1 Accuracy 1577 1 (% of Rdg + Counts) (% of Rdg + Counts) 6.000 V dc 0.001 V (0.09 % + 2) (0.2 % + 2) 60.00 V dc 0.01 V (0.09 % + 2) (0.2 % + 2) 600.0 V dc 0.1 V (0.09 % + 2) (0.2 % + 2) 1000 V dc 1V (0.09 % + 2) (0.2 % + 2) 1 Accuracies apply to 100% of range. Input Impedance: 10 M (nominal), <100 pF Normal mode rejection ratio: >60 dB @ 50 Hz or 60 Hz Common mode rejection ratio: >120 dB @ dc, 50 Hz or 60 Hz (1 k unbalanced) DC millivolts measurement Range Resolution Accuracy 1587 FC Accuracy 1577 (% of Rdg + Counts) (% of Rdg + Counts) 600.0 mV dc 0.1 mV (0.1 % + 1) (0.2 % + 1) Resolution Accuracy 1587 FC (% of Rdg+Counts) Accuracy 1577 (% of Rdg+Counts) Burden voltage (Typical) 2 mV/mA DC and AC current measurement Range AC 45 Hz to 1000 Hz 400 mA 0.1 mA (1.5 % + 2)1 (2 % + 2)1 60 mA 0.01 mA (1.5 % + 2)1 (2 % + 2)1 DC 400 mA 0.1 mA (0.2 % + 2) (1.0 % + 2) 60 mA 0.01 mA (0.2 % + 2) (1.0 % + 2) 2 mV/mA 1 kHz bandwidth 1 Overload: 600 mA for 2 minutes maximum Fuse protection for mA Input: 0.44 mA, 1000 V, IR 10 kA AC conversion: Inputs are ac coupled true-rms responding and specified from 5 % to 100 % of range. Input signal crest factor can be up to 3 up to 300 mA, decreasing linearly to crest factor 1.5 at 600 mA. For non-sinusoidal waveforms add +(2 % reading + 2 % FS) typical, for a crest factor up to 3. 4 Fluke Corporation 1587 FC/1577 Insulation Multimeters Ohms measurement Range Resolution 600.0 0.1 6.000 k 0.001 k 60.00 k 0.01 k 600.0 k 0.1 K 6.000 M 0.001 M 50.0 M [2] 0.01 M 1 Accuracies apply from 0 % to 100 % of range. 2 Accuracy 1587 FC1 + (% of Rdg+Counts) Accuracy 15771 + (% of Rdg+Counts) (0.9 % + 2) (1.2 % + 2) (1.5 % + 3) (2.0 % + 3) Up to 80 % relative humidity. Overload protection: 1000 V rms or dc Open circuit test voltage: <8.0 V dc Short circuit current: <1.1 mA Diode test (1587 FC only) Diode test indication Display voltage drop: 0.6 V at 1.0 mA nominal test current: Accuracy (2 % + 3) Continuity test Continuity indication Continuous audible tone for test resistance below 25 and off above 100 . Maximum reading; 1000 Open circuit voltage <8.0 V Short circuit current 1.0 mA typical Overload protection 1000 V rms Response time >1 m sec Frequency measurement (1587 FC only) Range Resolution Accuracy (% of Rdg+Counts) 99.99 Hz 0.01 Hz (0.1 % + 1) 999.9 Hz 0.1 Hz (0.1 % + 1) 9.999 kHz 0.001 kHz (0.1 % + 1) 99.99kHz 0.01 kHz (0.1 % + 1) Frequency counter sensitivity Input range V ac Sensitivity (RMS Sine Wave)1 DC trigger levels to 20 kHz2 5 Hz to 20 kHz 20 kHz to 100 kHz 600.0 mV ac 100.0 mV 150.0 mV NA 6.0 V 1.0 V 1.5 V -400.0 mV and 2.5 V 60.0 V 10.0 V 36.0 V 1.2 V and 4.0 V 600.0 V 100.0 V 12.0 V and 40.0 V 1000.0 V 300.0 V 12.0 V and 40.0 V 1 Maximum input for specified accuracy = 10x range (1000 V max). Noise at low frequencies and amplitudes may affect accuracy. 2 Usable to 100 kHz with full scale input. Capacitance (1587 FC only) Range Resolution 1000 nF 1 nF 10.00 F 0.01 F 100.0 F 0.1 F 9999 F 1 F Accuracy (% of Rdg+Counts) (1.2 % + 2) (1.2 % + 90 counts) Temperature measurement (1587 FC only) Range Resolution Accuracy1 (% of Rdg+Counts) -40 C to 537 C 0.1 C (1 % + 10 counts) -40 F to 998 F 0.1 F (1 % + 18 counts) 1 Accuracies apply following 90 minutes settling time after a change in the ambient temperature of the instrument. 5 Fluke Corporation 1587 FC/1577 Insulation Multimeters Insulation specifications Measurement range Model 1587 FC: 0.01 M to 2 G Model 1577: 0.1 M to 600 M Test voltages Model 1587 FC: 50, 100, 250, 500, 1000 V Model 1577: 500, 1000 V Test voltage accuracy +20 %, -0 % Short-Circuit test current 1 mA nominal Auto discharge Discharge time <0.5 second for C = 1 F or less Live circuit detection Inhibit test if terminal voltage > 30 V prior to initialization of test Maximum capacitive load Operable with up to 1 F load Model 1587 FC Output voltage 50 V (0 % to +20 %) 100 V (0 % to +20 %) 250 V (0 % to +20 %) 500 V (0 % to +20 %) 1000 V (0 % to +20 %) Display range Resolution 0.01 to 6.00 M 0.01 M 6.0 to 50.0 M 0.1 M 0.01 to 6.00 M 0.01 M 6.0 to 60.0 M 0.1 M 60 to 100 M 1 M 0.1 to 60.0 M 0.1 M 60 to 250 M 1 M 0.1 to 60.0 M 0.1 M 60 to 500 M 1 M 0.1 to 60.0 M 0.1 M 60 to 600 M 1 M 0.6 to 2.0 G 100 M 0.1 to 60.0 M 0.1 M 60 to 500 M 1 M 0.1 to 60.0 M 0.1 M 60 to 600 M 1 M Test current Resistance accuracy (% of Rdg + Counts) 1 mA @ 50 k (3 % + 5 counts) 1 mA @ 100 k (3 % + 5 counts) 1 mA @ 250 k (1.5 % + 5 counts) 1 mA @ 500 k (1.5 % + 5 counts) 1 mA @ 1 M (1.5 % + 5 counts) (10 % + 3 counts) Model 1577 500 V (0 % to +20 %) 1000 V (0 % to +20 %) 6 Fluke Corporation 1587 FC/1577 Insulation Multimeters 1 mA @ 500 k (2.0 % + 5 counts) 1 mA @ 1 M (2.0 % + 5 counts) Comparison chart 1587 FC PI/DAR timed ratio measurements with TrendItTM graphs through Fluke Connect Measurements app * Memory storage through Fluke Connect Measurements app * Temperature Compensation through Fluke Connect Measurements app * VFD low-pass filter for accurate motor drive measurements * * Insulation test voltages 50 V, 100 V, 250 V, 500 V, 1000 V * Insulation test voltages 500 V, 1000 V Insulation test: 0.01 M to 2.0 G * Insulation test: 0.1 M to 600 M Auto-discharge of capacitive voltage Insulation test smoothing reading Frequency Capacitance Diode test Temperature Min/Max AC/DC Voltage DC Millivolts AC/DC Milliamps Resistance (0.1 to 50 M) Continuity Three-year warranty Remote probe, test leads, alligator clips K-type thermocouple Rugged, utility hard case Auto power off 7 Fluke Corporation 1587 FC/1577 Insulation Multimeters 1577 * * * * * * * * * * * * * * * * * * * * * * * * * * * * Ordering information Fluke-1577 Insulation Multimeter Fluke-1587 FC Insulation Multimeter Fluke-1587/MDT FC 2-IN-1 ADV Motor & Drive Kit w/9040, i400 1587KIT/62MAX+ FC 2-IN-1 ADV Elec Kit w/62MAX+ i400 Included Remote probe, test leads, alligator clips, K-type thermocouple (1587 FC only), hard case, user documentation Optional accessories TPAK Magnetic Tool Hanger i400 AC Current Clamp C25 Soft Case See it. Save it. Share it. All the facts, right in the field. Fluke Connect(R) with ShareLiveTM video call is the only wireless measurement system that lets you stay in contact with your entire team without leaving the field*. The Fluke Connect mobile app is available for iPhone models 4S and up running iOS 8.0 or higher, iPad Air and iPad Mini (2nd generation) in an iPhone frame on iPad and iPod Touch (5th generation) HTC One and One M8 running Android 4.4.x or higher LG G3 and Nexus 5 running Android 4.4.x or higher Samsung Galaxy S4 running Android 4.3.x or higher Samsung Galaxy S5 running Android 4.4.x or higher and works with over 20 different Fluke products--the largest system of connected test tools in the world. And more are on the way. Go to the Fluke website to find out more. Fluke. Keeping your world up and running.(R) *Within provider's wireless service area. Download the app at: Fluke Corporation PO Box 9090, Everett, WA 98206 U.S.A. Fluke Europe B.V. PO Box 1186, 5602 BD Eindhoven, The Netherlands All trademarks are the property of their respective owners. WiFi or cellular service required to share data. Smartphone, wireless service and data plan not included with purchase. First 5 GB of storage is free. Phone support details can be viewed at fluke.com/phones. Smart phone wireless service and data plan not included with purchase. Fluke Connect is not available in all countries. 8 Fluke Corporation 1587 FC/1577 Insulation Multimeters For more information call: In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa +31 (0) 40 2675 200 or Fax +31 (0) 40 2675 222 In Canada (800)-36-FLUKE or Fax (905) 890-6866 From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com (c)2015 Fluke Corporation. Specifications subject to change without notice. Printed in U.S.A. 8/2014 6005917a-en Modification of this document is not permitted without written permission from Fluke Corporation.