Compact Power Line
48V DC Critical Power Solution
The Compact Power Line platform is designed to provide highly reliable DC power for
48V distributed power architectures. A single shelf configuration provides up to 11kW
of 48V output power in 1U high and mounts in 19-inch or 23-inch wide frames. The
CPL product platform is easily expandable for future growth. CPL is a reliable DC power
solution for mission-critical enterprise and telecommunications network equipment.
Shelf Options
The CP product line provides several
shelf options with common or split
DC output configurations. There
are two families of CPL shelves; one
used with a Pulsar Edge controller,
the other used without a controller
or with a customer’s own controller
using I2C communications. J85480S1
shelves have four slots for rectifiers
or converters (PEMs) and use I2C for
communications. J2007001 shelves
have four slots with space for a full-
feature Pulsar Edge Controller.
The Pulsar Edge controller has Ethernet
connectivity to facilitate remote
network management to monitor
and control rectifiers, batteries, and
distribution. CPL is ideal for a broad
range of applications requiring highly
efficient 48V DC power.
Rectifier Options
CP2000 and CP2725 rectifiers are single
phase, constant power rectifiers that
provide 2000 Watts and 2725 Watts
(respectively) of highly reliable DC power.
The constant output power characteristics,
extended temperature range, universal AC
input, and compact size are key attributes
that make this rectifier the right choice for
your power needs.
Pulsar Edge Controller
CPL features the Pulsar Edge controller
delivering large system intelligence in
a small system form factor. Ethernet
connectivity with SNMP facilitates
remote network management.
Features and Benefits
Reliability
Proven field performance
Advanced alarming
N+1 modularity
Intelligence
Industry leading controller features
Ethernet interface for remote access
Centralized network management
Investment Protection
Minimal space requirements
Versatile configurations
Efficient operation
On Time Delivery
Standard building blocks
8-16 week availability
24/7 support
Compact 48V DC
distributed power
system
• Eciency
approaching 97%
Maximum power in
minimal space
Scalable to 80 kW
Powering enterprise and
telecommunications
networks
CPL Power Supplies
Applications
Key Features
Specifications
The CPL series of rectifiers are specifically designed to operate as an integral part of a
complete distributed power system or can be easily integrated into an OEM design. The
high-density, front-to-back airflow rectifier is designed for minimal space utilization and is
highly expandable for future growth.
The power modules are available with many features including PoE isolation, RS485
communications bus for use with GE battery plant controllers in forming an energy reserve
system and redundant I2C communications bus for use with a customer’s controller. This
flexible and sophisticated feature set makes this front-end power supply an excellent choice
for power in a variety of application spaces.
Enterprise networks
OEM Telecom equipment
Power over Ethernet
VoIP/soft switches
SAN/NAS/iSCSI applications
LAN/WAN/MAN applications
Indoor wireless
Routers and switches
Compact 1RU form factor
PMBus compliant dual
I2C and RS485 serial bus
communications
Front panel LED indicators
Internal variable-speed
fan control
Constant power; 52 – 58 Vdc
Programmable output
voltage; 44 – 58 Vdc
Universal AC input
PoE compliant versions
available
CE marked
RoHS 6 compliant
Hot pluggable
AC-DC Power Supplies
Input 2000 2725
Voltage Range
- Low-Line
- High-Line
120Vac Nominal (1200W)
208, 240, 277Vac Nominal
Input Frequency 47 – 63 Hz
Input Current 11.9 Arms @ 110Vac
13.1 Arms @ 240Vac
Inrush Transient 25Apk Typical
Power Factor 0.98 from 50% to 100% Load
Holdup Time 20ms1, 30ms**
EMI/EMC Exceeds FCC and CISPR22 (EN55022) - Class A
1 measurement starts at zero crossing of the ac voltage, and voltage devayed to 40V
2 for loads below 1200W
Compact Power Line, CPB-CPL | GECriticalPower.com
2
AC-DC Power Supplies
Output 2000 2725
Voltage Default 54Vdc
Voltage Adjust Range
- Hardware set via margin pin
- I2C or RS485 set
44-58Vdc
42-58Vdc
Rated Output Current
- Low Line
- High Line
251
38.42
251
52.42
Rated Output Power
- Low Line
- High Line
1200W3
2000W4
1200W3
2725W4
Psophometric Noise 9mVrms5
Ripple (5Hz to 20MHz)
- RMS
- Peak to Peak
100mVrms max
250mVp-p max
Over Voltage Protection
- Delayed
- Immediate
60Vdc
60Vdc
Over Temperature
- Warning
- Shutdown
5C
20C
PoE Isolation Optional Optional
1 at 1200W, 54V @ 100-120Vac
2 at full power @ 52V @ 200-240Vac
3 at low line input from nominal 100-120Vac
4 at high line input from nominal 200-277Vac
5ComplieswithANSITI.523-2001section4.9.2emissionsmaxlimitof20mVatunweightedwidebandnoiselimit
DC-DC Power Supplies
Output 2000 2500
Voltage Range -40 to -72 Vdc
Input Current 60Adc max 75Adc max
Inrush Current 60Adc max 100Adc max
Holdup Time 6ms
EMI/EMC Exceeds FCC and CISPR22 (EN55022) - Class A
DC-DC Power Supplies
Output 2000 2500
Voltage Default 54Vdc
Voltage Adjust Range 44 - 58 Vdc
Rated Output Current 0.1 to 37A 0.1 to 46.3A
Rated Output Power 2000W 2500W
Ripple (5Hz to 20MHz)
- RMS
- Peak to Peak
250mVrms
500mVpk-pk
Over Voltage Protection
- Delayed
- Immediate
60Vdc
65Vdc
Over Temperature
- Warning
- Shutdown
5C
20C
PoE Isolation Yes Yes
Compact Power Line, CPB-CPL | GECriticalPower.com 3
Mechanical
Length (in./mm) 13.85 / 351.2
Width (in./mm) 4 / 101.6
Height (in./mm) 1.63 / 41.4
Weight (lb / kg) 5 / 2.27
General
Cooling Internal variable speed fan cooled
Eciency 90% @ 100 Vac (Vout>52V, Pout>50%
93% @ 230 Vac (Vout>52V, Pout)
Heat Dissipation AC-DC
2725 -> 151W / 514 BTU
2500 -> 138W / 471 BTU
2000 -> 110W / 375 BTU
DC-DC
2500 -> 220W / 751 BTU
2000 -> 176W / 601 BTU
Environmental
Operating Temperature -40ºC1 to +75ºC (-40°F to 167°F)
Storage Temperature -40°C to +85°C (-40°F to 185°F)
Power De-Rating > +55°C (derates @ 2% per °C)
Relative Humidity 95% max, non-condensing
Altitude 4,000m max (13,000 ft)
Audible Noise 55dBA, typical
Safety and Standards Compliance
Zone 4 PerTelcordiaGR-63-CORE,alloorswheninstalledin
CPL shelf
Safety CE mark to Low Voltage Directive 2006/95/EC
UL 609501-1 Recognized
CAN/CSAC22.2No.60950-1-03Certied
VDE 0805-1 Licensed to IEC60950-1
RoHS Compliant to RoHS EU Directive 2002/95/EC
EMC FCC and CISPR22 (EN 55022) Class A
ESD EN/IEC 61000-4-2 Level 3
1 Designed to start at an ambient as low as -40°C but may not meet operational
limits until above -5°C.
All AC-DC models and All DC-DC models
Compact Power Line, CPB-CPL | GECriticalPower.com
4
Outline Drawing
Symbol Analog Mode I2C Mode RS485 Mode
On: Input OK
Blinking: Input out of limits
On: Output OK
Blinking: Overload
On: Over-temperature warning On: Over-temperature warning
Blinking: Service
On: Over-temperature warning
On: Fault On: Output OK
Blinking: Overload
Dimensions
Front Panel LEDs
Applications
Key Features
Enterprise Networks - Voice, Data, PoE
Telecommunications networks
Transmission equipment
Fiber in the loop
Routers/switches
Data networks
PBX
Remote Access and Features
Integrated 10/100Base-T Ethernet Network
- TCP/IP
- SNMP V2c for management
- SMTP for email
- Telnet for command line interface
- DHCP for plug-n-play
- FTP for rapid backup and upgrades
- HTTP for standard web pages and
browsers
- Compatible with Galaxy Manager
and other management packages
- Shielded RJ-45 interface referenced
to chassis ground
Password protected security levels: User,
Super-User, Administrator for all access
Ground-referenced RS232 system port
ANSI T1.317 command-line interface
Modem access support
- Remote via external modem
- Callback security
EasyView2, Windows-based GUI software for
local terminal or
Modem access
Standard System Features
Monitor and control of more than 40
connected devices
- Maximumof32rectiers
- Maximum of 6 distribution control cards
- Robust RS485 system bus
• Standardanduserdenedsystemalarms
- Alarm test
- Assignable alarm severity: Critical,
Major, Minor, Warning, and
Record-only
• Rectiermanagementfeatures
- Automaticrectierrestart
- ActiveRectierManagement
(energyeciency)
- Remoterectier(on/o)
- Reserve Operation
- Automaticrectiersequencecontrol
- N + X redundancy check
Multiple Low Voltage Load and Low Voltage
Battery Disconnect thresholds (4)
• Conguration,statistics,andhistory
- All stored in non-volatile memory
- Remote/local backup and restore of
congurationdata
Industry standard defaults
- Customerspeciccongurations
available
Remote/ local software upgrade
Basic, busy hour, and trend statistics
Detailed event history
Userdenedeventsandderivedchannels
Standard Battery Management Features
Float/boost mode control
- Manual boost
- Manual timed boost locally, T1.317,
and remotely initiated
- Auto boost terminated by time
or current
Battery discharge testing
- Manual (local/remote)
- Periodic
- Plant Battery Test (PBT) input driven
- Congurablethresholdor
20% algorithm
- Graphical discharge data
- Rectierson-lineduringtest
Slope thermal compensation
- High temperature
- Low temperature
- Step temperature
- STC Enable/Disable, low temperature
Enable/Disable
- CongurablemV/°Cslopes
State of charge indication
High temperature disconnect setting
Reserve-time prediction
Recharge current limit
• EmergencyPower-Oinput
Compact Power Line, CPB-CPL | GECriticalPower.com 5
Pulsar Edge Controller (For Applications in J2007001 shelves)
The CPL Pulsar Edge controller delivers large system intelligence in a small system form factor. This
family of controllers functions as a network interface controller (NIC) and as a full-featured battery plant
controller to the Compact Power Line (CPL) platform. Its thin modular plug-in form factor minimizes shelf
space consumption allowing maximum power module and distribution capabilities yet provides features
found in controllers used in much larger power systems.
The Pulsar Edge CP841A controller is utilized in bulk power applications in data centers and enterprise
applications. Ethernet connectivity with SNMP facilitates remote network management access through its
front-accessible RS232 or USB port and is aided by the EasyView2 graphical user interface.
As a battery plant controller, it provides a complete set of features to monitor and control rectifiers, batteries, and distribution. A flexible
set of configurable inputs allow the CP841A to monitor a wide variety of system equipment and incorporate appropriate state information
enabling a centralized point of management.
The controller utilizes standard network management protocols allowing for advanced network supervision. GE Galaxy Manager* software is
the centralized visibility and control component of a comprehensive power management system designed to meet engineering, operations, and
maintenance needs. The Galaxy Manager client-server architecture enables remote access to system controllers across the power network.
* See next page for Galaxy Manager description
Compact Power Line, CPB-CPL | GECriticalPower.com
6
General
Operating Voltage ±24 Vdc, ±48 Vdc
(Range: ±18 to ±60 Vdc)
Input Power Less than 7W
Operating Temperature Range -40°C to +75°C (-40°F to 167°F)
Storage Temperature Range -40°C to +85°C (-40°F to 185°F)
Operating Relative Humidity 0 - 95% (non-condensing)
PhysicalSpecications 1.75 in. H, 0.75 in. W, 8.00 in. D; 0.5lb
45mm H, 20mm W, 204mm D; 227g
Display 8-line by 40-character backlit LCD
Agency Certications
Radiated Emissions FCC, Class B; EN 55022, Class B
Safety UL Unlisted Component as Part of CPL or SPS
Power System
RoHS Compliant to RoHS EU Directive 2002/95/EC
EMC FCC/EN55022 Class B, CISPR22 Level B
ESD EN 61000-4-2 level 4
Integrated Monitoring Inputs/Outputs
System plant voltage (accuracy ±0.5%, resolution 0.01V)
One system shunt (accuracy ±1% full scale, resolution 1A)
- Battery or load
- Mounted in the return side of DC bus
Up to 15 binary inputs
- Six inputs close/open to battery
- 9 input close/open to return (number is dependent upon
number of output alarms)
- User assignable
Up to 5 user assignable Form-C output alarms (50VDC @ .3A)
1-Wire* bus devices
- Up to 16 temperature probes (QS873)
- Up to 6 mid-string monitors (ES771)
Galaxy Manager Compatible
Centralized web server and database with multiple user access to
live or managed data with drill down to problem details
Monitor and control of more than 40 connected devices
Management information from polling or alarms received from
alarm traps from multiple sites are available on one screen via the
inter/intranet
Trend user selected data over time
Automatic or manual report generation
Standard engineering tools like reserve time calculators and cable
voltage drop analyzer
48V DC Critical Power Solution
Features – Model J85480S1
Features – Model J2007001
The Compact Power Line platform is designed to provide highly
reliable DC power for 48V distributed power architectures. When
embedded into an OEM design, GE can support the integration
into the OEM design, Otherwise an external shelf can be used to
provide power. A single shelf configuration provides up to 11kW of
48V output power in 1U high and mounts in 19-inch or 23-inch wide
frames. The CPL product platform is easily expandable for future
growth by stacking multiple shelves. CPL is a reliable DC power
solution for mission-critical enterprise and telecommunications
network equipment.
The CPL product line provides several shelf options. J85480S1
shelves have four slots for either rectifiers or converters (PEMs).
These shelves are primarily used without a controller or with a
customer’s controller using I2C communications. J2007001 shelves
have four slots with space for a full-feature Pulsar Edge Network
Interface Controller (NIC). The Pulsar Edge controller has Ethernet
connectivity with SNMP to facilitate remote network management
to monitor and control rectifiers, batteries, and distribution. These
shelves are used with either shelf mounted distribution or external
distribution panels for small battery plant applications.
Fits into a standard 19” rack
Two DC Outputs may be common or split. Each output bus is rated
for 100A with two-hole lug landings for 2 AWG wire.
Choose between IEC-320 C13 or C19 or other
AC input connections.
Analog or dual/redundant I2C communications.
Adjustable mounting ears for near flush front or multiple set
back positions.
Fits into a standard 19” rack
Single DC output rated for 200A with two-hole lug landings for up
to 2/0 AWG cable.
Choose between IEC-320 or Molex Mini-Fit SR for AC input. Single,
dual or quad input feeds
RS485 communications.
Adjustable mounting ears with multiple set back positions.
Up to 3 shelves may be interconnected with bus straps for DC
outputs for a 600A system
Plug-N-Play CP841A controller with front access craft port, rear
access LAN and alarm connections
Select Shelves include distribution modules
J2007 Rectifier Shelf
J2007 Converter Shelf
J85480 Rectifier Shelf
J85480 Converter Shelf
Compact Power Line, CPB-CPL | GECriticalPower.com 7
Ordering Information – Compact Power Line
Compact Power Line, CPB-CPL | GECriticalPower.com
8
Shelf Line Drawing – J85480S1Shelves
List Max
Power
DC Input
Plug
DC Output Max Power
Supply
Features Order Code
Bus Termination Setpoint Other
14 10kW Qty 2 (1 per 2
rectiers) split DH Lugs CP2500DC (+) 48Vdc POE, Analog, I2CCC109124764
List Max
Power
AC Input
Plug
DC Output Max Rectier
Size
Features Order Codes
Bus Termination Setpoint Other
20
11kW IEC-320, C19
Common
DH Lugs
CP2725
(+) 54Vdc
Analog, I2C
CC109147344
21 Split -54Vdc CC109147328
23 8kW IEC-320, C13 Common CP2000 (+) 54Vdc POE, Analog, I2CCC109150447
J85480S1 Shelf Options
List 25 shelves are preprogrammed to be always ON. Either polarity can be grounded.
Split shelves L21 and Vout (-) is split, however Vout (+) is paralleled among the 4
rectifiers. Vout (+) should be grounded.
All lists, up to 2 shelves can be paralleled for a single I2C line. Up to eight shelves may
be paralleled for current shared power delivery.
All lists, shelf configured set point ensures inter-operability among all rectifiers from
CP2000 to CP2725. Rectifiers will proportionately current share relative to their output
power capacity.
All Shelves are RoHS 6 compliant. Order should reflect J85480S1LxxZ where xx is the
list number and Z indicates compliance to RoHS 6.
Notes:
Compact Power Line, CPB-CPL | GECriticalPower.com 9
Description Schematic
Common Output Bus for Terminal Lug Connection
Each Lug Connection rated for 100A with 2 gauge wire
(200A for shelf)
Split Output Bus for Terminal Lug Connection
Vdc( - ) has Split buses Vdc( + ) is common to
both sections.
• Each bus may be independently controlled
• Multiple shelves may not be paralleled together.
Each Lug Connection rated for 100A with 2 gauge wire
(200A for shelf)
J1 CONNECTOR – Pin Out
Pin Signal Pin Signal
1POWER_CAP_1 16 SDA_1
2POWER_CAP_2 17 Fault
3POWER_CAP_3 18 Alert#_0
4POWER_CAP_4 19 Enable side B
5MOD_PRES_1 20 Logic_GRD
6MOD_PRES_2 21 Enable Side A
7MOD_PRES_3 22 Logic_GRD
8MOD_PRES_4 23 Alert#_1
9PFW_1 24 5VA
10 PFW_2 25 OTW
11 PFW_3 26 Reset
12 PFW_4 27 Iso. barrier n/c
13 SCL_0 28 Iso. barrier n/c
14 SCL_1 29 Shelf_Addr_B
15 SDA_0 30 Shelf_Addr_A
J2 CONNECTOR – Pin Out
Pin Signal Pin Signal
1SCL_0 8Alert#_1
2SCL_1 9Isolation n/c
3SDA_0 10 Isolation n/c
4SDA_1 11 Ishare - B
5Alert#_0 12 Ishare - A
65VA 13 8V_INT - B
7Logic_GRD 14 8V_INT - A
DC Output Types – J85480S1 Shelves
Communication Signals – J85480S1 Shelves
Compact Power Line, CPB-CPL | GECriticalPower.com
10
Shelf Line Drawing – J2007001 Shelves
List Max Rectifer
Size AC Input DC Output Rear View of Shelf
32725 Watts Single AC feed
(terminal blocks
for 6ga wire and
¾”conduittting)
DC output bus is
rated for 200A for
two 2ga or one
2/0 gauge two-
hole lugs
(¼-20 studs on
5/8” centers).
DC Output Bus AC Signal
42725 Watts Individual feed
(Molex Mini-Fit SR)
62725 Watts Individual feed
(IEC-320 C19
Cords)
J2007001 Shelf Options
1. CP841A Pulsar Edge Controller ships separately.
2. Up to 3 shelves may be interconnected.
Notes:
List Max
Power
DC Input
Plug
DC Output Max Power
Supply
Features Order Code
Bus Termination Setpoint Other
14 10kW 2 x ¼-20 x 5/8 in
DH Lug Common 2 x ¼-20 x 5/8 in
DH Lug CP2500DC Variable, set by
Edge Controller RS485 CC109157657
J2007001L14 DC PEM Shelf Options
Compact Power Line, CPB-CPL | GECriticalPower.com 11
J2007001 Shelves System Controller Overview
Communication Signals for J2007001 Shelves
Battery Monitoring
J1 CONNECTOR – Pin Out
Pin Signals for SPS841A_3C3R Signals for SPS841A_0I5R
1ALM1 Input Alarm Relay 3 Rtn
2ALM2 Input Alarm Relay 2 Rtn
3Alarm Relay 1 Rtn Alarm Relay 1 Rtn
4Power Minor Rtn Power Minor Rtn
5Power Major Rtn Power Major Rtn
6ALM1, 2, 6C RTNS Alarm Relay 3
7ALM6 Input Alarm Relay 2
8Alarm Relay 1 Alarm Relay 1
9Power Minor Power Minor
10 Power Major Power Major
Edge Controller
CP841A_3C3R J1 has 3 alarm inputs with a common return and 3 output relays; Power Major, Power Minor, 1 Selectable
J2 CONNECTOR
Pin Signal
1ALM6 Input
2 -
3ALM3 Input
4ALM4 Input
5ALM5 Input
6-48V
7-48V
8-48V
J7 CONNECTOR
Pin Signal
1FAJ
2Coil Rtn
3LVD_NC
4LVD_NO
5Shunt-
6OS
7Coil1
8Coil2
9LVD Status Rtn
10 Shunt+
J1 provides alarm outputs and inputs based on the controller installed (see
table below). Inputs are “Dry”, no voltage, contact Closures or Opens to a
common return on pin 6. Outputs are relay contacts. Both input and output
alarms are customer defined on the controller’s web pages.
J2 provides alarm inputs (see table below). Alarm inputs are contact Closures
or Opens to the non-grounded side of the dc bus [-48V]. Pins 6, 7, 8 provide
-48V for these alarm inputs.
J3 battery thermal probe (QS873A) or battery mid-string voltage monitor
(ES771) with battery thermal probe.
J4 shelf to shelf communication connection
J5 LAN/Ethernet.
J7 provides distribution control for shelves with external distribution.
See table below.
Temperature/Voltage probes are needed for battery monitoring. They
are connected to each battery or battery string to provide slope thermal
compensation, temperature alarms and voltage imbalance alarms. Refer to
ordering guide for diagram and part numbers.
Compact Power Line, CPB-CPL | GECriticalPower.com
12
Communication Cables
10’ Communication Cable (J1) CC848854034
Shelf to shelf communication cable
(J2)
CC848848952
Rectier
CP2000AC54TEZ CC109158440
CP2000AC54TEP CC109167565
CP2725AC54TEP CC109167532
CP2725AC54TEZ CC109149423
Rectier Slot Filler
CentralOce
White
CC848822263
Converter (PEM) Options
CP2000DC54PEZ CC109162104
CP2500DC54PEZ1CC109170528
Rectier Slot Filler
CentralOceWhite CC848822263
Rectier Shelf Options
List 20 CC109147344
List 21 CC109147328
List 23 CC109150447
For more options see page 7
Converter Shelf Options
List 14 CC109124764
Mounting Brackets
1U bracket for 23”
frame mount
CC848844803
2U bracket for 23”
frame mount
848683009
Wall mount bracket CC848864504
Mounting Brackets
1U bracket for 23”
frame mount
CC848844803
Wall mount bracket CC848864504
DC Input Cables
DC input cable,
10 GA, 4’
CC848794908
DC Output Cables
DC output cable,
2 GA 10’
848748987
DC Bus for 1/4”
Faston Connections
(2 required)
CC848886192
AC Input, DC Output Cables
C13 plug with 5-15P plug, 10’ CC848776105
C13 plug with L6-20P plug, 10’ CC848820317
C13 plug, unterminated, 10’ 847861192
C19 plug, with 5-15P plug, 8’ CC848850792
C19 plug, with L6-20P plug, 8’ CC848850842
C19 plug, unterminated, 8’ CC848847368
DC output cable, 2 GA, 10’ 848748987
AC DC
J85480S1 Shelf
Ordering Guide
J85480S1 Converter Shelf
Ordering Guide
Compact Power Line, CPB-CPL | GECriticalPower.com 13
Converter (PEM) Options
CP2000DC54PEZ CC109162104
CP2500DC54PEZ1CC109170528
Rectier Slot Filler
CentralOceWhite CC848822263
Converter Shelf Options
List 14 CC109157657
Controller
CP841A_3C3R CC109145331
Slot Filler CC848847871
Mounting Brackets
1U bracket for 23”
frame mount
CC848844803
Wall mount bracket CC848864504
DC Output Cables
DC output cable,
2 GA 10’
848748987
DC Bus for 1/4”
Faston Connections
(2 required)
CC848886192
J2007001 Converter Shelf
Ordering Guide
Alarm and Communication Cables
15’ Alarm or distribution cable (J1 or J7) CC848865980
50’ Alarm or distribution cable (J1 or J7) CC848817651
150’ Alarm or distribution cable (J1 or J7) CC848817668
15’ Alarm input cable (J2) CC848853614
Shelf to shelf communication cable
(J3, J4)
CC848847780
Rectier Shelf Options
List 3 CC109147542
List 4 CC109140043
List 6 (Shown) CC109140027
Rectier
CP2000AC54TEZ CC109158440
CP2000AC54TEP CC109167565
CP2725AC54TEP CC109167532
CP2725AC54TEZ CC109149423
Rectier Slot Filler
CentralOceWhite CC848822263
Mounting Brackets
1U bracket for 23”
frame mount
CC848844803
2U bracket for 23”
frame mount
848683009
Wall mount bracket CC848864504
AC Input, DC Output Cables
C19 plug, with 5-15P plug, 8’ CC848850792
C19 plug, with L6-20P plug, 8’ CC848850842
C19 plug, unterminated, 8’ CC848847368
Molex Mini-Fit SR, unterminated,
8awg, 10’ (2 cables provided)
848710711
DC output cable, 2ga, 10’ 848748987
DC Bus Bar Strap (2 required) CC848844324
AC DC
J2007001 Shelf
Ordering Guide
Controller
CP841A-3C3R CC109145331
Compact Power Line, CPB-CPL | GECriticalPower.com
14
Power Module Output Power/Input Voltage Output Voltage Protection Physical
CP2000AC54TEZ/TEP 2000W / 200-277VAC
1200W / 100-120VAC Hardware set
44 - 58Vdc
Software set
42 - 58Vdc
15A breaker, 14 gauge wire
Length: 13.85”/351.8mm
Width: 4.00”/101.6mm
Height: 1.66”/42.2mm
Weight: 4.6lb/2.1kg
CP2500DC54PEZ 2500W / 40-72VDC 70A breaker, 8 gauge wire
CP2725AC54TEZ/TEP 2725W / 200-277VAC
1200W / 100-120VAC
20A breaker, 12 gauge wire
CP2000DC54-PE 2000W / 40-72VDC 60A breaker, 8 gauge wire
Mechanical J85480S-1 J2007001
Height 1.71inches/43.4mm 1.71 inches/43.4mm
Width (with mounting ears) 19 inches/483mm 19 inches/483mm
Depth 16.25 inches/413mm 17.06 inches/433mm
Weight(withoutrectiers) 9.25lbs/4.2kg 8.75lbs/4.0kg
Environmental J85480S-1 J2007001
Operating Temperature Range List 14: -40°C to 75°C (-40 to 167 °F)
Lists 20, 21:
-40°C to 25°C (-40 to 77 °F)
[Commercial 60°C C19 AC cord]
-40°C to 55°C (-40 to 131 °F)
[High Temp C19 AC cord]
Lists 23:
-40°C to 25°C (-40 to 77 °F)
[Commercial 60°C C13 AC cord]
-40°C to 55°C (-40 to 131 °F)
[High Temp C13 AC cord]
Lists 6:
-40°C to 25°C (-40 to 77 °F)
[Commercial 60°C C19 AC cord]
-40°C to 55°C (-40 to 131 °F)
[High Temp C19 AC cord]
Lists 3, 4: -40°C to 55°C (-40 to 131 °F)
Operating Relative Humidity 0 - 95% (non-condensing)
Storage Temperature Range -40°C to 85°C (-40 to 185 °F)
EMC FCC, EN 55022, CISPR22, Level A, conducted and radiated
Immunity EN55024 (CISPR24) Class A, conducted and radiated
Safety/Standards Compliance J85480S-1 J2007001
Safety Standards CAN/CSA C22.2 No. 60950-1-03, UL 60950-1, 1st Edition
VDE IEC 60950-1, 1st Edition
CerticationMarks Lists 14, 20, 21, 23 VDE
Lists 14 UL Recognized (Canada and U.S.)
Lists 20, 21, 23 UL Listed (Canada and U.S.)
Lists 4, 6 VDE
Lists 4 UL Recognized (Canada and U.S.)
Lists 6 UL Listed (Canada and U.S.)
Specications
Rectifiers
Shelves
NOTES: PE suffix denotes PoE compliance. Z suffix denotes RoHS 6 compliance. TE suffix denotes Total Efficiency* architecture.
Note: All GE CP AC cords are High Temperature cords.
Battery Management Accessories
A: QS873A Thermal Probe CC109142980
B: 10’ probe to controller wireset CC848817024
C: 1’ probe to probe wireset CC848822560
C: 5’ probe to probe wireset 848719803
C: 10’ probe to probe wireset CC848822321
ES771A Voltage Monitor Card 108958422
D: 2 ½ ‘ ES771A to probe wireset CC848791517
D: 6’ ES771A to probe wireset CC848797290
D: 10’ ES771A to probe wireset 848719829
G: 4’ ES771A to ES771A or controller wireset CC848791500
G: 10’ ES771A to ES771A or controller wireset 848652947
Compact Power Line, CPB-CPL | GECriticalPower.com 15
Notes
Compact Power Line, CPB-CPL, Rev. 03/14
*Trademark of General Electric Company. Copyright 2014 General Electric Company. All Rights Reserved.
GEreservestherighttomakechangestospecicationsofproductsdescribedatanytimewithoutnoticeandwithoutobligationtonotifyany
person of such changes.
601 Shiloh Road, Plano, TX 75074
+1 877 546 3243 (toll-free in North America)
+1 972 244 9288 (direct number)
info.criticalpower@ge.com
GECriticalPower.com
24/7 Technical Support
pe.techsupport@ge.com
Management Visibility
Galaxy Manager* software is the centralized visibility and control
component of a comprehensive power management system
designed to meet engineering, operations and maintenance needs.
The Galaxy Manager client-server architecture enables remote
access to system controllers across the power network.
Dashboard display with one-click access to management
information database
Trend analysis
Scheduled or on demand reports
Fault, configuration, asset, and performance management
Training
GE offers on-site and classroom training options based on
certification curriculum. Technical training can be tailored to
individual customer needs. Training enables customers and
partners to more effectively manage and support the power
infrastructure. We have built our training program on practical
learning objectives that are relevant to specific technologies or
infrastructure design objectives.
Service & Support
GE field service and support personnel are trusted advisors to our
customers – always available to answer questions and help with
any project, large or small. Our certified professional services team
consists of experts in every aspect of power conversion with the
resources and experience to handle large turnkey projects along
with custom approaches to complex challenges. Proven systems
engineering and installation best practices are designed to safely
deliver results that exceed our customers’ expectations.
Warranty
GE is committed to providing quality products and solutions. We
have developed a comprehensive warranty that protects you and
provides a simple way to get your products repaired or replaced as
soon as possible.
For full warranty terms and conditions please go to
www.gecriticalpower.com.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
GE (General Electric):
CP2000AC54TEZ CC848822263