Electrical Products Division
6801 River Place Blvd.
Austin, TX 78726-9000
http://www.3M.com/elpd Litho in USA.
© 3M 2002 78-8126-0492-0-A
IMPORTANT NOTICE
Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all r isks and liability
associated with such use.
Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture as of the date of purchase.
3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be,
at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will
not be liable for any loss or damage arising from this 3M product, whether direct, indirect, special, incidental or consequential
regardless of the legal theory asserted.
3M and Scotchlok are trademarks of 3M
Engineering Specification
Crimp-type terminals shall, electrically and mechanically,
connect to a pre-stripped end of a stranded copper wire:
and hav e a flat tongue portion with a central opening for
mounting around a scre w or stud.
The terminal line shall of fer tongue v ariations in hole
(stud) size (6, 8 10, etc.) and configuration (ring, fork,
block fork, flanged block fork, locking fork, etc.): and
barrel v ariations in wire (AWG) size (26-24*, 22-18,
16-14, 12-10, etc.) and construction (non-insulated brazed
seam, vinyl insulated b utted seam, n ylon insulated with
insulation grip, etc.). The terminal line shall ha v e
regulatory agenc y co verage (UL Listing, CSA
Certification). The terminal tongue shall be mark ed with
the wire range and manufacturer’s symbol ().
*Not UL Listed or CSA Certified.
The nylon-insulated, standard fork terminal with
insulation grip shall be tin-plated, annealed copper , with
the tongue having a specif ied stud slot (size 0 thru 10) and
a butted seam barrel with a tin plated brass, funnel entry
insulation grip, cov ered by a molded n ylon slee v e, color
coded and sized for a specified (AWG) wire range
(26-24*, 22-18, 16-14, 12-10).
Insulated terminals shall be UL Listed and CSA Certified
for 600 Volts maximum building wire: 1000 Volts
maximum in signs, fixtures and luminaires and ha v e a
maximum operating temperature of 221°F (105°C).