1Description
Primary switched power supply, 1-phase,
output current: 5 A
TRIO-PS/1AC/48DC/ 5
© PHOENIX CONTACT - 05/2008
Data Sheet
INTERFACE
TRIO POWER is the DIN-rail-mountable power supply unit
with basic functions. With an output voltage of 12 V DC,
24 V DC and 48 V DC and 1- and 3-phase versions with 60 W
or 960 W, it is particularly suited for use in series production
in mechanical engineering. The wide-range input and
international certification package allows worldwide
implementation.
The high MTBF of 500,000 h stands for high supply reliability.
The devices can be connected in parallel to increase the
capacity and redundancy.
The clear LED signaling and the device connection with
double terminal block for plus and minus for fast potential
distribution are further advantages of this device series. A
third terminal block simplifies the grounding on the secondary
side. All power supply units are idle proof and short circuit
proof and provide a regulated and adjustable output voltage.
DANGER OF EXPLOSION!
Only remove equipment when it is disconnected and not in the potentially explosive area.
DANGER
Components with dangerously high voltage and high stored energy are located in the device!
Never carry out work on live parts!
Depending on the ambient temperature and the load, the housing can become very hot!
Make sure you always use the the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
Reliable power supply unit even at high ambient
temperatures
No load and short circuiting resistance
High dielectric strength
Can be used worldwide in all industrial sectors due to a
wide-range input and an international approval package
103349_en_00
Features
TRIO-PS/1AC/48DC/ 5
103349_en_00 PHOENIX CONTACT 2
2Table of contents
1 Description ..................................................................................................................................1
2 Table of contents.........................................................................................................................2
3 Ordering data ..............................................................................................................................3
4 Technical data.............................................................................................................................3
5 Structure......................................................................................................................................6
6 Block diagram .............................................................................................................................7
7 Safety notes ................................................................................................................................7
8 Installation ...................................................................................................................................8
9 Installation position......................................................................................................................8
10 Mounting on DIN rails ..................................................................................................................9
Assembly ...................................................................................................................................................................9
Removing...................................................................................................................................................................9
11 Connection to various systems....................................................................................................9
12 Input .......................................................................................................................................... 10
Recommended backup fuse for mains protection....................................................................................................10
13 Output ....................................................................................................................................... 11
Protection of the secondary side..............................................................................................................................11
14 Signaling ................................................................................................................................... 11
15 Function .................................................................................................................................... 12
Output characteristic curve ......................................................................................................................................12
Thermal behavior.....................................................................................................................................................12
Parallel operation .....................................................................................................................................................12
Redundant operation ...............................................................................................................................................13
Increased performance............................................................................................................................................13
TRIO-PS/1AC/48DC/ 5
103349_en_00 PHOENIX CONTACT 3
Description Type Order No. Pcs.
Pkt.
Primary switched power supply, 1-phase, output current: 5 A TRIO-PS/1AC/48DC/ 5 2866491 1
Input data
Input nominal voltage range 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC
AC frequency range 45 Hz ... 65 Hz
Current consumption Approx. 2.5 A (120 V AC)
Approx. 1.3 A (230 V AC)
Inrush current limitation < 15 A
I2t< 0.7 A2s
Power failure bypass > 15 ms (120 V AC)
> 16 ms (230 V AC)
Typical response time < 1 s
Protective circuitry Transient surge protection Varistor
Recommended backup fuse for mains protection 10 A (characteristic B)
16 A (characteristic B)
Discharge current to PE < 3.5 mA
Output data
Nominal output voltage 48 V DC ±1%
Setting range of the output voltage 30 V DC ... 56 V DC (> 48 V constant capacity)
Output current 5 A (-25°C ... 70°C)
Derating Above +55°C: 2.5% per Kelvin
Current limitation Approx 5.7 A (in the event of a short circuit)
Max. capacitive load Unlimited
Control deviation < 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Power loss nominal load max. 28 W
Maximum power dissipation idling 3.5 W
Efficiency > 89 %
Ascent time < 2 ms (UOUT (10% ... 90%))
Residual ripple < 50 mVPP
Peak switching voltages < 50 mVPP
Connection in parallel Yes, for redundancy and increased capacity
Connection in series No
Surge protection against internal surge voltages yes, limited to approx. 60 V DC
Resistance to reverse feed 60 V DC
Signal output DC OK active
Status display "DC OK" LED green / UOUT < 0.9 x UN: LED flashing
3Ordering data
4 Technical data
TRIO-PS/1AC/48DC/ 5
103349_en_00 PHOENIX CONTACT 4
General data
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 2 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (type test)
Degree of protection IP20
Class of protection I, with PE connection
MTBF > 500 000 h in acc. with IEC 61709 (SN 29500)
Type of housing Steel sheet, zinc-plated
Side element version Aluminum
Dimensions W / H / D (state of delivery) 60 mm / 130 mm / 152.5 mm
Weight 1.1 kg
Ambient conditions
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25°C, no condensation)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6
15 Hz ... 150 Hz, 2.3g, 90 min.
Shock 15g in all directions in acc. with IEC 60068-2-27
Pollution degree in acc. with EN 50178 2
Climatic class 3K3 (in acc. with EN 60721)
Standards
Electrical Equipment for Machinery EN 60204 / Surge voltage category III
Safety transformers for power supply units EN 61558-2-17
Electrical safety (of information technology equipment) EN 60950/VDE 0805 (SELV)
EN 61558-2-17
Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV)
SELV EN 60950 (SELV)
EN 60204 (PELV)
Safe isolation DIN VDE 0100-410
DIN VDE 0106-1010
Protection against electric shock DIN 57100-410
Protection against electric shock, basic requirements for safe isolation in
electrical equipment
DIN VDE 0106-101
Limitation of mains harmonic currents EN 61000-3-2
Approvals
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950
TRIO-PS/1AC/48DC/ 5
103349_en_00 PHOENIX CONTACT 5
Conformance with EMC directive 2004/108/EC
Noise immunity according to EN 61000-6-2
Electrostatic discharge EN 61000-4-2
Housing Level 3
Contact discharge 6 kV
Discharge in air 8 kV
Comments Criterion B
Electromagnetic HF field EN 61000-4-3
Housing Level 3
Frequency range 80 MHz ... 3 GHz
Field intensity 10 V/m
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (level 4 - asymmetrical: conductor to ground)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
Comments Criterion B
Surge current loads (surge) EN 61000-4-5
Input 4 kV (level 4 - asymmetrical: conductor to ground)
2 kV (level 4 - symmetrical: conductor to conductor)
Output 1 kV (Level 3 - symmetrical: Conductor to conductor)
2 kV (level 3 - asymmetrical: conductor to ground)
Comments Criterion B
Conducted interference EN 61000-4-6
Input/output Level 3 - asymmetrical
Frequency range 10 kHz ... 80 MHz
Voltage 10 V
Comments Criterion A
Voltage dips EN 61000-4-11
Input (mains buffering > 10 ms)
Comments Criterion B
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
TRIO-PS/1AC/48DC/ 5
103349_en_00 PHOENIX CONTACT 6
5Structure
TRIO POWER
L
N
Input AC
100-240V
Output DC
48V 5 A
+
+
Adjust
30-56V
DC OK
1
3
6
2
4
5
1AC input
2DC output
3Potentiometer 30 V DC ... 56 V DC
4"DC OK" LED
5DIN rail adapter
6Take-up for cable binders
[mm2]AWG [Nm]
solid stranded Torque
Input 0.2 - 2.5 0.2 - 2.5 24 - 14 0.4 - 0.5
Output 0.2 - 2.5 0.2 - 2.5 24 - 14 0.4 - 0.5
Input data
Input nominal voltage range 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC (derating < 90 V AC: 2.5% per Kelvin)
AC frequency range 45 Hz ... 65 Hz
Recommended backup fuse for mains protection 10 A (characteristic B)
16 A (characteristic B)
Type of connection Screw connection
Stripping length 9 mm
Output data
Nominal output voltage 48 V DC ±1%
Setting range of the output voltage 30 V DC ... 56 V DC (> 48 V constant capacity)
Output current 5 A (-25°C ... 70°C)
Type of connection Screw connection
Stripping length 9 mm
TRIO-PS/1AC/48DC/ 5
103349_en_00 PHOENIX CONTACT 7
6Block diagram
L
N
PE
active
PFC
7Safety notes
DANGER OF EXPLOSION!
Only remove equipment when it is disconnected and not in the potentially explosive area.
DANGER
Components with dangerously high voltage and high stored energy are located in the device!
Never carry out work on live parts!
Depending on the ambient temperature and the load, the housing can become very hot!
CAUTION
Before startup please ensure:
The mains connection has been carried out by a competent person and protection against electric shock is
guaranteed!
The device can be disconnected outside the power supply unit in accordance with the regulations as in
EN 60950 (e.g. through primary side line protection)!
The ground conductor is connected!
All feed lines are sufficiently protected and dimensioned!
All output lines are dimensioned according to the maximum output current of the device or separately
protected!
Sufficient convection is guaranteed!
ATTENTION: Danger if used improperly
The power supply units are built-in devices. The device may only be installed and put into operation by qualified
personnel. The corresponding national regulations must be observed.
TRIO-PS/1AC/48DC/ 5
103349_en_00 PHOENIX CONTACT 8
8 Installation
TRIO POWER
L
N
Input AC
100-240V
Output DC
48V 5 A
+
+
Adjust
30-56V
DC OK
ATTENTION: Module can become
damaged
In order to guarantee sufficient convection, we
recommend observing the following minimum
distance to other modules: 5 cm in a vertical
direction and 0 cm in a horizontal direction.
The power supply unit can be snapped onto all
DIN rails in acc. with EN 60715 and must be
mounted vertically (connecting terminal blocks
on bottom).
9 Installation position
TRIO POWER
L
N
Input AC
100-240V
Output DC
48V 5 A
+
+
Adjust
30-56V
DC OK
60
50
115
230
130
Mounting position: Installation depth 152.5 mm (+ DIN rail)
TRIO-PS/1AC/48DC/ 5
103349_en_00 PHOENIX CONTACT 9
10 Mounting on DIN rails
A B
A
B
Assembly
Position the module with the DIN rail guide on the upper edge
of the DIN rail, and snap it in with a downward motion.
Removing
Pull the snap lever open with the aid of a screwdriver and slide
the module out at the lower edge of the DIN rail.
11 Connection to various systems
TN-S TN-C TT iT
L
N
PE
+
LN
-
PE
L
PEN
+
LN
-
PE
+
LN
-
PE
L
N
+-
LNPE
L1
L2
L3
The 100 V AC ... 240 V AC connection is made using the L, N and PE screw connections.
The device can be connected to 1-phase AC systems or to two of the phase conductors of three-phase networks (TN, TT or
iT system in acc. with VDE 0100-300/IEC 60364-3) with nominal voltages of 100 V AC ...240 V AC.
The device also continues to work on short-term input voltages > 300 V AC.
For operation on two of the phase conductors of a three-phase system, an isolating facility for all poles must be provided.
ATTENTION: Module can become damaged
In order to comply with the UL certification, use copper cables that are designed for operating temperatures of
>75°C.
In order to comply with EN 60950/UL 60950, flexible cables require ferrules. To safely connect a device, the
ferrules should have a length of at least 10 mm. To achieve a reliable and shockproof connection, strip the
connecting ends according to section "Structure".
TRIO-PS/1AC/48DC/ 5
103349_en_00 PHOENIX CONTACT 10
12 Input
TRIO POWER
L
N
Input AC
100-240V
Output DC
48V 5A
+
+
Adjust
30-56V
DC OK
The device must be installed in acc. with the regulations as in
EN 60950. It must be possible to disconnect the device using
a suitable isolating facility outside the power supply. Primary
circuit mains protection, for example, is suitable for this
purpose.
Recommended backup fuse for mains protection
Power circuit-breaker 10 A or 16 A, characteristic B (or
identical function).
ATTENTION: Module can become
damaged
If an external fuse is triggered, there is most
probably a malfunction in the device. In this
case, the device must be inspected in the
factory!
TRIO-PS/1AC/48DC/ 5
103349_en_00 PHOENIX CONTACT 11
13 Output
TRIO POWER
L
N
Input AC
100-240V
Output DC
48V 5A
+
+
Adjust
30-56V
DC OK
Output DC
48 V 5 A
+
+
The connection is made using the "+" and "-" screw
connections on the screw connection of the DC output. The
set output voltage is 48 V DC at the time of delivery. The
output voltage can be set on the potentiometer.
Protection of the secondary side
The device is electronically protected against short circuit and
idling. In the event of a malfunction, the output voltage is
limited to 60 V DC.
ATTENTION: Module can become
damaged
Make sure that all output lines are dimensioned
according to the maximum output current or are
separately protected. The cables on the
secondary side must have sufficiently large
cross sections in order to keep the voltage
drops on the lines as low as possible.
You can fasten the connection cables to the
housing using cable binders.
Ensure that the cable binders and the
connection cables are designed for the surface
temperatures that occur in operation.
Make sure that the insulation of the connection
cables is not damaged when tightening the
cable binders.
14 Signaling
The "DC OK" LED enables evaluation of the function of the power supply directly on site.
State 1 State 2
"DC OK" LED ON OFF
Cause Output voltage > 0.9 x UNOutput voltage > 0.9 x UN or no voltage at output
Meaning Output voltage and output
current OK
The device is in operation, but there is a fault in the
consumer, the current consumption is greater than IN or the
output is short circuited.
The device is out of operation because there is no mains
voltage, the fuse on the primary side has been triggered, or
the device is faulty.
TRIO-PS/1AC/48DC/ 5
103349_en_00 PHOENIX CONTACT 12
15 Function
I [A]
OUT
U [V]
OUT
U
N
I
N
Output characteristic curve
The device functions following the U/I characteristic curve.
Under load, the working point follows this curve. The output
current is limited in the event of a short circuit or overload.
Thereby, the device does not switch off, but rather supplies a
continuous output current.
The secondary voltage is reduced until the short circuit or
overload on the secondary side has been remedied. The U/I
characteristic curve ensures that both heavily capacitive
loads and loads with DC/DC converters in the primary circuit
can be supplied. Downstream fuses are triggered. Selectivity
in the design of your system is guaranteed at all times.
UN = 48 V
IN = 5 A
PN = 240 W
0
0
I
N
20 40 60
Ambient temperature [°C]
Output current [A]
Thermal behavior
With an ambient temperature of up to +55°C, the device
supplies the continuous output current of IN. In the case of
ambient temperatures above +55°C, the output current must
be reduced by 2.5% per Kelvin increase in temperature. The
device does not switch off at ambient temperatures of +70°C
or thermal overload. The output capacity is reduced as far as
necessary to provide device protection. After it has cooled
down, the output capacity is increased again.
Parallel operation
Devices of the same type can be connected in parallel to
enable both redundancy and an increase in efficiency. No
other alignment is necessary when in the state of delivery.
If the output voltage is adjusted, a uniform distribution of
power is guaranteed by setting all parallel operated power
supply units to exactly the same output voltage.
To ensure symmetrical distribution of power, we recommend
designing all cable connections from the power supply unit to
a busbar of the same length and with the same conductor
cross section. The system makes it advisable to install a
protective circuit at the output of each device when more than
two power supply units are connected in parallel (e.g.
decoupling diode or DC fuse). This prevents high reverse
feed currents in the event of a secondary device fault.
TRIO-PS/1AC/48DC/ 5
103349_en_00 13
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
+
IN
+
IN
+
+
Σ=I
N
Redundant operation
Redundant circuits are suitable for the supply of systems
which make especially high requirements on the operational
safety. If a fault occurs in the primary circuit of the first power
supply unit, the second device automatically takes over the
entire power supply, without interruption, and vice versa. For
this reason, the power supply units to be connected in parallel
are dimensioned in such a way that the total current
requirement of all consumers can be completely covered by
one power supply unit. 100% redundancy makes external
decoupling diodes necessary (QUINT-DIODE/40, Order No.
2938963)!
+
IN
+
IN
+
+
Σ=2xI
N
Increased performance
For n parallel connected devices, the output current can be
increased to n x IN. Parallel connection to increase efficiency
is used for the expansion of existing systems. It is advisable
to use parallel connection if the power supply unit does not
cover the current requirement of the most powerful
consumer. Otherwise the consumers should be spread
among individual devices independent of one another. A
maximum of five devices can be connected in parallel!