Amprobe® Test Tools
Data Sheet
ACDC-3400 IND CAT IV Industrial True RMS Clamp Meter
Specifications (valid for 23 °C ± 5 °C, for less than 75% relative humidity).
DC Volts Ranges Accuracy
660.0 mV, 6.600 V, 66.00 V, 660.0 V, 1000 V ± (0.5% rdg + 2 dgts)
Input impedance 660 mV: >100 MΩ; 6.6 V:10 MΩ; 66 V to 1000 V: 9.1 MΩ
Overload protection 1000 VDC or 750 VAC rms
AC Volts True RMS Ranges Frequency Accuracy
660.0 mV 50 to 100 Hz ± (1.5% rdg + 8 dgts)
6.600V, 66.00V 50 to 500 Hz ± (1.5% rdg + 8 dgts)
660.0V, 750V 50 to 500 Hz ± (1.5% rdg + 8 dgts)
Frequency* 50 to 1 kHz ± (0.1% rdg + 5 dgts)
* Frequency: 10% to 100% of voltage range
Peak Hold Ranges Frequency Accuracy
66.00V, 660.0V, 750V 50 to 500 Hz ± (3.0% rdg + 300 dgts)
AC coupled TRMS 5% to 100% of range
Crest factor ≤ 3
Input impedance 660 mV: >100 MΩ; 6.6 V:10 MΩ; 66 V to 750 V: 9.1 MΩ
Overload protection 1000 VDC or 750 VAC rms
AC Current True RMS Ranges Frequency Accuracy
660.0A 50 to 60 Hz ± (2.0% rdg + 10 dgts)
660.0A 61 to 400 Hz ± (3.0% rdg + 10 dgts)
1000 A 50 to 60 Hz ± (2.5% rdg + 10 dgts)
1000 A 61 to 400 Hz ± (3.5% rdg + 10 dgts)
Frequency* 50 to 1kHz ± (0.1% rdg + 5 dgts)
* Frequency: 10% to 100% of current range
Peak Hold Ranges Frequency Accuracy
660.0A, 1000A 50 to 400 Hz ± (3.0% rdg + 200 dgts)
AC coupled TRMS 5% to 100% of range
Crest factor ≤ 3
Overload protection 1000A AC
DC Current Range Accuracy
660.0A ± (2.0% rdg + 5 dgts)
1000A ± (3.0% rdg + 5 dgts)
Overload protection 1000A DC
Resistance Range Accuracy
660.0Ω, 6.600kΩ, 66.00kΩ, 660.0kΩ ± (1.0% rdg + 5 dgts)
6.600MΩ ± (2.0% rdg + 5 dgts)
66.00MΩ ± (3.5% rdg + 5 dgts)
Open circuit volts -0.8 Vdc typical , (-1.2 Vdc on 660 Ω range)
Overload protection 1000 VDC or 750 VAC rms