Switch mode Power Supply S8VS L-55
Power
Supplies
Switch mode Power Supply
S8VS
Visible and Slim New Din Rail Power Supply
Ultra-compact size (40 (W) × 95 (H) mm) (60-W Model)
Displayed on 3-digit, 7-segment LED shows many status
(voltage, current etc.) of power supply.
Approved standards: UL508/60950, CSA C22.2 No.14/60950,
EN50178 (=VDE0160), EN60950 (=VDE0806)
Model Number Structure
Model Number Legend
1. Power Ratings
060: 60 W
090: 90 W
2. Output voltage
24: 24 V
3. Configuration
None: Standard Power Supply
A: With maintenance forecast monitor
B: With total run time monitor
Ordering Information
123
S8VS- @@@@@@
Power ratings Type Output voltage Output current Model number
60 W Standard type 24 V 2.5 A S8VS-06024
With maintenance forecast monitor type S8VS-06024A
With total run time monitor type S8VS-06024B
90 W Standard type 3.75 A S8VS-09024
With maintenance forecast monitor type S8VS-09024A
With total run time monitor type S8VS-09024B
L-56 Switch mode Power Supply S8VS
Specifications
Ratings/Characteristics
Note: 1. Refer to the Engineering Data section on page 59 for details.
2. Displayed on 7-segment LED.
3. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (±1 digit for output voltage value)
4. Resolution of output load indication: 0.1 A, Precision of output load indication: ±5% (±1 digit for output load value)
5. Resolution of Peak-hold load indication: 0.1 A, Precision of Peak-hold load indication: ±5% (±1 digit for output load value), width of Peak-
hold load indication: 10 ms
Power ratings 60 W 90 W
Type
Item
Standard
Maintenance
forecast monitor
Total run time
monitor
Standard
Maintenance
forecast monitor
Total run time
monitor
Efficiency (typical) 78% min. 80% min.
Input Voltage 100 to 240 VAC (85 to 264 VAC)
Frequency 50/60 Hz (47 to 450 Hz)
Current 100 V input 1.7 A 2.3 A
200 V input 1.0 A 1.4 A
Power factor correction Conforms to EN61000-3-2 A-14
Leakage
current
100 V input 0.5 mA max.
200 V input 1.0 mA max.
Inrush current
(See note 1.)
100 V input 25 A max.
200 V input 50 A max.
Output Voltage adjustment range 10% to 15% (with V.ADJ)
Ripple 2.0% (p-p) max. (at rated input/output voltage)
Input variation influence 0.5% max. (at 85 to 264 VAC input, 100% load)
Load variation influence
(rated input voltage)
1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence
0.05%/°C max.
Start up time (See note 1.) 1,000 ms max.
(at rated input/output voltage)
500 ms max. 1,000 ms max.
(at rated input/output voltage)
500 ms max.
Hold time (See note 1.) 20 ms min. (at rated input/output voltage)
Additional
function
Overload protection (See note 1.)
105% to 160% of rated load current, inverted L drop, intermittent, automatic reset
Overvoltage protection (See note 1.)
Ye s
Output voltage indication (See note 2.)
No Yes (selectable) (See note 3.) No Yes (selectable) (See note 3.)
Output load indication (See note 2.)
No Yes (selectable) (See note 4.) No Yes (selectable) (See note 4.)
Peak-hold load indication (See note 2.)
No Yes (selectable) (See note 5.) No Yes (selectable) (See note 5.)
Maintenance forecast monitor
indication (See note 2.)
No Yes (select-
able)
No No Yes
(selectable)
No
Maintenance forecast
monitor output
No
Yes (open collector
output), 30 VDC max.,
50 mA max.
No
Total run time monitor
indication (See note 2.)
No Yes
(selectable)
No Yes
(selectable)
Total run time monitor
output
No
Yes (open collector
output), 30 VDC max.,
50 mA max.
Undervoltage alarm
indication (See note 2.)
No Yes (selectable) No Yes (selectable)
Undervoltage alarm output
terminals
No Yes (open collector output),
30 VDC max., 50 mA max.
Parallel operation No
Series operation Yes (with external diode)
Other Ambient temperature
Operating: Refer to the derating curve in Engineering Data. (with no icing or condensation) Storage: 25 to 65°C
Ambient humidity Operating: 25% to 85%; Storage: 25% to 90%
Dielectric strength 3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and GR terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and GR terminals; detection current: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance 100 M min. (between all outputs/ alarm outputs and all inputs/ GR terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (color: green)
Electromagnetic interference
Conforms to FCC Class A, EN50081-2
EMI Conforms to EN50081-2
Approved standards
UL: UL508 (Listing; Class 2: Per UL1310), UL60950
cUL: CSA C22.2 No.14, No.60950 (Class 2)
EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0806)
UL: UL508 (Listing), UL60950
cUL: CSA C22.2 No.14, No.60950
EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0806)
Weight 330 g max. 490 g max.
Switch mode Power Supply S8VS L-57
Power
Supplies
Connections
Block Diagram
Note: The circuits within the dotted line are for the S8VS-06024@ Model only.
Note: The circuits within the dotted line are for the S8VS-09024@ Model only.
+V
V
Detection
circuit
Photo coupler
Rectifier/smoothing circuit
Rectifier/smoothing circuit
(See note.)
Rectifier/
smoothing
circuit
Noise filter
AC (L)
INPUT
AC (N)
Drive control
circuit
DC OUTPU
T
Fuse 3.15 A
Overcurrent
circuit
Current detection
circuit
Arithmetic
operation circuit
Display circuit
Switch
Overvoltag
detection circuit
Inrush
current
protection
circuit
S8VS-06024 (60 W)
S8VS-06024A (60 W)
S8VS-06024B (60 W)
+V
V
Detection
circuit
Photo coupler
Photo coupler
Rectifier/smoothing circuit
Rectifier/smoothing circuit
Rectifier/
smoothing
circuit
Noise filter
Inrush
current
protection
circuit
AC (L)
INPUT
AC (N)
Drive control
circuit
Alarm
DC LOW
Yrs
Common
DC OUTPUT
Fuse 4.0 A
Overcurrent
circuit
Arithmetic
operation circuit
Display circuit
Switch
Overvoltag
detection circuit
(See note.)
Current detection
circuit
S8VS-09024 (90 W)
S8VS-09024A (90 W)
S8VS-09024B (90 W)
L-58 Switch mode Power Supply S8VS
Installation
60-W Model
S8VS-06024 S8VS-06024@
90-W Model
S8VS-09024 S8VS-09024@
Note: 1. The fuse is located on the (L) side.
2. S8VS-@@@24@ only.
3. S8VS-09024@ Model only.
1
3
2
4
5
1
3
2
4
8
76
5
3
1
2
4
5
3
1
13
12
11
2
4
5
8
9
76
10
3
No. Name Function
1 AC Input terminals
(L), (N)
Connect the input lines to these
terminals. (See note 1.)
2 Ground terminals
(GR)
Connect the ground line to this terminal.
3 DC Output terminals
(V), (+V)
Connect the load lines to these
terminals.
4 Output indicator
(DC ON: Green)
Lights while a direct current (DC) output
is ON.
5 Output voltage
adjuster (V.ADJ)
Use to adjust the voltage.
6 Main display
(See note 2.)
Indicates the measurement or set value.
7 Operation
indicator
(See note 2.)
V Lights up when the output voltage is
indicated. Blinks during setup of
undervoltage alarm value.
A
Lights up during indication of output current.
Apk
Lights up during indication of peak hold current.
Yrs
Lights up during indication of maintenance
forecast monitor. Blinks during setup of
maintenance forecast monitor setting.
(S8VS-0024A)
Kh Lights up during indication of total run
time monitor. Blinks during setup of total
run time monitor. (S8VS-0@024B)
No. Name Function
8 Mode Key (See note 2.) Use the Mode Key to change the
indicated parameter or reset the
peak hold current value.
9 Up Key (See note 3.)
Use the Up Key to change to the
setting mode or to increase the set
value.
10 Down Key (See note 3.) Use the Down Key to change to
the setting mode or to decrease
the set value.
11 Alarm
output
terminal
Undervoltage alarm
output terminal (DC
LOW) (See note 3.)
Outputs when a drop in the
output voltage is detected.
(at voltage drop: OFF)
12
Maintenance forecast
monitor terminal (Yrs)
(S8VS-09024A)
Total run time monitor
output terminal (Kh)
(S8VS-09024B)
(See note 3.)
Outputs when the maintenance
forecast has reached the set
value.
13 Common terminal
for alarm output
(See note 3.)
Terminal (emitter) shared for
alarm outputs (11) and (12).
Switch mode Power Supply S8VS L-59
Power
Supplies
Engineering Data
Derating Curve
Installation
Note: 1. Use standard mounting only. Using any other mounting
method will prevent proper heat dissipation and may result
in deterioration or damage of internal elements. Or, the re-
maining service life notice function cannot work properly.
2. If there is a derating problem, use forced air-cooling. The
ambient temperature is specified for a point 50 mm below
the power supply.
Overload Protection
The Power Supply is provided with an overload protection function
that protects the load and the power supply from possible damage by
overcurrent. When the output current rises above 105% min. of the
rated current, the protection function is triggered, decreasing the out-
put voltage. When the output current falls within the rated range, the
overload protection function is automatically cleared.
Note: Do not allow the short-circuited or overcurrent state to continue
for more than 20 s, otherwise internal elements may deteriorate
or be destroyed.
Overvoltage Protection
The Power Supply is provided with an overvoltage protection function
that protects the load and the Power Supply from possible damage
by overvoltage. When an excessive voltage is output, the output volt-
age is shut OFF. Reset the Power Supply by turning it OFF for at
least three minutes and then turning it back ON again.
Note: Do not turn ON the power again until the cause of the overvolt-
age has been removed.
Inrush Current, Start Up Time,
Hold Time
20 10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
Load (%)
Ambient temperature (˚C)
Upper Upper
Standard mounting Face-up mounting
0 50 100
Intermittent operation
Output current
(
%
)
Output voltage (V)
+15%
10%
0V
Overvoltage protection
operating
Variable range
Rated output
voltage
Output voltage (V)
90%
96.5%
Start up time (1,000 ms max.)
Hold time (20 ms min.)
AC input
voltage
AC input
current
Output
voltage
Inrush current on input application
Input OFF
Input ON
L-60 Switch mode Power Supply S8VS
Undervoltage Alarm Function (Indication and Output)
When output voltage drop is detected, an alarm (a01) and lowest
output voltage value are indicated alternately. The preset value of
detection voltage can be changed in the setting mode.
(S8VS-06024@: The value of detection voltage is fixed at 20V)
Further, the alarm is output from the transistor ((11) DC LOW) to an
external device with the S8VS-09024A/B.
(Upon output voltage alarm: OFF; with no continuity across (11) and
(13))
:
Note: 1. Operation begins after about two seconds since the AC
power is supplied.
2. The alarm is not indicated in the setting mode.
3. Press the ((8) Mode Key) after the output voltage is re-
stored, to reset alarm indication.
4. The undervoltage alarm function monitors the output termi-
nal voltage of the power supply unit. To check the voltage
accurately, measure the voltage at the load end.
Note: Operation begins after about three seconds since the AC pow-
er is supplied.
Engineering Data (S8VS-@@@24@ Only)
Mode Change
Note: No setting mode is provided for the S8VS-06024@.
Operation Mode
Various states of the power supply unit are indicated.
Note: The output voltage will be displayed when the power supply is
first turned on after it is received from the factory. Thereafter,
the output voltage will be indicated in the same display when
shutting down.
In the case that the
output voltage drops
below the set value (19V)
and an alarm is issued
AC input
Output
voltage
Undervoltage
output
Main display Voltage indication
Detection value
of Undervoltage
alarm
Operation
mode
Lowest value of
output voltage
Power-ON
Operation mode
Key Press and hold for
three seconds or more.
Or no key operation for 30 seconds or more.
Model indication
Setting mode
Press and hold
Up or Down Key for
three seconds or more.
Output voltage
Output current
Peak hold current
Maintenance forecast monito
r
(S8VS-@@@24A)
or total run time monitor
(S8VS-@@@24B)
Switch mode Power Supply S8VS L-61
Power
Supplies
Setting Mode
(Except for S8VS-06024@)
Set various parameters of the power supply unit.
Note: 1. Press and hold the (9) Up Key or (10) Down Key for two sec-
onds or more to increase or decrease the value rapidly.
2. The S8VS-06024@ is not provided with the setting mode
and its parameters are fixed at the shipment setting.
Peak Hold Current Reset
Note: The peak hold current value is not reset in the setting mode.
Total Run Time Monitor
Indication and Alarm Output
(S8VS-@@@24B)
The cumulative running hours of the power supply unit are monitored
as total run time. When the total run time reaches the predetermined
alarm set value, an alarm (a02) and the total run time monitor are
indicated alternately with an output issued from the transistor ((12)
Kh) to an external device. (The output is turned off when the total run
time reaches the alarm set value; with no continuity across (12) and
(13).)
The alarm set value can be changed in the setting mode.
Note: 1. The total run time cannot be reset. To reset the alarm, in-
crease the alarm set value beyond the value indicated as to-
tal run time.
Ex.) If a customer decided to change the load at 5,000
hours, when they turn the unit again the timing will start at
5,000 hours and on.
2. The alarm function (setting, indication, and output) is not
provided for S8VS-06024B.
Self-Diagnostics Function
Note: 1. External noise is probable as a cause of ---, e01 , e02 and e03 errors.
2. Operation out of the derating curve area, ventilation error, and incorrect mounting direction are probable as a cause of h%t error.
3. If the h%t error state continues for about three hours, the maintenance forecast monitor function (S8VS-@@@24A only) becomes invalid.
The indication for maintenance forecast monitor remains as h%t even after the overheat condition is removed, and the Yrs output (12)
remains OFF (with no continuity across (12) and (13)).
Replace the power supply if this condition occurs even if the output is correct, as internal parts may be deteriorated.
4. The h%t error detection function is only for the S8VS-@@@24A.
*
*
*
Undervoltage
alarm
Maintenance
forecast monitor
(S8VS-09024A)
or Total run time
monitor alarm
(S8VS-09024B)
18.5 t o 20.0 t o 27.5 (V)
0.1V intervals
* The reverse video indicate
s
the shipment setting.
0.5 year intervals
0.0 t o 0.5 to 5.0 (years)
1 kh intervals
1 to 50 to 150 (kh)
Operation mode
Peak hold current
value measurement
starts
Reset
2 seconds
Key 3 seconds or more
In the case that the total
run time reaches the
set value (88kh) and an
alarm is issued
(6) Main display Description Output state Restoration method
Setting after restoration
--- Noise detected in voltage or current No change Automatic restoration No change
h%t Overheated (12) OFF Automatic restoration No change
e01 Undervoltage alarm set value memory
error
(11) OFF Press and hold the (9) Up Key or (10)
Down Key for three seconds and check
the set value of the corresponding point.
The set value must return to the
shipment setting
Shipment setting or
value set in the setting
mode again
e02 Memory error of alarm set value of
maintenance forecast monitor or total
run time monitor
(12) OFF
e03 Other memory error (11) (12) OFF Turn the AC input off then on again.
If the product is not reset, contact the
dealer.
No change
L-62 Switch mode Power Supply S8VS
Undervoltage Alarm Indication
This indicator lights when the output voltage is insufficient.
Note: The display changes to the output voltage display when the
voltage is restored to the set value or higher.
Multiple Alarms
When two or more different alarms occur at the same time
Maintenance Forecast
Displays when the maintenance forecast has reached the set value.
Indication and Output
When the product is purchased, ful will be indicated. As electro-
lytic capacitors deteriorate, indication changes to hlf. After the
remaining time to maintenance is reduced to two years, indication
automatically changes to a value, which decreases from 1.5 to 1.0
to 0.5 to 0 (year) as the running hours increase.
If the maintenance forecast monitor setting is set to a value larger
than two years, value indication automatically begins after the
remaining time to maintenance is reduced to the set years.
If the remaining time becomes smaller than setting L (which can be
set arbitrarily between 0 and 5.0 years), an alarm (a02) and the
remaining time are indicated alternately.
With the S8VS-09024A, an output is given to an external device from
a transistor ((12) Yrs) to notify of the replacement timing, together
with indication. (The output is turned off after the replacement timing
is reached; with no continuity across (12) and (13).)
Note: 1. The remaining time to maintenance is based on continuous
operation, not including the time when the power supply is
turned off, and so may take longer to reach than the actual
time indicated.
2. Until the power supply has been turned for about one month
in total, indication is fixed at ful to estimate the extent of
deterioration, while the output remains turned on (with con-
tinuity across (12) and (13)).
*
Operation
Mode
Output
current
Peak-hold
current
Maintenance
forecast
monitor
Undervoltage
alarm
Undervoltage occurs.
Output voltage lower limi
t
* This indicator alternately
displays alarm ( )
and the output voltage
lower limit.
*
*
Operation Mode
Undervoltage
alarm
Maintenance
forecast monitor
The indication shifts
alternately in the direction
of the arrow every 2 s.
* When undervoltage alarm is indicated: Press output load indication
When the maintenance forecast monitor or overheat alarm is indicated:
Press undervoltage alarm indication
*
Operation
Mode
Output
voltage
Maintenance
forecast
monitor
Remaining time
until replacement
The maintenance forecast
has reached the set value.
Output
current
Peak-hold
current
* This indicator alternately
displays alarm ( )
and the maintenance
time until replacement.
In the case that the
remaining time is reduced
to smaller than 0.5 year
and an alarm is issued.
Switch mode Power Supply S8VS L-63
Power
Supplies
Maintenance Forecast Monitor Function
The power supply unit is equipped with electrolytic capacitors.
The electrolyte inside the electrolytic capacitor penetrates the seal-
ing rubber and evaporates as time passes since it is manufactured,
which causes deterioration of characteristics such as decreasing the
capacitance, etc.
Due to this deterioration of the characteristics of the electrolytic
capacitor, the power supply unit decreases its performance as time
passes.
The maintenance forecast monitor function shows an approximate
period left for maintenance of the power supply unit due to deteriora-
tion of electrolytic capacitors. When the period left for maintenance
that the power supply forecasts reaches the set value, an alarm is
indicated and an output signal is triggered.
Use this function to know the approximate replacement timing of the
power supply unit.
Note: The maintenance forecast monitor function indicates an ap-
proximate period left for maintenance, based on deterioration
of the electrolytic capacitor. It does not predict failures caused
by other reasons.
Relationship Between Indicated Values and Output of Set Values
Principle of Operation
The deterioration speed of the electrolytic capacitor varies consider-
ably according to the ambient temperature. (Generally the speed fol-
lows Rule of Two for every 10°C; for every 10°C increase in
temperature the rate of degradation doubles according to Arrheniuss
equation.) The S8VS-0@024A monitors the temperature inside the
power supply, and calculates the amount of deterioration according
to the running hours and inside temperature. Judging by this amount
of deterioration, the power supply will give the alarm indication and
output when the period left for maintenance reaches the set value.
Note: 1. Due to degradation of internal electronic parts, replace the
power supply at least once every 15 years even if indication
and output of maintenance forecast monitor are not issued.
2. The maintenance forecast is accelerated or decelerated ac-
cording to operating conditions. Periodically check indica-
tion.
Reference Value
Note: The maintenance forecast is the service life (the power sup-
plys internal temperature is monitored at all times) of the inter-
nal electrolytic capacitor in actual operating conditions, and
varies according to the customers operating conditions. 15
years is taken as the maximum period of the maintenance fore-
cast.
(L0.5)
5.0
L=2.5
L=0.5
2.5 2.0 1.5 1.0 0.5 0
Initial capacity
"1.0" is displayed on the main display for the
duration that the maintenance forecast up to
replacement satisfies the condition 1.0 T < 1.5.
L: Maintenance forecast set value
(See note.) 0.0 to 5.0, 0.5 steps
In case of setting L between 2.5 and 5 years.
Maintenance forecast monitor output
T: Maintenance time
until replacement
The numerical value
decreases with time.
Main displayCapacity of Capacitor
Capacity level
at replacement
Note: This function can be set only on the S8VS-09024A Model.
Item Value Definition
Reliability
(MTBF)
135,000 hrs
min.
MTBF stands for Mean Time Between
Failures, which is calculated according to
the probability of accidental device fail-
ures, and indicates reliability of devices.
Therefore, it does not necessarily repre-
sent a life of the product.
Life
expectancy
10 yrs. min. The life expectancy indicates average op-
erating hours under the ambient tempera-
ture of 40°C and a load rate of 50%.
Normally this is determined by the life ex-
pectancy of the built-in aluminum electro-
lytic capacitor.
L-64 Switch mode Power Supply S8VS
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Note: The photo is the S8VS-06024A Model.
Note: The photo is the S8VS-09024A Model.
DIN Track (Order Separately)
Note: All units are in millimeters unless otherwise indicated.
Mounting Track (Material: Aluminum)
Mounting Track (Material: Aluminum)
97
11.3
35.4
108.3
140
10
74 95
Five, M4
with square washer
Track stopper
4.5
(Sliding: 15 max.)
S8VS-06024 (60 W)
S8VS-06024A (60 W)
S8VS-06024B (60 W)
110.5
10.8
34.9
121.3
1
94 115
10
50
Five, M4
with square washer
Track stopper
Screwless block (2.5 mm pitches)
4.5
(Sliding: 15 max.
)
S8VS-09024 (90 W)
S8VS-09024A (90 W)
S8VS-09024B (90 W)
4.5
15 25 25
10 10
1,000 (500) *
25 25 15(5) *
35±0.3
7.3±0.15
27±0.15
1
*Values in parentheses
are for the PFP-50N.
PFP-100N
PFP-50N
4.5
15 25 25
10 10
1,000
25 25 15 1 1.5
29.
242735±0.3
16
PFP-100N2
Switch mode Power Supply S8VS L-65
Power
Supplies
Precautions
!Caution
Do not disassemble the product or touch internal parts.
Electric shock may be caused.
Do not touch the product during power-on, and immediately after
poweroff. Hot surface may cause heat injury.
Tighten the terminal screw with torque 1.08 N·m.
A loose screw may cause fire.
Install the terminal cover.
Electric shock may be caused if not installed.
Mounting
Be sure to allow convection in the atmosphere around devices when
mounting. Do not use in locations where the ambient temperature
exceeds the range of the derating curve.
When cutting out holes for mounting, make sure that cuttings do not
enter the interior of the products.
Before turning the Power Supply ON, be sure to remove sheets that
were used as covers during mounting, and make sure that heat
release is not obstructed.
Wiring
Ground the product (GR) completely. Failure to do so could cause
electric shock or malfunction.
Ensure that input and output terminals are wired correctly.
Do not apply more than 100N force to the terminal block when tight-
ening it.
Be sure to remove the sheet covering the product for machining
before power-on.
Recommended Wire Type
Installation Environment
Do not use the Power Supply in locations subject to shocks or vibra-
tions. In particular, install the Power Supply as far away as possible
from contactors or other devices that are a vibration source.
Install the Power Supply well away from any sources of strong, high-
frequency noise.
Operating and Storage Environments
Do not use or store the Power Supply in the following locations.
Doing so may result in failure, malfunction, or deterioration of perfor-
mance characteristics.
Do not use in locations subject to direct sunlight.
Do not use in locations where the ambient temperature exceeds
the range of the derating curve.
Do not use in locations where the humidity is outside the range
25% to 85%, or locations subject to condensation due to sudden
temperature changes.
Do not store in locations where the ambient temperature is outside
the range 25 to 65°C or where the humidity is outside the range
25% to 90%.
Do not use locations where liquids, foreign matter, corrosive gases,
or flammable gases may enter the interior of products.
S8VS-@@@24A Model Only
Satisfy the following conditions when storing the Power Supply for
long periods of time to maintain its remaining service life function.
When storing for more than three months, store within an ambient
temperature range of 25 to +30°C and the humidity range of 25 to
70%.
Periodic Inspection (S8VS-09024A
Model Only)
Under general operating conditions, the remaining service life func-
tion starts to work from several to ten and several years after start of
use. When the Power Supply is used for long periods of time, peri-
odically follow the procedure below to check that the remaining ser-
vice life function ((12)Yrs) is working properly.
1. Set to the Power Supply to the Run Mode.
2. Make sure that output ((12)Yrs) is ON (electrical continuity across
terminals (12) and (13)).
3. In the Run Mode, hold down the Down Key (10) and the Mode
Key (8) for at least three seconds at the same time.
The main display ((6)) changes to a02.
This function is working properly if output ((12)Yrs) is OFF (no
electrical continuity across terminals (12) and (13)).
4. Release the key to return to the regular mode.
Note: DC output is also maintained during periodic inspection.
Model Recommended wire size
S8VS-06024@AWG14 to 20
(Cross section 0.517 to 2.081mm2)
S8VS-09024@AWG14 to 18
(Cross section 0.823 to 2.081mm2)
Alarm output terminal: AWG22 to 28
(Cross section 0.081 to 0.326mm2)
*1
*1
*2
*1. Convection of air
*2. 20 mm min.
1
13
12
11
2
4
5
8
9
76
10
3
L-66 Switch mode Power Supply S8VS
Charging the Battery
If a battery is to be connected as the load, mount an overcurrent lim-
iting circuit and an overvoltage protection circuit.
Output Voltage Adjuster
Do not add unnecessary power. The output voltage adjuster (V.ADJ)
may be damaged.
DIN Track Mounting
To mount the Block on a DI track, hook portion (A) of the Block
onto
the track and press the Block in direction (B).
To dismount the Block, pull down portion (C) with a flat-blade screw-
driver and pull out the Block.
Series Operation
Two power supplies can be connected in series.
The (±) voltage output can be accomplished with two power supplies.
Note: 1. Connect the diode as shown in the figure. If the load is
short-circuited, a reverse voltage may be applied inside the
power supply unit, causing deterioration or breakage of the
power supply unit.
Select a diode having the following ratings.
2. Though products having different specifications can be con-
nected in series, the current flowing through the load must
not exceed the smaller rated output current.
Parallel Operation
The product is not designed for parallel operation.
In Case There is No Output Voltage
The possible cause for no output voltage may be the presence of an
overload or overvoltage condition, or may be due to the functioning of
an latching protective device. The latching protection may operate if
a large amount of surge voltage such as a lightening surge occurs
while turning on the power supply.
In case there is no output voltage, please check the following points
before contacting us:
Check the Overload Protected Status:
Check whether the load is in overload status or is short-circuited.
Remove wires to load when checking.
Attempt to clear the overvoltage or latching protection function:
Turn the power supply off once, and leave it off for at least 3 min-
utes. Then turn it on again to see if this clears the condition.
B
A
C
30 mm min.
Track stopper
+V
V
+V
V
AC (L)
AC (N)
AC (L)
AC (N)
Type Schottky Barrier diode
Dielectric strength
(VRRM)
Twice the rated output voltage or
above
Forward current
(IF)
Twice the rated output current or
above
+V
V
+V
V
AC (L)
AC (N)
AC (L)
AC (N)
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. T026-E1-01
Switch mode Power Supply S8PS L-67
Power
Supplies
Switch mode Power Supply
S8PS
The Most Compact DIN-track-mounting
Switch mode Power Supplies Ever with
Capacities Up to 600 W
Power range from 50 W up to 600 W.
Open-frame and covered types available.
Easily mounted to DIN track with provided Mounting Brackets.
Models with Front-mounting Bracket available.
Conforms to EMC standards: EN50081-1, EN50082-2, and
EN61000-3-2.
Maintenance-free up to 300 W due to natural ventilation.
Protection-ON alarm indicator shows valuable protection func-
tions in action (300-/600-W models).
AC universal input: 100 to 240 VAC
Approved by UL/CSA standards, EN60950 (IEC950), and
VDE0160.
Six-language instruction manual provided.
Life expectancy of 10 years min.
Finger protection terminal block meets VDE0106/P100. (Cov-
ered type)
Model Number Structure
Model Number Legend
1. Power Ratings
050: 50 W
100: 100 W
150: 150 W
300: 300 W
600: 600 W
2. Output Voltage
05: 5 V
12: 12 V
24: 24 V
3. Configuration
C: Covered type with Front-mounting Bracket
D: Open-frame type with DIN Track Mounting Bracket
CD: Covered type with DIN Track Mounting Bracket
None: Open-frame type with Front-mounting Bracket
Ordering Information
List of Models
S8PS-@@@@@@@
1 2 3
Configuration Input voltage Power ratings Output voltage Output current Front-mounting
Bracket
DIN Track Mounting
Bracket
Covered type 100 to 240 VAC 50 W 5 V 10 A S8PS-05005C S8PS-05005CD
12 V 4.2 A S8PS-05012C S8PS-05012CD
24 V 2.1 A S8PS-05024C S8PS-05024CD
100 W 24 V 4.5 A S8PS-10024C S8PS-10024CD
150 W 24 V 6.5 A S8PS-15024C S8PS-15024CD
300 W 24 V 14 A S8PS-30024C S8PS-30024CD
600 W 24 V 27 A S8PS-60024C ---
Open-frame type 100 to 240 VAC 50 W 5 V 10 A S8PS-05005 S8PS-05005D
12 V 4.2 A S8PS-05012 S8PS-05012D
24 V 2.1 A S8PS-05024 S8PS-05024D
100 W 24 V 4.5 A S8PS-10024 S8PS-10024D
150 W 24 V 6.5 A S8PS-15024 S8PS-15024D
L-68 Switch mode Power Supply S8PS
Specifications
Ratings/Characteristics
Note: 1. 100% load for rated input voltage (100 VAC or 200 VAC)
2. Do not press down on the terminal block with a force exceeding 75 N while tightening the terminals.
3. MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates
reliability of devices. Therefore, it does not necessarily represent a life of the product.
4. The life expectancy shown in the above table indicates average operating hours under the ambient temperature of 40°C and a load rate
of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. It must be noted that the life
expectancy of the fan built into the 600-W model is not included.
5. The weight indicated is for the open-frame type. (Includes the cover for 300-W and 600-W models.)
Item 50 W 100 W 150 W 300 W 600 W
Efficiency (typical) 75 to 87% (depends on the model)
Input Voltage 100 to 240 VAC (85 to 264 VAC)
Frequency 47 to 450 Hz
Current (see note 1) 0.9 or 0.45 A
max.
1.8 or 0.9 A
max.
2.7 or 1.4 A
max.
5.4 or 2.7 A
max.
10 or 5 A max.
Power factor (see note 1) 0.95 TYP.
Leakage current (see note 1) 0.5 or 1.0 mA max.
Inrush current (25°C, cold start) (see note 1) 25 or 50 A max.
Output Voltage adjustment range 5% to 10%
Ripple (see note 1) 2% (p-p) max.
Input variation influence 0.4% max. (at 85 to 132 VAC input/at 170 to 264 VAC input, 100% load)
Load variation influence 0.8% max. (with rated input, 0 to 100% load)
Temperature variation influence (see note 1) 0.05%/°C max.
Rise time 1,000 ms max. (up to 90% of output voltage at rated output voltage/current)
Hold time (see note 1) 20 ms min.
Additional
function
Overload protection 105% min., voltage trailing intermittent operation
(With the 600-W model, output is turned OFF at 5 s min.)
Overvoltage protection Ye s
Overheat protection No Yes
Protection-ON alarm indicator No Yes (Red)
Parallel operation No Yes, 2 units max.
Other Heat radiation Natural air-cooling Fan
Ambient temperature Operating: See the derating curve in the Engineering Data section. (with no condensation
nor icing)
Storage: 25°C to 65°C (with no condensation nor icing)
Ambient humidity 25% to 85%
Dielectric strength 3.0 kVAC, 50/60 Hz for 1 min (between all inputs and outputs)
2.2 kVAC, 50/60 Hz for 1 min (between all inputs and GR terminals)
1 kVAC, 50/60 Hz for 1 min (between all outputs and GR terminals)
Insulation resistance 100 M min. (between all output and input/GR terminals at 500 VDC)
Vibration resistance 10 to 55 Hz, 0.75-mm amplitude for 2 h each in X, Y, and Z directions
Shock resistance 300 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (green)
Terminal screw tightening torque 1.08 N·m (see note 2)
Electromagnetic interference Conforms to FCC Class B, EN50081-1
EMC (EMI): EN50081-1
Emission Enclosure: EN55022 class B
Emission AC Mains: EN55022 class B
Harmonic Current: EN61000-3-2
(EMS): EN50082-2
Immunity ESD: EN61000-4-2: 4-kV contact discharge (level 2)
8-kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2-kV power-line (level 3)
2-kV output line (level 4)
Immunity Surge: EN61000-4-5: between 3-kV lines
between 4.5-kV line and FG
Approved standards UL508, UL1012, CSA C22.2 No. 950, CSA C22.2 No. 14, EN60950, VDE0160.
Conforms to UL1950 and CSA E.B. 1402C
Reliability (MTBF) (see note 3) 135,000 hrs min. 60,000 hrs min.
Life expectancy (see note 4) 10 yrs. min. (Used at 40°C at the rated input with a 50% load, standard installation)
Weight (see note 5) 420 g max. 600 g max. 900 g max. 2,200 g max. 3,500 g max.
Mounting method Front-mounting Bracket or DIN Track Mounting Bracket Front-mounting Bracket
Switch mode Power Supply S8PS L-69
Power
Supplies
Connections
Block Diagrams
AC(L)
AC(N)
+V
V
AC(L)
AC(N)
AC(L)
AC(N)
+V
V
+V
V
DC OUT
Noise filter
Rectifier
Detector
INPUT
S8PS-050@@@@ (50 W)
S8PS-60024C (600 W)
DC OUTINPUT
Fuse* Noise filter
Rectifier
Detector
Control circuit
INPUT Noise filter
Rectifier
DC OUT
Fan
Detector
Control circuit
Fuse
(4 A)
Inrush current
protection circuit
Overload
detection circuit
Harmonic
current
control
Smooth-
ing
Drive control
circuit
Rectifier/
smoothing
circuit
Overload
detection circuit
Rectifier/
smoothing
circuit
Overload
detection circuit
Smooth-
ing
Harmonic
current
control
Inrush current
protection circuit
Overload
detection circuit
*Fuse capacity
100-W: 6.3 A
150-W: 6.3 A
300-W: 8 A
S8PS-10024@@ (100 W)
S8PS-15024@@ (150 W)
S8PS-30024@@ (300 W)
Fuse
(15 A)
Inrush current
protection circuit Harmonic cur-
rent control Smooth-
ing Rectifier/
smoothing
circuit
Overcurrent
detection
Overheat
detection
Overload
detection circuit
L-70 Switch mode Power Supply S8PS
Installation
4
5
1
3
2
4
5
1
3
2
50-W Models 100-/150-W Models
4
5
1
6
2
3
451
62 3
300-W Models 600-W Models
1. DC Output Terminals: Connect the load lines to these terminals.
2. Input Terminals: Connect the input lines to these terminals.
Note: A fuse is inserted into the AC (L) side.
3. Ground Terminal (GR): Connect a ground line to this terminal.
4. Output Indicator (DC ON): Lights while a Direct Current (DC) output is ON.
5. Output Voltage Adjuster (V.ADJ): It is possible to increase or decrease the output voltage by 10%.
6. Protection-ON Alarm Indicator: The red indicator will be lit if the overvoltage (for a 300-/600-W model) or overheat protection (for a
600-W model) circuit is triggered. This indicator will also be lit when overcurrent (for a 600-W model) is detected.
Switch mode Power Supply S8PS L-71
Power
Supplies
Engineering Data
Derating Curve
20 mm min.
Open-frame Type Covered Type
Load (%)
Ambient temperature (°C)
Load (%)
Ambient temperature (°C)
20 mm min. 20 mm min. 20 mm min. 20 mm min.
30 mm min. 30 mm min. 20 mm min.20 mm min.
30 mm min. 30 mm min. 20 mm min. 20 mm min.
20 mm min. 20 mm min. 20 mm min. 20 mm min.
20 mm min. 20 mm min. 20 mm min. 20 mm min.
30 mm min. 30 mm min. 20 mm min. 20 mm min.
50- to 150-W Model
Forced air-cooling
50- to 150-W Model
Natural air-cooling
50- to 300-W Model
Forced air-cooling,
600-W Model
50- to 300-W Model
Natural air-cooling
Note: 1. Forced air-cooling must be provided with an air volume of 1 m3/mm min.
2. The derating curve shown is for standard installation. The derating curve depends on the mounting direction of the Power Supply.
Standard Installation
50-W Model
Standard Installation
100/150-W Model
Standard Installation
300-W Model
Standard Installation
600-W Model
L-72 Switch mode Power Supply S8PS
Overload Protection
50- to 300-W Models
The Power Supply is provided with an overload protection function
that protects the load and the power supply from possible damage by
overcurrent. The protection function operates when the load current
rises above an overcurrent set value (105% of the rated load cur-
rent). For a short-circuit or overcurrent lasting less than 20 seconds,
output voltage is decreased to protect equipment. When the output
current falls within the rated range, the overload protection function is
automatically cleared.
Note: Do not continue using the S8PS under short-circuited or over-
current conditions for longer than 20 seconds, otherwise the in-
ternal elements of the S8PS may be damaged or broken.
600-W Models
If an excessive current flows for 5 s or more, the output will be turned
OFF and simultaneously protection-ON alarm indicator will be lit. To
reset the S8PS, turn OFF the input voltage, leave the S8PS for at
least three minutes, and then apply the input voltage again.
Note: Do not continue using the S8PS with the output terminals
short-circuited or the overcurrent condition continued, other-
wise the internal elements of the S8PS may be damaged or
broken.
Overvoltage Protection
The Power Supply is provided with an overvoltage protection function
that protects the load and the Power Supply from possible damage
by overvoltage. When the output voltage rises above a set value
(115% of the rated output voltage), the protection function is trig-
gered, shutting OFF the output voltage. If this occurs, reset the
Power Supply by turning it OFF for 1 minute min. and then turning it
ON again.
300- and 600-W Models Only
The overvoltage protection-ON alarm indicator lights when the func-
tion is operating.
Overheat Protection Function
600-W Model Only
If the internal temperature of the S8PS rises excessively as a result
of fan failure or any other reason, the overheat protection circuit will
be triggered to protect the internal elements of the S8PS and simul-
taneously a protection-ON alarm indicator will be lit. To reset the
S8PS turn OFF the input voltage, leave the S8PS for at least one
minute and then apply the input voltage again.
Inrush Current, Rise Time, Hold Time
Output voltage (V)
Output current (%)
Rating
Intermittent
operation
0 V
Variable range
Output voltage (V)
Overvoltage
protection
operating
Rated output
voltage
90% 96.5%
Input ON Input OFF
Inrush current on input application
AC input
voltage
AC input
current
Output
voltage Rise time
(1,000 ms max.) Hold time
(20 ms min.)
Switch mode Power Supply S8PS L-73
Power
Supplies
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Front-mounting Bracket Type
The Front-mounting Bracket is provided as an accessory. Screws for fixing the Bracket to the panel are not provided.
1.5 11
9
60
520
31.5
15
20.5
4.7
4.6
11
74
15±0.2
4.6
60
20
Five, M4 terminal screws
3.5 dia.
3.5 dia.
11.5 max.
Three, M3 (depth: 6 max.)
Front-mounting Bracket for 50-W Models
Mounting Holes
Using the Mounting Bracket
Two, M3
Five, M4 terminal screws 4.5 dia.
4.5 dia.
11.5 max.
Three, M4 (depth: 4 max.)
Mounting holes (also on opposite side)
Mounting Bracket
S8PS-050@@ (50 W)
S8PS-050@@@C (50 W)
Attach the Mounting Bracket to the panel and loosely
tighten the two screws. Insert the projected parts of the
Bracket (b) to the square holes of the power supply (a).
Then securely tighten the screws.
Two,
3.5 dia.
S8PS-10024 (100 W)
S8PS-10024C (100 W)
L-74 Switch mode Power Supply S8PS
(14)
5 dia.
Appearance and Mounting Dimensions
Five, M4 terminal screws
4.5 dia.
4.5 dia.
11.5 max.
Three, M4 (depth: 6 max.)
Front-mounting Bracket for 100/150-W Models
Dimensions with Mounting Bracket Using the Mounting Bracket
S8PS-30024C (300 W)
Eight, M4 (depth: 8 max., also for the opposite side)
Mounting holes (also on opposite side)
Mounting Bracket
115 max.
Two, 5 dia.
Seven, M4 terminal screws
Four, M4 (depth: 8 max.)
S8PS-15024 (150 W)
S8PS-15024C (150 W)
Switch mode Power Supply S8PS L-75
Power
Supplies
10 dia.
Two, 5 dia.
Front-mounting Bracket for 300/600-W Models Using the Mounting Bracket
S8PS-60024C (600 W)
Eight, M4 (depth: 8 max., also for the opposite side)
Seven, M4 (depth: 8 max.)
Four, M4 (depth: 8 max., opposite side only)
600-W models
Four, M4
Four, M4
600-W models
300-W models
Four, M4
(depth: 8 max.)
Appearance and Mounting
Dimensions
Dimensions with Mounting Bracket
300-W models
Note: Four screws for attaching the Bracket to
the Power Supply Unit are provided.
Note: Mount the Unit 21.6 mm away from the
mounting surface in order to provide air
ventilation on the rear side.
Note: Mount the Unit 28 mm away from the mount-
ing surface in order to provide air ventilation
on the rear side.
L-76 Switch mode Power Supply S8PS
DIN Track Mounting Bracket Type
DIN Track Mounting Bracket
Five, M4 terminal screws
3.5 dia.
11.5 max.
Five, M4 terminal screws 4.5 dia.
11.5 max.
Five, M4 terminal screws
4.5 dia.
11.5 max.
DIN Track Mounting Bracket is
attached to the Power Supply
Unit when the Unit is shipped.
5.6
(With slide: 9 max.)
5.6
(With slide: 9 max.)
S8PS-050@@D (50 W)
S8PS-050@@@CD (50 W)
S8PS-10024D (100 W)
S8PS-10024CD (100 W)
S8PS-15024D (150 W)
S8PS-15024CD (150 W)
5.6
(With slide: 9 max.)
Switch mode Power Supply S8PS L-77
Power
Supplies
Accessories
(14)
S8PS-30024CD (300 W)
Seven, M4 terminal screws
5.6
(With slide: 9 max.)
4.5
15 25 25 25 25 15
10 10
1,000
35±0.3 27 24
16
29.
2
1 1.5
4.5
15 25 25 25 25
10 10
7.3±0.15
35±0.3 27±0.15
1
PFP-100N2
Mounting Track (Order Separately)
PFP-100N/PFP-50N
Note: The values shown in parentheses are for the
PFP-50N.
1,000 (500)
(see note) 15 (5)
(see note)
L-78 Switch mode Power Supply S8PS
Precautions
!Caution
Be sure to connect the grounding line. Not doing so may result in
electric shock.
!WARNING
Do not attempt to disassemble the Power Supply or touch its inter-
nal parts while power is being supplied. Doing so may result in
electric shock.
Do not touch the terminals of the Power Supply within one minute
after power has been turned OFF. Doing so may result in electric
shock due to a residual voltage.
Do not touch the S8PS or heat radiation fin while the power is be-
ing supplied or immediately after the power is turned OFF. Other-
wise, a skin burn may result from the hot Switching Power Supply
or radiator.
Mounting
To improve and maintain the reliability of the Power Supply over a
long period of time, adequate consideration must be given to heat
radiation.
The Power Supply is designed to radiate heat by means of natural
air-flow. Therefore, mount the Power Supply so that air flow takes
place around the Power Supply.
When mounting the Power Supply, mounting it to a metal plate is rec-
ommended.
Forced air-cooling is highly recommended.
It is recommended that the clearance around the Power Supply be
larger than those shown on page page 71 under Standard Installa-
tion.
Generating Output Voltage (±)
An output of ± can be generated by using two Power Supplies as
shown below, because the Power Supply produces a floating output.
Series Operation
Only models with power ratings of 100/150 W allow series operation.
As shown in the following diagram, the output voltage from each
Switching Power Supply can be added.
Parallel Operation
Only 300- and 600-W models can be in parallel operation provided
that they are operated under 90% of the ratings. Do not operate any
other models in parallel.
Make sure that the thickness and the length of all wires connected to
the load are the same to ensure that the wires will have no voltage
drop differences.
Fan Replacement
The service life of the fan is approximately 50,000 hours (at 25°C).
The service life varies, however, depending on the ambient tempera-
ture or other surrounding environmental conditions such as dust. As
a preventive maintenance measure, replace the fan within two years
if it is used at an ambient temperature of 40°C.
Fans are available as replacements.
Fan Set:
Fan (above), four M4 x 35 sems screws, instruction sheet, and pack-
ing case
Replace the fan as shown in the following illustration.
+ V
V
+ V
V
Input INPUT
INPUT
LoadLoad
+V
V
+V
V
INPUT
INPUT
Load
+ V
V
+ V
V
INPUT
INPUT
Load
Model: S82Y-JFAN
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. T021-E1-03