L-68 Switch mode Power Supply S8PS
Specifications
■Ratings/Characteristics
Note: 1. 100% load for rated input voltage (100 VAC or 200 VAC)
2. Do not press down on the terminal block with a force exceeding 75 N while tightening the terminals.
3. MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates
reliability of devices. Therefore, it does not necessarily represent a life of the product.
4. The life expectancy shown in the above table indicates average operating hours under the ambient temperature of 40°C and a load rate
of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. It must be noted that the life
expectancy of the fan built into the 600-W model is not included.
5. The weight indicated is for the open-frame type. (Includes the cover for 300-W and 600-W models.)
Item 50 W 100 W 150 W 300 W 600 W
Efficiency (typical) 75 to 87% (depends on the model)
Input Voltage 100 to 240 VAC (85 to 264 VAC)
Frequency 47 to 450 Hz
Current (see note 1) 0.9 or 0.45 A
max.
1.8 or 0.9 A
max.
2.7 or 1.4 A
max.
5.4 or 2.7 A
max.
10 or 5 A max.
Power factor (see note 1) 0.95 TYP.
Leakage current (see note 1) 0.5 or 1.0 mA max.
Inrush current (25°C, cold start) (see note 1) 25 or 50 A max.
Output Voltage adjustment range −5% to 10%
Ripple (see note 1) 2% (p-p) max.
Input variation influence 0.4% max. (at 85 to 132 VAC input/at 170 to 264 VAC input, 100% load)
Load variation influence 0.8% max. (with rated input, 0 to 100% load)
Temperature variation influence (see note 1) 0.05%/°C max.
Rise time 1,000 ms max. (up to 90% of output voltage at rated output voltage/current)
Hold time (see note 1) 20 ms min.
Additional
function
Overload protection 105% min., voltage trailing intermittent operation
(With the 600-W model, output is turned OFF at 5 s min.)
Overvoltage protection Ye s
Overheat protection No Yes
Protection-ON alarm indicator No Yes (Red)
Parallel operation No Yes, 2 units max.
Other Heat radiation Natural air-cooling Fan
Ambient temperature Operating: See the derating curve in the Engineering Data section. (with no condensation
nor icing)
Storage: −25°C to 65°C (with no condensation nor icing)
Ambient humidity 25% to 85%
Dielectric strength 3.0 kVAC, 50/60 Hz for 1 min (between all inputs and outputs)
2.2 kVAC, 50/60 Hz for 1 min (between all inputs and GR terminals)
1 kVAC, 50/60 Hz for 1 min (between all outputs and GR terminals)
Insulation resistance 100 MΩ min. (between all output and input/GR terminals at 500 VDC)
Vibration resistance 10 to 55 Hz, 0.75-mm amplitude for 2 h each in X, Y, and Z directions
Shock resistance 300 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (green)
Terminal screw tightening torque 1.08 N·m (see note 2)
Electromagnetic interference Conforms to FCC Class B, EN50081-1
EMC (EMI): EN50081-1
Emission Enclosure: EN55022 class B
Emission AC Mains: EN55022 class B
Harmonic Current: EN61000-3-2
(EMS): EN50082-2
Immunity ESD: EN61000-4-2: 4-kV contact discharge (level 2)
8-kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2-kV power-line (level 3)
2-kV output line (level 4)
Immunity Surge: EN61000-4-5: between 3-kV lines
between 4.5-kV line and FG
Approved standards UL508, UL1012, CSA C22.2 No. 950, CSA C22.2 No. 14, EN60950, VDE0160.
Conforms to UL1950 and CSA E.B. 1402C
Reliability (MTBF) (see note 3) 135,000 hrs min. 60,000 hrs min.
Life expectancy (see note 4) 10 yrs. min. (Used at 40°C at the rated input with a 50% load, standard installation)
Weight (see note 5) 420 g max. 600 g max. 900 g max. 2,200 g max. 3,500 g max.
Mounting method Front-mounting Bracket or DIN Track Mounting Bracket Front-mounting Bracket