Contents Page
Description and specifications .................2-3
Catalog numbers ............................ 4
Conductor information and available fuses ........ 5
Dimensions ................................ 5
Accessories ..............................6
Multi-wire lug kit ............................ 6
Selector and pistol handles .................... 7
Shafts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
NFPA 79 compliant handle .................... 7
Auxiliary contacts ........................... 8
PLC fuse monitor .........................9-10
How to order tables .....................11
Switches only ..............................11
Clockwise rotary operated switches ..........12-13
Counterclockwise rotary operates switches .......14
Motor fuse sizing table ...................15
Next generation Compact Circuit Protector (cat. no. CCP2)
For use with Class CC, Supplemental and IEC 10x38 mm fuses
CCP2 switch
CCP2 left front rotary switch
CCP2 right front rotary switch
CCP2 left side rotary switch
CCP2 right side rotary switch
2011/65/EU
Technical Data 10789 Effective January 2019
Supersedes October 2018
BUSSMANN
SERIES
2
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
Catalog symbols
Symbol Fuse type Description
CCP2-(poles)-30CC Class CC Switch only
CCP2-(poles)-30M UL sup./IEC 10x38
CCP2-1-DCC Class CC Vdc 1-pole switch only
CCP2-1-DCM UL sup./IEC 10x38 Vdc
CCP2R-(pole)-30CC Class CC Right front rotary switch
CCP2R-(pole)-30M UL sup./IEC 10x38
CCP2RL-(pole)-30CC Class CC Left front rotary switch
CCP2RL-(pole)-30M UL sup./IEC 10x38
CCP2S-(pole)-30CC Class CC Right side rotary switch
CCP2S-(pole)-30M UL sup./IEC 10x38
CCP2SL-(pole)-30CC Class CC Left side rotary switch
CCP2SL-(pole)-30M UL sup./IEC 10x38
Description
The revolutionary next generation Bussmann™ series Compact
Circuit Protector (cat. no. CCP2) fused disconnect switch is 3/5 the
footprint of a traditional fusible switch and provides up to a high 200
kA Short-Circuit Current Rating (SCCR) to help improve panel and
assembly SCCR.
The 35 mm DIN-Rail mount CCP is available in a variety of
configurations to meet many application needs including rotary
operation.
Application flexibility is extended with an optional multi-wire lug kit,
with finger-safe shrouds, that provides three additional wire ports on
each pole for power distribution applications.
Other accessories include a PLC interface device for open fuse
monitoring and NO/NC auxiliary contacts that easily integrate into
many monitoring systems.
Front and side rotary operated versions are easily applied for
through-the-door or through the left or right side operation to
enhance safety.
Ratings
• Volts
• 600 Vac (UL® Class CC)
• 240 Vac (UL Supplemental)
• 400 Vac (IEC 10x38 mm)
• 80 Vdc (DC Class CC, DC UL Supplemental/IEC)
• Amps
• 30 A (UL)
• 32 A (IEC)
• SCCR
• 200 kA (UL Class CC)
• 10 kA (UL Supplemental)
• 120 kA (IEC 10x38 mm max)
• 20 kA (DC Class CC/UL)
• 10 kA (DC UL Supplemental/IEC)
Poles
• 1-, 2- and 3-poles catalog number dependent
Agency information
• UL Class CC fuse versions
• UL 98 Listed, Guide WHTY, File E302370
• cULus to Canadian Standard 22.2 No. 4-04, UL Guide WHTY7,
File 302370
• UL Supplemental and IEC 10x38 mm fuse versions
• UL 508 Listed, Guide NRNT, File E320230
• cULus Certified 22.2 No. 14-05
• IEC 60947-3 AC-23A
• DC voltage UL Class CC version (CCP2-1-DCC)
• UL 508 Listed, cULus 22.2, No. 1405
• DC IEC 10x38 version (CCP2-1-DCM)
• IEC 60947-3, DC-23A
• RoHS compliant
• CE
Conductors/terminals
• 75°C Cu/Al, see conductor tables for size, type and torque
information
• Box lug, single/dual conductor
• Fork terminal suitable for line, load or accessory connection
• Multi-wire lug kit — see accessories for details
Storage and operating temperature
• - 20°C to 75°C (-4°F to 167°F)*
* For fuse performance under or above 25°C, consult fuse performance derating
charts in the Bussmann Division publication no. 3002, titled Selecting Protective
Devices (SPD)
Lockout/tagout provisions
• Switch only — 4 mm lock or Brady pin-out device part number
90850
• Switch with rotary operating mechanism — 1/4” lock
Minimum enclosure size
• 10” x 8” x 6” (254 x 203 x 152 mm)
Mounting
• 35 mm DIN-Rail
Local open fuse indication minimum voltage**
• 90 Vac for AC switches
• 12 Vdc for DC switches
** Open fuse indication requires an open fuse to be in the CCP2 and the switch
in the ON position.
Accessories
• Multi-wire lug kit with terminal shrouds
• Selector and pistol handles for use with rotary operated switches
• 8 mm shafts for use with selector and pistol handles
• Auxiliary contacts
• PLC fuse monitor
Carton quantity and shipping weight
Item Poles Weight lbs (kg)
Switch only 12 2.84 (1.29)
Switch with side rotary mechanism 20.9 (0.404)
31.12 (0.509)
Switch with front rotary mechanism 20.95 (0.431)
31.18 (0.537)
3
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
Switch handle
(ganged on 2- and
3-pole versions)
Fuse access door
Fork terminal
Box lug terminal
Open fuse
indicating light
Lockout/tagout
provision
Features
• Extremely compact (18 mm wide per pole ) design
• High SCCR up to 200 kA (UL Class CC) and 120 kA (IEC)
• Disconnect rated for load isolation
• Full voltage rated up to 600 Vac or 80 Vdc
• UL 98 Listed Class CC version is horsepower rated and suitable
for branch circuit protection and disconnect
• IEC 10x38 version complies with IEC 60947-3 and suitable for
branch circuit protection and disconnect
• Suitable for global installations, the switches comply with UL,
cULus and IEC standards accepting UL Class CC, Supplemental
or IEC aM and gG/gL fuses
• Open fuse indication
• Standard local open fuse indicating light for each pole
• Optional PLC fuse monitor can be utilized to signal a PLC and
open a contactor to de-energize all phases, if required
• IP20 finger-safe with 10 AWG (6 mm2) or larger wire (box lug
terminals only)
• Built-in switch interlock prohibits removing the fuse under load
• Padlockable handle for lockout/tagout
• 4 mm lock for switch only
• 1/4” lock for rotary operated switches
• Rotary operated versions provide for through-the-door and
through-the-side operation flexibility and enhanced safety with:
• Right front switch operation
• Left front switch operation
• Right side switch operation
• Left side switch operation
• Optional selector, pistol and NFPA 79 compliant handles available
for use with rotary operated versions
• Multi-wire lug kit with terminal shrouds allows for power
distribution to multiple loads. Each lug has three ports rated for
single and dual wires (see lug kit in accessories for conductor and
torque details).
Left front rotary switch
Clockwise operating handles
Right front rotary switch
Clockwise operating handles
Right side rotary switch
Clockwise operating handles
Rotary operating switch versions
Right front rotary operated CCP2 switch with PLC fuse monitor.
Left side rotary switch
Counterclockwise operating
handles
4
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
Catalog numbers
Catalog no. Poles Description Amps Volts SCCR
Max horsepower rating (Vac) Wire type/
size*120 240 480 600
Class CC
CCP2-1-30CC 1
Switch only
30 A
347 Vac
200 kA
1/2
75°C Cu/Al
18-4 AWG
Fork terminal††
CCP2-2-30CC 2 600 Vac 2
CCP2-3-30CC 3 3/4 3 5 7. 5
CCP2R-2-30CC 2 Switch with right
front rotary operation 600 Vac 2
CCP2R-3-30CC 3 3/4 3 5 7. 5
CCP2RL-2-30CC 2 Switch with left front
rotary operation 600 Vac 2
CCP2RL-3-30CC 3 3/4 3 5 7. 5
CCP2S-2-30CC 2 Switch with right side
rotary operation 600 Vac 2
CCP2S-3-30CC 3 3/4 3 5 7. 5
CCP2SL-2-30CC 2 Switch with left side
rotary operation 600 Vac 2
CCP2SL-3-30CC 3 3/4 3 5 7. 5
UL Supplemental and IEC 10x38 mm
CCP2-1-30M 1
Switch only
UL 30 A
IEC 32 A**
UL 240 Vac†
IEC 400 Vac†
UL 10 kA†
IEC 120 kA† ————
75°C Cu/Al
18-4 AWG
Fork terminal††
CCP2-2-30M 2
CCP2-3-30M 3
CCP2R-2-30M 2 Switch with right
front rotary operation
CCP2R-3-30M 3
CCP2RL-2-30M 2 Switch with left front
rotary operation
CCP2RL-3-30M 3
CCP2S-2-30M 2 Switch with right side
rotary operation
CCP2S-3-30M 3
CCP2SL-2-30M 2 Switch with left side
rotary operation
CCP2SL-3-30M 3
Single-pole DC switches
CCP2-1-DCC 1 UL Class CC 30 A 80 Vdc20 kA————75°C Cu/Al
18-4 AWG
Fork terminal††
CCP2-1-DCM 1
UL supplemental 30 A
80 Vdc10 kA————
IEC 10x38 32 A**
* See box lug terminal conductor data table for details.
** 32 A Class aM, 25 A Class gG.
SCCR may be lower, refer to installed fuse data sheet for interrupting rating at applied voltage.
†† Fork terminal with a 4.3 mm gap for a #8-32 stud, 30 A max, insulated flange, wire size 12-10 AWG.
5
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
Dimensions – mm (in)
Switch
80
3.1
49
1.9
93
3.7
18
0.7
35
1.4
53
2.1
Box lug terminal conductor data
Type
AWG
range Class Quantity
Torque
N•m (lb-in)
Cu
4-18 Stranded, Class B to K Single 2.26 (20)
6-8 Stranded, Class B/C Dual 3.39 (30)
6-8 Stranded, Class K Dual 2.26 (20)
10-18 Stranded, Class B to K
10-18 Solid Single/dual
4-18 Stranded, UL ferrule, Class B/C Single 3.39 (30)
6-18 Twin
4-18 Stranded, UL ferrule, Class K Single 2.82 (25)
6-18 Twin
Al
4-8
Stranded
Single 2.26 (20)
6Dual 2.82 (25)
82.26 (20)
Two stranded conductors placed in one UL Listed twin ferrule.
Available Bussmann series fuses
Fuse
class Type/description Volts
Data
sheet
no.
CC
LP-CC time-delay 600 Vac/300 Vdc* 1023
FNQ-R time-delay 600 Vac/300 Vdc 1014
KTK-R fast-acting 600 Vac 1015
M
FNM time-delay 250 Vac 2028
FNQ time-delay 500 Vac 1012
KTK fast-acting 600 Vac 1011
BAF fast-acting 250 Vac 2011
KLM fast-acting 600 Vac/dc 2020
gG/gL C10G 500 V (400 V@32 A) 720115
aM C10M 500 V (400 V@20@25 A) 720115
* 1/2 to 2-1/2 and 20 to 30 A are 300 Vdc, 2-8/10 to 15 A are 150 Vdc.
93
3.7
99
3.9
80
3.1
49
1.9 18
0.7
35
1.4
53
2.1
78
3.1
99
[3.9]
49
[1.9]
93
[3.7]
80
[3.1]
93
[3.7]
78
[3.1]
18
[0.7]
53
[2.1]
35
[1.4]
Left front and right front rotary switches
93
3.7
80
3.1
49
1.9 18
0.7
35
1.4
53
2.1
78
3.1
93
3.7
80
3.1
49
1.9
18
0.7
35
1.4
53
2.1
78
3.1
Left side and right side rotary switches
6
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
Multi-wire lug kit
Catalog number
• CCP2-MW1-3
Description
The multi-wire lug kit permits expanding each box lug terminal
on the switch into a three-port terminal for power distribution
applications.
Each multi-wire lug kit comes with three (3) three-port lugs and
three terminal shrouds. Shrouds provide finger-safe protection when
properly installed.
Lugs may be mounted on either the loadside or lineside to meet
various application needs.
Ports on any one lug accept any conductor combination listed, e.g.,
one of the three ports may have dual 14 AWG wires and the other
two ports single 10 AWG wires.
Ratings
• Volts 600 V
• Amps 60 A max
• SCCR 200 kA
Agency information
• UL Recognized (lug only)
• RoHS compliant
Storage and operating temperature
• - 20°C to 75°C (-4°F to 167°F)
Multi-wire lug conductor information
• 75°C Cu/AL
• AWG size and quantity per port - see table below
Type
AWG
range Class Quantity
Torque
N•m (lb-in)
Cu/Al 4-6 Stranded, Class B/C Single 3.95 (35)
82.82 (25)
Cu
10-14 Stranded, Class B/C Single/dual* 2.26 (20)
10-14 Solid Single 2.26 (20)
8UL ferrule, Class B to K Single/twin2.82 (25)
10-14 2.26 (20)
* Dual wire to be same size and type.
Two stranded conductors placed in one UL Listed twin ferrule.
CCP2 box lug torque for multi-wire lug
• 4.52 N•m (40 lb-in)
Terminal shroud accessory
Terminal shrouds are available without multi-wire terminals.
Catalog no. Description
CCP2-TS1-3 Pack of three
Installed on CCP2-3-xx
Multi-wire lugs mount in switch box lug terminals to provide three
additional wire ports per pole. Lugs can be mounted on the switch
lineside or loadside. Each multi-wire lug kit comes with three lugs
and three shrouds.
Wire insulation strip lengths
1 = 11/16”
2 = 1-1/8”
3 = 1-9/16”
1/8” Allen
head screw
Strip back wire insulation to the lengths as indicated in the
illustration above and the table below.
Lug port Strip wire insulation back (inch)
1 11/16
2 1-1/8
3 1-9/16
Wiring versatility is provided by single/dual rated box lug terminals
on the switch, or by the three-port multi-wire lug kit that’s also
single/dual wire rated.
7
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
Counterclockwise
• CCP2-H4X-B1L
• CCP2-H4X-R1L
Clockwise
• CCP2-H4X-B1
• CCP2-H4X-R1
Selector and pistol handles
Catalog symbol
• CCP2-H4X-_
Description
Selector and pistol handles for use with any 2- and 3-pole CCP2
rotary operated switch. Both selector and pistol handles are available
in black/grey and red/yellow colors and clockwise/counterclockwise
operating modes. Applying clockwise and counterclockwise
operation depends upon the CCP2 rotary switch configuration.
Installation requires an 8 mm shaft (ordered separately).
Each handle is rated NEMA 4X and capable of accepting up to three
(3) 1/4” diameter shank locks for lockout/tagout in the OFF position.
They can also be field configured for lock-on.
In application, only the clockwise operating handles in combination
with either the left front or right front rotary switches provide a door
interlock means to ensure the enclosure door remains shut during
lockout/tagout or lock-on. Both clockwise and counterclockwise
operating handles when mounted on the enclosure’s left or right side
do NOT provide a door interlock means.
See the catalog number table below for applicable rotary switch,
handle and shaft combinations.
Agency information
• UL Listed, Guide DIHS, File E140305
• NEMA 4X rating
• RoHS complaint
• CE
Storage and operating temperature
• -20°C to 75°C (-4°F to 167°F)
Packaging
• Each handle is packaged individually
Handle shafts
Catalog symbol
• CCP2-SH1-_
Description
Eight millimeter square shafts available in 290 and 490 millimeter
(11.5 and 19.3 inch) lengths. Shafts are indexed to ensure handle/
switch orientation for correct operation. Shafts are cut to length
when installed.
Packaging
• Each shaft is packaged separately
For these switch
catalog numbers Description/operation
Order these handle catalog numbers
(description) Order either shaft catalog number
CCP2R-(pole)-30CC Right front rotary, clockwise CCP2-H4X-B1 (selector, black/grey)
• CCP2-H4X-R1(selector, red/yellow)
• CCP2-H4X-B2 (pistol, black/grey)
• CCP2-H4X-R2 (pistol, red/yellow) • CCP2-SH1-290 (11.5”/290 mm)
• CCP2-SH1-490 (19.3”/490 mm)
CCP2R-(pole)-30M
CCP2RL-(pole)-30CC Left front rotary, clockwise
CCP2RL-(pole)-30M
CCP2S-(pole)-30CC Right side rotary, clockwise
CCP2S-(pole)-30M
CCP2SL-(pole)-30CC
Left side rotary, counterclockwise
• CCP2-H4X-B1L (selector, black/grey)
• CCP2-H4X-R1L (selector, red/yellow)
• CCP2-H4X-B2L (pistol, black/grey)
• CCP2-H4X-R2L (pistol, red/yellow)
CCP2SL-(pole)-30M
Selector handles
Counterclockwise
• CCP2-H4X-B2L
• CCP2-H4X-R2L
Clockwise
• CCP2-H4X-B2
• CCP2-H4X-R2
Pistol handles
Handle shafts
NFPA 79 compliant handles
Catalog number
• CCP2-NFPA-1
Description
NFPA 79 handle mounts on the shaft of front rotary
operated switch installations and provides a lockout
means independent of the door position.
Carton quantity
Catalog no. Fits shaft size Qty.
CCP2-NFPA-1 8 mm 1
8
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
1.8
2.6
3.7
1.9
0.19
0.3
33 NO
41 NC
34 NO
42 NC
STRIP
Auxiliary contacts
Catalog number
• CCP2-AUX
Description
NO+NC contact output to indicate the
switching mechanism status on the
CCP2. A single unit can be mounted
on any 1-, 2- or 3-pole CCP2 switch
and the left front/left side rotary
operated switches.
Ratings
• Amps up to 5 A
• Volts up to 240 Vac
• NC/NO contacts are closed/open when the CCP2 switch is in the
ON” position (closed)
Description Max per CCP2* Signal output
Auxiliary contacts NO+NC
for switch status
1 per CCP2
(1-, 2- or 3-pole) 5 A / 240 Vac
* The CCP2-AUX CANNOT be mounted on the right front and right side rotary
operated versions.
De-energize all circuits and follow all prevailing safety procedures before
installing or removing the CCP2-AUX.
Agency information
• UL 98 Recognized, Guide WHTY2, File E155130
• cURus to Canadian Standard 22.2 No. 4-04
• IP20 finger-safe in installed state
• RoHS compliant
• CE
Wiring
• 75°C Cu, 20-16 AWG (0.5 to 1.5 mm2) wire
• Torque 0.56 N•m (5 lb-in)
Packaging
• The CCP2-AUX is packaged individually
Installation technique
• Mounts on the CCP2’s right side ONLY and mechanically
interlocks with the CCP2 switch handle with provided hardware.
The CCP2-AUX CANNOT be mounted on the right front and right
side rotary operated versions.
Storage and operating temperature
• -20°C to 75°C (-4°F to 167°F)
Installed on a CCP2-3-xx
Note: CCP2-AUX CANNOT be mounted on the right front and right
side rotary operated versions.
Dimensions — in
CCP2-AUX auxiliary contacts mounted on a 3-pole CCP2 switch.
9
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
PLC fuse monitor
Catalog number
• CCP2-PLC-IND
Description
A resettable three-phase
fuse monitor that integrates
with the I/O card in a
Programmable Logic
Controller (PLC). A single
unit can be mounted on
any 1-, 2- or 3-pole CCP2
switch and the right front/ right side rotary operated switches.
A single unit monitors up to three phases. When used on 1- and
2-pole switches unused conductor(s) are removed after installation.
The CCP2-PLC-IND CANNOT be mounted on the left front/left side
rotary operated versions or if the multi-wire lug kit is installed.
Ratings
• Signal output to PLC*
• +24 Vdc, 10 mA max
• Output signals
• Digital 0 Vdc (low), 24 Vdc max (high)
• 0 Vdc Low – fuse is good
• 24 Vdc High – fuse has opened
* When the fuse opens, the output signal is sent high and will remain high until
the unit is reset.
Emissions and immunity testing
• IEC 60947-1: Voltage Switchgear and Control Gear
• IEC 61000-6-2: Electromagnetic Compatibility (EMC)
• IEC 61000-4-2: Electrostatic Discharge Immunity - Test at level
3 (6 kV-Contact Discharge) and level 2 (4 kV-Air Discharge)
• IEC 61000-4-3: Electromagnetic Compatibility - Radiated, Radio-
frequency, Electromagnetic Field Immunity test at level x
(20 V/m)
• IEC 61000-4-4: Electromagnetic Compatibility - Testing and
Measurement Techniques at level 3 (± 2 kV - Power Port and
±1 kV - I/O Ports)
• IEC 61000-4-5: Electromagnetic Compatibility - Surge Immunity
test at level 4 (±4 kV)
• IEC 61000-4-6: Immunity to Conducted Disturbances at level 3 (10 V)
Description
Max per
CCP2**
Signal output
to PLC
Min. circuit
volts
Wired remote fuse
indication for PLC
applications
1 per CCP2
(1, 2- or 3-pole) 24 Vdc/ 10 mA 100 Vac
** The CCP2-PLC-IND CANNOT be mounted on the left front/left side rotary
operated versions or if the multi-wire lug kit is installed.
De-energizeallcircuitsandfollowallprescribedsafetyproceduresbeforeinstalling
orremovingtheCCP2-PLC-IND.
Agency information
• UL 98 Recognized, Guide WHTY2, File E155130
• cURus to Canadian, Standard 22.2 No. 4-04
Local indication
• Two distinct LEDs indicate unit power (green) and open fuse (red).
Open fuse LED is resettable upon fuse replacement and actuating
the reset switch.
Wiring
• For power, signal and ground connections use shielded twisted
pair 22-24 AWG (0.34-0.25 mm2) 300 V rated wire
Packaging
• The CCP2-PLC-IND is packaged individually
• Includes 0.110” (2.8 mm) quick connects for power, signal and
ground connections
Installation technique
• Mounts on the left side ONLY of the CCP2 and mechanically
interlocks with the CCP2 switch handle with hardware provided.
The CCP2-PLC-IND CANNOT be mounted on the left front/
left side rotary operated versions or if the multi-wire lug kit is
installed.
IP20 rating — yes
Storage and operating temperature
• -20°C to 75°C (-4°F to 167°F)
PLC programming
• The CCP2-PLC-IND signal line is designed to provide a digital
input to a PLC I/O card. In this case, a Programmable Logic
Control program must be written to properly interpret the input
signal to the PLC. The PLC program should check for consecutive
high signals before taking action on a critical process.
Installed on a CCP2-3-xx
CCP2-PLC-IND mounted on a 3-pole switch and using the fork
terminals. When mounted on a 2- or 1-pole switch, remove unused
leads.
Note: The CCP2-PLC-IND CANNOT be mounted on the left front/left
side rotary operated versions or if the multi-wire lug kit is installed.
CCP2-PLC-IND fuse monitor mounted on a right front rotary
operated switch.
10
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
PLC wiring schematic CCP2-PLC-IND connections from a CCP2-3-xx to a remote
monitoring device
PLC power supply PLC fuse monitor
PLC
input card
+24 Vdc
0 Vdc/Gnd
+24 Vdc
0 Vdc/Gnd
+24 Vdc
0 Vdc/Gnd
Signal
10 mA max.
The PLC fuse monitor needs
to be powered by the same
+24 Vdc and ground
(0 Vdc/Gnd return)
terminals that feed the
PLC input card.
If it is not, it may
improperly signal.
If feeding multiple
PLC fuse monitors from
different power supplies,
there must be multiple
input cards being powered
by those same power
supplies as well.
Circuit monitoring leads from
CCP2-PLC-IND to CCP2
(100 – 600 Vac)
Circuit monitoring
leads from PLC or
remote monitoring
device.
Connection from CCP2-PLC-IND to CCP2-3-xx
Leads from CCP2-PLC-IND are connected to the fork terminals as
shown.
Note: When monitoring a 1- or 2-pole switch, remove unused leads.
Lead from CCP2-PLC-IND
Power lead
2.6
1.8
3.7
1.9
0.3
ON
RESET
STATUS
+24vDC
+24vDC
GND
SIG
5L33L21L1
6T
3
4T
2
2T
1
Pin interlocks with
CCP2 switch handle
Dimensions — in
11
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
Class CC and UL Supplemental (IEC 10x38) Switches
For a complete assembly, select from the following required and optional components, and accessories.
Required
Catalog no.
Switches Amps Poles
Switch
CCP2-1-30CC
30
1
CCP2-2-30CC 2
CCP2-3-30CC 3
CCP2-1-30M 1
CCP2-2-30M 2
CCP2-3-30M 3
And
Optional
Lug kits Description
CCP2-MW1-3 3-port multi-wire, 75°C Cu/Al, 6-14, includes terminal shrouds, pack of 3
And
Accessories
Terminal shrouds Description
CCP2-TS1-3 Pack of 3
Auxiliary contacts Description
CCP2-AUX NO + NC, 5 A / 240 V
PLC fuse monitor Description
CCP2-PLC-IND Signal output 24 Vdc / 10 mA
12
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
Class CC and UL Supplemental (IEC 10x38) clockwise rotary switches
For a complete assembly, select from the following required and optional components, and accessories.
Required
Catalog no.
Switches Amps Poles
Right front rotary
CCP2R-2-30CC
30
2
CCP2R-3-30CC 3
CCP2R-2-30M 2
CCP2R-3-30M 3
Left front rotary
CCP2RL-2-30CC
30
2
CCP2RL-3-30CC 3
CCP2RL-2-30M 2
CCP2RL-3-30M 3
Right side rotary
CCP2S-2-30CC
30
2
CCP2S-3-30CC 3
CCP2S-2-30M 2
CCP2S-3-30M 3
And
Rotary handles Description NEMA rating
CCP2-H4X-B1 Selector handle — black/grey
4X
CCP2-H4X-R1 Selector handle — red/yellow
CCP2-H4X-B2 Pistol handle — black/grey
CCP2-H4X-R2 Pistol handle — red/yellow
And
Shafts (8 mm) Length
CCP2-SH1-290 290 mm
CCP2-SH1-490 490 mm
NFPA 79 compliant
handle Color
CCP2-NFPA-1 Red
And
Optional
Lug kits Description
CCP2-MW1-3 3-port multi-wire, 75°C Cu/Al, 6-14, includes terminal shrouds, pack of 3
13
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
And
Accessories
Terminal shrouds Description
CCP2-TS1-3 Pack of 3
Auxiliary contacts Description — cannot be used on right front or right side operated switches
CCP2-AUX NO + NC, 5 A / 240 V
PLC fuse monitor Description — Cannot be used on left front operated switches
CCP2-PLC-IND Signal output 24 Vdc / 10 mA
14
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
Class CC and UL Supplemental (IEC 10x38) counterclockwise switches
For a complete assembly, select from the following required and optional components, and accessories.
Required
Catalog no.
Switches Amps Poles
Left side rotary
CCP2SL-2-30CC
30
2
CCP2SL-3-30CC 3
CCP2SL-2-30M 2
CCP2SL-2-30M 2
And
Rotary handles Description NEMA rating
CCP2-H4X-B1L Selector handle — black/grey
4X
CCP2-H4X-R1L Selector handle — red/yellow
CCP2-H4X-B2L Pistol handle — black/grey
CCP2-H4X-R2L Pistol handle — red/yellow
And
Shafts (8 mm) Length
CCP2-SH1-290 290 mm
CCP2-SH1-490 490 mm
And
Optional
Lug kits Description
CCP2-MW1-3 3-port multi-wire, 75°C Cu/Al, 6-14, includes terminal shrouds, pack of 3
And
Accessories
Terminal shrouds Description
CCP2-TS1-3 Pack of 3
Auxiliary contacts Description —mounts on right side
CCP2-AUX NO + NC, 5 A / 240 V
15
Technical Data 10789
Effective January 2019
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Eaton.com/bussmannseries
Motor fuse sizing table:
LP-CC time-delay Class CC fuses
Voltage Motor size (Hp) Motor FLA (amps) Min (amps) Code max (amps) Heavy start (amps)
115 Vac, 1-phase
1/6 4.4 9 15 15
1/4 5.8 12 20 20
1/3 7. 2 15 25 25
1/2 9.8 30 30 30
230 Vac, 1-phase
1/6 2.2 4.5 10 10
1/4 2.9 6 10 10
1/3 3.6 7 15 15
1/2 4.9 10 15 15
3/4 6.9 15 25 25
1 8 25 25 30
1-1/2 10 30 30 30
200 Vac, 3-phase
1/2 2.5 5 10 10
3/4 3.7 7. 5 15 15
1 4.8 10 15 15
1-1/2 6.9 15 25 25
27. 8 25 25 30
208 Vac, 3-phase
1/2 2.4 5 10 10
3/4 3.5 7 15 15
1 4.6 10 15 15
1-1/2 6.6 15 20 25
27. 5 15 25 30
230 Vac, 3-phase
1/2 2.2 4.5 10 10
3/4 3.2 7 10 12
1 4.2 9 15 15
1-1/2 6 12 20 20
2 6.8 15 25 25
3 9.6 30 30 30
460 Vac, 3-phase
1/2 1. 1 2.25 6 6
3/4 1. 6 3.2 6 6.25
1 2.1 4.5 10 10
1-1/2 3 6 10 12
2 3.4 7 15 15
3 4.8 10 15 15
57. 6 25 25 30
575 Vac, 3-phase
1/2 0.9 1. 8 3 3.5
3/4 1. 3 2.8 6 6
11. 7 3.5 6 6.25
1-1/2 2.4 5 10 10
2 2.7 5.6 10 10
3 3.9 8 15 15
5 6.1 15 20 20
7-1/2 9 30 30 30
Note: NEMA motors only (no IEC or design B energy efficient). Minimum size if no more than 1 start/hour. Code max if low to moderate reverse/jog/plug applications.
Heavy start permitted only if code max does not allow motor start-up. For high reverse/jog/plug applications or larger horsepower motors.
Compact Circuit Protector disconnect switches
For use with Class CC, Supplemental and IEC 10x38 mm fuses
Technical Data 10789
Effective January 2019
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are
by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the
end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit
distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once
a product has been selected, it should be tested by the user in all possible applications.
Eaton and Bussmann are valuable trademarks
of Eaton in the US and other countries. You
are not permitted to use the Eaton trademarks
without prior written consent of Eaton.
CSA is a registered trademark of the Canadian
Standards Group
UL is a registered trademark of the
Underwriters Laboratories, Inc.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2019 Eaton
All Rights Reserved
Printed in USA
Publication No. 10789 – BU-MC18031
January 2019