Data Sheet
SS/264XS_2
ABB 2600T Series
Engineered solutions
for all applications
Base accuracy : ±0.075%
Span limits
0.14 to 16000kPa; 0.56inH2O to 2320psi
– 0.27 to 16000kPa abs; 2mmHg to 2320psia
Reliable sensing system coupled with very latest
digital technologies
provides large turn down ratio up to 100:1
Comprehensive sensor choice
optimize in-use total performance and stability
5–year stability
Flexible configuration facilities
provided locally via local keys combined with LCD
indicator or via hand held terminal or
PC configuration platform
Multiple protocol availability
provides integration with HART®, PROFIBUS PA
and FOUNDATION Fieldbus platforms offering
interchangeability and transmitter upgrade
capabilities
Full compliance with PED Category IV
suitable for safety accessory application
FieldIT
2600T Series Pressure Transmitters
Model 264DS Differential
Model 264PS Gauge
Model 264VS Absolute
maximum working pressure up to 21MPa, 3045psi
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
2
Damping
Selectable time constant : 0, 0.25, 0.5, 1, 2, 4, 8 or 16s.
This is in addition to sensor response time
Turn on time
Operation within specification in less than 1s with minimum
damping.
Insulation resistance
> 100M at 1000VDC (terminals to earth)
Span limits
Maximum span = URL
(can be further adjusted up to ± URL (TD = 0.5) for differential
models, within the range limits)
IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR
CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS
POSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS.
Zero suppression and elevation
Zero and span can be adjusted to any value within the range limits
detailed in the table as long as:
– calibrated span minimum span
Functional Specifications
Range and span limits
rosneS
edoC
egnaRreppU
)LRU(timiL
)LRL(timiLegnaRrewoL napsmuminiM
SD462
laitnereffid
SP462
eguag
SV462
etulosba
laitnereffidSD462
eguagSP462
SV462
etulosba
B
aPk4
rabm04
Hni61
2
O
aPk4
rabm04
Hni61
2
O
aPk4
rabm04
Hni61
2
O
aPk41.0
rabm4.1
Hni65.0
2
O
E
aPk61
rabm061
Hni46
2
O
aPk61
rabm061
Hni46
2
O
aPk61
rabm061
Hni46
2
O
sbaaPk70.0
sbarabm7.0
gHmm5.0
aPk72.0
rabm7.2
Hni80.1
2
O
aPk72.0
rabm7.2
gHmm2
F
aPk04
rabm004
Hni061
2
O
aPk04
rabm004
Hni061
2
O
aPk04
rabm004
Hni061
2
O
sbaaPk70.0
sbarabm7.0
gHmm5.0
aPk4.0
rabm4
Hni6.1
2
O
aPk76.0
rabm7.6
gHmm5
G
aPk56
rabm056
Hni062
2
O
aPk56
rabm056
Hni062
2
O
aPk56
rabm056
Hni062
2
O
sbaaPk70.0
sbarabm7.0
gHmm5.0
aPk56.0
rabm5.6
Hni6.2
2
O
aPk1.1
rabm11
gHmm8
H
aPk061
rabm0061
Hni246
2
O
aPk061
rabm0061
Hni246
2
O
sbaaPk1
sbarabm01
aisp51.0
sbaaPk70.0
sbarabm7.0
gHmm5.0
aPk6.1
rabm61
Hni4.6
2
O
aPk76.2
rabm7.62
gHmm02
M
aPk006
rab6
isp78
aPk006
rab6
isp78
sbaaPk1
sbarabm01
aisp51.0
sbaaPk70.0
sbarabm7.0
gHmm5.0
aPk6
rab60.0
isp78.0
aPk01
rab1.0
isp54.1
P
aPk0042
rab42
isp843
aPk0042
rab42
isp843
sbaaPk1
sbarabm01
aisp51.0
sbaaPk70.0
sbarabm7.0
gHmm5.0
aPk42
rab42.0
isp5.3
aPk04
rab4.0
isp8.5
Q
aPk0008
rab08
isp0611
aPk0008
rab08
isp0611
sbaaPk1
sbarabm01
aisp51.0
sbaaPk70.0
sbarabm7.0
gHmm5.0
aPk08
rab8.0
isp6.11
aPk431
rab43.1
isp4.91
S
aPk00061
rab061
isp0232
aPk00061
rab061
isp0232
sbaaPk1
sbarabm01
aisp51.0
sbaaPk70.0
sbarabm7.0
gHmm5.0
aPk061
rab6.1
isp2.32
aPk762
rab76.2
isp7.83
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
3
Operative limits
Temperature limits °C (°F) :
Ambient (is the operating temperature)
Lower ambient limit for LCD indicators: –20°C (–4°F)
Upper ambient limit for LCD indicators: +70°C (+158°F)
Note : For Hazardous Atmosphere applications see the temperature
range specified on the certificate/approval relevant to the aimed
type of protection
Process
Lower limit
– refer to lower ambient limits; –20°C (–4°F) for Viton gasket
Upper limit
– Silicone oil: 121°C (250°F) (1)
– Inert fluid: 100°C (212°F) (2)
(1) 100°C (212°F) for application below atmospheric pressure
(2) 65°C (150°F) for application below atmospheric pressure
Storage
Lower limit: –50°C (–58°F); –40°C (–40°F) for LCD indicators
Upper limit: +85°C (+185°F)
Pressure limits
Overpressure limits (without damage to the transmitter)
0.067kPa abs, 0.67mbar abs, 0.01psia (double with inert filling) to
– 7MPa, 70bar, 1015psi for sensor code B
– 16MPa, 160bar, 2320psi for sensor code E
21MPa, 210bar, 3045psi for sensor codes F to S
Static pressure
Transmitters for differential pressure model 264DS operates within
specifications between the following limits
– sensor code B:
1.3kPa abs,13mbar abs, 0.2psia and 7MPa, 70bar, 1015psi
– sensor code E:
1.3kPa abs,13mbar abs, 0.2psia and 16MPa, 160bar, 2320psi
– sensor codes F to S:
1.3kPa abs,13mbar abs, 0.2psia and 21MPa, 210bar, 3045psi
Proof pressure
The transmitter can be exposed without leaking to line pressure of up
to 48MPa, 480bar, 6960psi. Meet ANSI/ISA–S 82.03 hydrostatic test
requirements and SAMA PMC 27.1.
Environmental limits
Electromagnetic compatibility (EMC)
Comply with EN 61000–6–3 for emission and EN 61000–6–2 for
immunity requirements and test;
Radiated electromagnetic immunity level: 30V/m
(according to IEC 1000–4–3, EN61000–4–3)
Conducted electromagnetic immunity level : 30V
(according to IEC 1000–4-6, EN 61000–4–6)
Surge immunity level (with surge protector): 4kV
(according to IEC 1000-4–5 EN 61000–4–5)
Fast transient (Burst) immunity level: 4kV
(according to IEC 1000–4–4 EN 61000–4–4)
Pressure equipment directive (PED)
Comply with 97/23/EEC Category IV Modules D and B.
Humidity
Relative humidity: up to 100% annual average
Condensing, icing: admissible
Vibration resistance
Accelerations up to 2g at frequency up to 1000Hz
(according to IEC 60068–2–26)
Shock resistance
Acceleration: 50g
Duration: 11ms
(according to IEC 60068–2–27)
Wet and dust-laden atmospheres
The transmitter is dust and sand tight and protected against immersion
effects as defined by EN 60529 (1989) to IP 67 (IP 68 on request) or by
NEMA to 4X or by JIS to C0920.
Hazardous atmospheres
With or without output meter/integral display
INTRINSIC SAFETY/EUROPE:
ATEX/ZELM approval
II 1 GD T50°C, EEx ia IIC T6 (–40°C Ta +40°C)
T95°C, EEx ia IIC T4 (–40°C Ta +85°C)
TYPE "N"/EUROPE:
ATEX/ZELM type examination (for HART)
II 3 GD T50°C, EEx nL IIC T6 (–40°C Ta +40°C)
T95°C, EEx nL IIC T4 (–40°C Ta +85°C)
(FOUNDATION Fieldbus/PROFIBUS PA): pending
FLAMEPROOF/EUROPE:
ATEX/CESI approval
II 1/2 GD T85°C, EEx d IIC T6 (–40°C Ta +75°C)
CANADIAN STANDARDS ASSOCIATION
and FACTORY MUTUAL:
– Explosionproof: Class I, Div. 1, Groups A, B, C, D
– Dust ignitionproof : Class II, Div. 1, Groups E, F, G
– Suitable for : Class II, Div. 2, Groups F, G; Class III, Div. 1, 2
– Nonincendive: Class I, Div. 2, Groups A, B, C, D
– Intrinsically safe: Class I, II, III, Div. 1, Groups A, B, C, D, E, F, G
AEx ia IIC T6/T4, Zone 0 (FM)
STANDARDS AUSTRALIA (SAA): pending
TS/WCA Approval
Ex d IIC T5 (Tamb +85°C)/T6 (Tamb +70°C) Class 1 Zone 1;
Ex ia IIC T4 (Tamb +85°C) /T5 (Tamb +55°C) T6 Class 1 Zone 0
gnilliF
SP462-SD462sledoMSV462ledoM
srosneS
SotF
srosneS
EotB
srosneS
SotF
rosneS
Eedoc
enociliS
lio
58+dna04
)581+dna04(
58+dna52
)581+dna31(
58+dna04
)581+dna04(
07+dna51
)851+dna5+(
trenI
nedlaG
58+dna02
)581+dna4(
58+dna01
)581+dna41+(
56+dna01
)051+dna41+( elbacilppaton
trenI nobracolaH 58+dna02 )581+dna4( 58+dna01 )581+dna41+( 56+dna01
)051+dna41+( elbacilppaton
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
4
Optional surge protection
Up to 4kV
voltage 1.2 µs rise time / 50 µs delay time to half value
current 8 µs rise time / 20 µs delay time to half value
Output signal
Two–wire 4 to 20mA, user-selectable for linear or square root output,
power of 3/2 or 5/2, 5th order or two 2nd order switching point selectable
programmable polynomial output.
HART® communication provides digital process variable (%, mA or
engineering units) superimposed on 4 to 20mA signal, with protocol
based on Bell 202 FSK standard.
Output current limits (to NAMUR standard)
Overload condition
- Lower limit: 3.8mA
- Upper limit: 20.5mA
Transmitter failure mode (to NAMUR standard)
The output signal can be user-selected to a value of 3.7 or 22mA on
gross transmitter failure condition, detected by self-diagnostics.
In case of CPU failure the output is driven <3.7mA or >22mA.
Electrical Characteristics and Options
HART digital communication and 4 to 20mA output
Power Supply
The transmitter operates from 10.5 to 42VDC with no load and is
protected against reverse polarity connection (additional load allows
operations over 42VDC).
For EEx ia and other intrinsically safe approval power supply must
not exceed 30VDC.
Ripple
20mV max on a 250 load as per HART specifications
Load limitations
4 to 20mA and HART total loop resistance :
A minimum of 250 is required for HART communication.
Optional indicators
Output meter
CoMeter and Prometer LCD :
5-digit (±99999 counts) programmable with 7.6mm. high (3in),
7-segment numeric characters plus sign and digital point for digital
indication of output value in percentage, current or engineer unit;
10-segment bargraph display (10% per segment) for analog
indication of output in percentage;
7-digit with 6mm. high (2.3in), 14-segment alphanumeric
characters, for engineer units and configuration display
Analog : 36mm (1.4in) scale on 90°.
Integral display
LCD, 15 lines x 56 column dot matrix providing 2 lines indication as
– top: 5-digit (numeric) plus sign or 7-digit alphanumeric
– bottom: 7-digit alphanumeric
and additional 50-segment bargraph for indication of analog output
in percentage.
User-definable matrix display mode with HART communication:
– process variable in pressure unit or
– output signal as percentage, current or engineering units
Display also indicates in/out transfer function, static pressure, sensor
temperature and diagnostic messages and provides configuration
facilities.
R(k) = Supply voltage – min. operating voltage (VDC)
–––––––––––––––––––––––––––––––––––––––
22.5
(volts)
MINIMUM OPERATING VOLTAGES
10.5
with integral display
with optional output analog indicator
with optional surge protection
with ProMeter output indicator
10.7 12.3 12.5
no link on output indicator plugs
15.3
with CoMeter indicator and HART communication
13.3
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
5
PROFIBUS PA output
Device type
Pressure transmitter compliant to Profiles 3.0 Class A & B; ident.
number 052B HEX.
Power supply
The transmitter operates from 10.5 to 32VDC , polarity independent.
For EEx ia approval power supply must not exceed 17.5VDC.
Intrinsic safety installation according to FISCO model.
Current consumption
operating (quiescent): 10.5mA
fault current limiting: 20mA max.
Output signal
Physical layer in compliance to IEC 1158–2/EN 61158–2 with
transmission to Manchester II modulation, at 31.25kbit/sec.
Output interface
PROFIBUS PA communication according to Profibus DP50170 Part 2/
DIN 19245 part 1–3.
Output update time
25ms
Function blocks
2 analog input, 1 transducer, 1 physical
Integral display
LCD, 15 lines x 56 column dot matrix providing 2 lines indication as
– top: 5-digit (numeric) plus sign or 7-digit alphanumeric
– bottom: 7-digit alphanumeric
and additional 50-segment bargraph for indication of output in
percentage of the analog input function block assigned to the primary
variable.
User-definable matrix display mode:
– process variable in pressure units or
– primary variable in engineering units (output of transducer block) or
– output as percentage or engineering units of analog input function
blocks
Display also indicates diagnostic messages and provides
configuration facilities.
Secondary variable, static pressure and sensor temperature can be
read.
Transmitter failure mode
On gross transmitter failure condition, detected by self-diagnostics,
the output signal can be driven to defined conditions, selectable by the
user as safe, last valid or calculated value. If electronic failure or short
circuit occur the transmitter consumption is electronically limited at a
defined value (20mA approx), for safety of the network.
FOUNDATION Fieldbus output
Device type
LINK MASTER DEVICE
Link Active Scheduler (LAS) capability implemented.
Power supply
The transmitter operates from 9 to 32VDC, polarity independent.
For EEx ia approval power supply must not exceed 24VDC (entity
certification) or 17.5VDC (FISCO certification), according to FF–816.
Current consumption
operating (quiescent): 10.5mA
fault current limiting: 20mA max.
Output signal
Physical layer in compliance to IEC 1158–2/EN 61158–2 with
transmission to Manchester II modulation, at 31.25kbit/sec.
Function blocks/execution period
2 standard Analog Input blocks/25ms max (each)
1 standard PID block/70ms max.
Additional blocks
1 standard Resource block,
1 custom Pressure with calibration transducer block.
Number of link objects
25
Number of VCRs
24
Output interface
FOUNDATION fieldbus digital communication protocol to standard H1,
compliant to specification V. 1.5; FF registration number IT019000.
Integral display
LCD, 15 lines x 56 column dot matrix providing 2 lines indication as
– top: 5-digit (numeric) plus sign or 7-digit alphanumeric
– bottom: 7-digit alphanumeric
and additional 50-segment bargraph for indication of output in
percentage of the analog input function block assigned to the primary
variable.
User-definable matrix display mode:
– process variable in pressure units or
– primary variable in engineering units (output of transducer block) or
– output as percentage or engineering units of analog input function
blocks
Display also indicates diagnostic messages and provides
configuration facilities.
Secondary variable, static pressure and sensor temperature can be
read.
Transmitter failure mode
The output signal is "frozen" to the last valid value on gross transmitter
failure condition, detected by self-diagnostics which also indicate a
BAD conditions. If electronic failure or short circuit occur the transmitter
consumption is electronically limited at a defined value (20mA approx),
for safety of the network.
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
6
Operating influences
Ambient temperature
per 20K (36°F) change between the limits of –20°C to +65°C (–4 to
+150°F) :
Optional CoMeter and ProMeter ambient temperature
Total reading error per 20K (36°F) change between the ambient limits
of –20 and +70°C (-4 and +158°F) :
±0.15% of max span (16mA).
Static pressure (zero errors can be calibrated out at line pressure)
per 2MPa, 20bar or 290psi (sensor code B)
per 7MPa, 70bar or 1015psi (sensor codes E to S)
Model 264DS
zero error: ±0.08% of URL
span error: ±0.08% of reading
Multiply by 2 the errors for sensor code E.
Supply voltage
Within voltage/load specified limits the total effect is less than
0.005% of URL per volt.
Load
Within load/voltage specified limits the total effect is negligible.
Radio frequency interference
Total effect : less than 0.10% of span from 20 to 1000MHz and for
field strengths up to 30V/m when tested with shielded conduit and
grounding, with or without meter.
Common mode interference
No effect from 100Vrms @ 50Hz, or 50VDC
Mounting position
Rotations in plane of diaphragm have negligible effect. A tilt to 90°
from vertical causes a zero shifts up to 0.5kPa, 5mbar or 2inH2O,
which can be corrected with the zero adjustment. No span effect.
Stability
±0.10% of URL over a thirty-six-month period
Vibration effect
±0.10% of URL (according to IEC 61298–3)
URL
Span
URL
Span
URL
Span
Performance specifications
Stated at reference condition to IEC 60770 ambient temperature of 20°C
(68°F), relative humidity of 65%, atmospheric pressure of 1013hPa
(1013mbar), mounting position with vertical diaphragm and zero based
range for transmitter with isolating diaphragms in AISI 316 L ss or Hastelloy
and silicone oil fill and HART digital trim values equal to 4–20mA span end
points, in linear mode.
Unless otherwise specified, errors are quoted as % of span.
Some performance data are affected by the actual turndown (TD) as ratio
between Upper Range Limit (URL) and calibrated span.
IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODE
PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO
OPTIMIZE PERFORMANCE CHARACTERISTICS.
Dynamic performance (according to IEC 61298–1 definition)
Dead time: 40ms
Time constant (63.2% of total step change):
– sensors M to S: 70ms
sensor H: 100ms
– sensor G: 130ms
– sensor F: 180ms
Response time (total) = dead time + time constant
Accuracy rating
% of calibrated span, including combined effects of terminal based
linearity, hysteresis and repeatability.
For fieldbus versions SPAN refer to analog input function block outscale
range
Model 264DS, 264PS
±0.075% for TD from 1:1 to 15:1
(±0.10% for sensor code B for TD from 1:1 to 10:1)
±0.005% x for TD from 15:1 to 60:1
(30:1 for sensor code E)
(±0.01% x for sensor code B for TD from 10:1 to 20:1)
Models 264VS
±0.075% for TD from 1:1 to 10:1
±0.0075% x for TD from 10:1 to 20:1
ledoM rosneS
edoC
DTrof
otpu
SD462
SP462
SotE1:51)naps%560.0+LRU%40.0(±
B1:01)naps%01.0+LRU%60.0(±
SV462 SotE1:01)naps%31.0+LRU%80.0(±
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
7
Physical Specification
(Refer to ordering information sheets for variant availability related to
specific model or versions code)
Materials
Process isolating diaphragms (*)
AISI 316 L ss; Hastelloy C276™; Monel 400™; Tantalum;
Hastelloy C276™ on AISI 316 L ss gasket seat.
Process flanges, adapters, plugs and drain/vent valves (*)
AISI 316 L ss; Hastelloy C276™; Monel 400™.
Blind flange (reference side of 264PS, 264VS)
AISI 316 L ss.
Sensor fill fluid
Silicone oil (DC200); inert fill (Halocarbon™ 4.2 or Galden™).
Mounting bracket (**)
Zinc plated carbon steel with chrome passivation;
AISI 316 L ss.
Gaskets (*)
Viton™; PTFE.
Sensor housing
AISI 316 L ss.
Bolts and nuts
AISI 316 ss bolts Class A4–80 and nuts Class A4–70 per UNI 7323
(ISO 3506);
AISI 316 ss bolts and nuts Class A4–50 per UNI 7323 (ISO 3506), in
compliance with NACE MR0175 Class II.
Electronic housing and covers
Barrel version
– Copper-free content aluminium alloy with baked epoxy finish;
– Low-copper content aluminium alloy with baked epoxy finish;
– AISI 316 L ss.
DIN version
Low-copper content aluminium alloy with baked epoxy finish.
Covers O-ring
Buna N.
Local zero and span adjustments:
Glass filled polycarbonate plastic (removable).
Tagging
AISI 316ss data plate attached to the electronics housing.
Calibration
Standard: at maximum span, zero based range, ambient temperature
and pressure;
Optional: at specified range and ambient conditions.
Optional extras
Mounting brackets
For vertical and horizontal 60mm. (2in) pipes or wall mounting.
Output indicator
plug-in rotatable type, LCD or analog.
Supplemental customer tag
AISI 316 ss tag screwed/fastened to the transmitter for customer's tag
data up to a maximum of 20 characters and spaces on one line for tag
number and tag name, and up to a maximum of 3 spaced strings of 10
characters each for calibration details (lower and upper values plus
unit). Special typing evaluated on request for charges.
Surge protection (only as external unit for PROFIBUS PA and FF)
Cleaning procedure for oxygen service
Hydrogen or special service preparation
Test Certificates (test, design, calibration, material traceability)
Tag and manual language
Communication connectors
Process connections
on flanges : 1/4in NPT on process axis
on adapters : 1/2in NPT on process axis
centre distance (264DS): 54mm (2.13in ) on flange;
51,54 or 57mm (2.01, 2.13 or 2.24in) as per adapters fittings
fixing threads: 7/16in–20 UNF at 41.3mm centre distance
Electrical connections
Two 1/2 NPT or M20x1.5 or PG 13.5 or 1/2 GK threaded conduit
entries, direct on housing.
Special communication connector (on request)
– HART : straight or angle Harting Han connector and one plug.
– FOUNDATION Fieldbus, PROFIBUS PA: M12x1 or 7/8.
Terminal block
HART version: three terminals for signal/external meter wiring up to
2.5mm2 (14AWG) and three connection points for test and
communication purposes.
Fieldbus versions: two terminals for signal wiring (bus connection)
up to 2.5mm2 (14AWG)
Grounding
Internal and external 6mm2 (10AWG) ground termination points are
provided.
Mounting position
Transmitter can be mounted in any position.
Electronics housing may be rotated to any position. A positive stop
prevents over travel.
Mass (without options)
3.5kg approx (8lb); add 1.5kg (3.4lb) for AISI housing.
Add 650g (1.5lb) for packing.
Packing
Carton 26 x 26 x 18cm approx (10 x 10 x 7in).
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
8
Configuration
Transmitter with HART communication and 4 to 20 mA
Standard configuration
Transmitters are factory calibrated to customer's specified range.
Calibrated range and tag number are stamped on the tag plate. If a
calibration range and tag data are not specified, the transmitter will be
supplied with the plate left blank and configured as follows:
Engineering Unit Specify from table
4 mA Zero
20 mA Upper Range Limit (URL)
Output Linear
Damping 1 sec.
Transmitter failure mode Upscale
Software tag characters Blank
Optional LCD indicator/display 0 to 100.0% linear
Any or all the above configurable parameters, including Lower range–value
and Upper range-value which must be the same unit of measure, can be
easily changed using the HART hand–held communicator or by a PC
running the configuration software SMART VISION with DTM for 2600T.
The transmitter database is customized with specified flange type and
material, O–ring and drain/vent materials and meter code option.
Custom configuration (option)
The following data may be specified in addition to the standard
configuration parameters:
Descriptor 16 alphanumeric characters
Message 32 alphanumeric characters
Date Day, month, year
Transmitter with PROFIBUS PA communication
Transmitters are factory calibrated to customer's specified range.
Calibrated range and tag number are stamped on the tag plate. If a
calibration range and tag data are not specified, the transmitter will be
supplied with the plate left blank and configured as follows:
Measure Profile Pressure
Engineering Unit kPa
Output scale 0% Lower Range Limit (LRL)
Output scale 100% Upper Range Limit (URL)
Output Linear
Hi-Hi Limit Upper Range Limit (URL)
Hi Limit Upper Range Limit (URL)
Low Limit Lower Range Limit (LRL)
Low-Low Limit Lower Range Limit (LRL)
Limits hysteresis 0.5% of output scale
PV filter 0 sec.
Address (settable by local key) 126
Tag 32 alphanumeric characters
Any or all the above configurable parameters, including Lower range-value
and Upper range–value which must be the same unit of measure, can be
easily changed by a PC running the configuration software SMART VISION
with DTM for 2600T. The transmitter database is customized with specified
flange type and material, O–ring and drain/vent materials and meter code
option.
Custom configuration (option)
The following data may be specified in addition to the standard
configuration parameters:
Descriptor 32 alphanumeric characters
Message 32 alphanumeric characters
Date Day, month, year
Transmitter with FOUNDATION Fieldbus
communication
Transmitters are factory calibrated to customer's specified range.
Calibrated range and tag number are stamped on the tag plate. If a
calibration range and tag data are not specified, the transmitter will be
supplied with the plate left blank and the analog input function block FB1
is configured as follows:
Measure Profile Pressure
Engineering Unit kPa
Output scale 0% Lower Range Limit (LRL)
Output scale 100% Upper Range Limit (URL)
Output Linear
Hi-Hi Limit Upper Range Limit (URL)
Hi Limit : Upper Range Limit (URL)
Low Limit Lower Range Limit (LRL)
Low-Low Limit Lower Range Limit (LRL)
Limits hysteresis 0.5% of output scale
PV filter time 0 sec.
Tag 32 alphanumeric characters
The analog input function block FB2 is configured for the sensor tempe-
rature measured in °C. Any or all the above configurable parameters,
including the range values, can be changed using any host compliant to
FOUNDATION fieldbus. The transmitter database is customized with
specified flange type and material, O–ring and drain/vent materials and
meter code option.
For any protocol available engineering units of pressure measure are :
Pa, kPa, MPa
inH2O@4°C, mmH2O@4°C, psi
inH2O@20°C, ftH2O@20°C, mmH2O@20°C
inHg, mmHg, Torr
g/cm2, kg/cm2, atm
mbar, bar
™ Hastelloy is a Cabot Corporation trademark
™ Monel is an International Nickel Co. trademark
™ DC 200 is a Dow Corning Corporation trademark
™ Galden is a Montefluos trademark
™ Halocarbon is a Halocarbon Products Co. trademark
™ Viton is a Dupont de Nemour trademark
(*) Wetted parts of the transmitter.
(**) U-bolt material: AISI 400 ss; screws material: high-strength alloy steel or
AISI 316 ss.
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
9
135 (5.31)
(*)
62 (2.44)
71 (2.80)
86 (3.39)
82 (3.23)
+
127 (5.00)
17 (0.67)
26 (1.02)
17 (0.67)
36 (1.42)
MOUNTING DIMENSIONS (not for construction unless certified) – dimensions in mm (in)
Transmitter with barrel aluminium housing on bracket for vertical or horizontal 60mm (2in) pipe mounting
(*) FOR MODEL 264DS
51 (2.01), 54 (2.13) or 57 (2.24) mm (in) according to 1/2in 14 NPT adapters fitting; 54 (2.13) mm (in) on 1/4in 18 NPT process flange
FOR MODEL 264PS
54 (2.13) mm (in) with low pressure side flange without process connection (a filter is fitted) and drain/vent valve
NOTE : Process connection, gasket groove and gaskets are in accordance with DIN 19213. Bolting threads for fixing adapter or other devices
(i.e. manifold etc.) on process flange is 7/16in – 20 UNF.
Certification
label
Identification tag
Adjustments
Terminal
side
Electronic
side
Integral
display
housing
Min. clearance
to remove
the cover
Output meter
housing
Drain/vent
Valve
Barrel type
housing
Process
connection
Model 264VS
66 (2.60) with plug
78 (3.07) with d/v valve
11 (0.43)
102 (4.02)
84 (3.31)
108 (4.25)
41.3 (1.63)
63 (2.48)
167 (6.57)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
86 (3.39)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
108 (4.25)
82 (3.23)
Adapter
Electrical
connections
Flange
Covers locking
screw
54 (2.13)
71 (2.80)
86 (3.39)
82 (3.23)
62 (2.44)
135 (5.31)
+
127 (5.00)
17 (0.67)
26 (1.02)
17 (0.67)
36 (1.42)
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
10
Transmitter on bracket for vertical or horizontal 60 mm (2in) pipe mounting (DIN housing)
Transmitter with flanges for vertical connection (Barrel housing)
Adjustments
Integral
display
housing
Certification
label
Output
meter
housing
Terminal
side
DIN type
housing
Electronic
side
Drain/vent
Valve
Flange
Adapter
Identification
tag
Covers locking
screw
Certification
label
Harting Han
connector
External
ground
Electrical
connections
108 (4.25)
82 (3.23)
26 (1.02)
41.3 (1.63)
51 (2.01)
33
(1.30)
63 (2.48)
179 (7.05)
17 (0.67)
148 (5.83)
36 (1.42)
17 (0.67)
55 (2.17) max 7 (0.28)
142 (5.59)
16 (0.63)
86 (3.39)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
+
127 (5.00)
17 (0.67)
26 (1.02)
17 (0.67)
36 (1.42)
54 (2.13)
71 (2.80) 62 (2.44)
86 (3.39)
185 (7.28)
86 (3.39)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
83 (3.27)
33 (1.30)
41.3 (1.63)
74 (2.91)
Certification
label
Identification tag
Adjustments
Terminal
side
Electronic
side
Integral
display
housing
Min. clearance
to remove
the cover
Output meter
housing
Drain/vent
Valve
Barrel type
housing
Process
connection
Adapter
Electrical
connections
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
11
Transmitter on bracket for wall mounting (by four M8 screws)
Transmitter with barrel AISI ss housing on bracket (flat type for box) for vertical or horizontal 60mm (2in)
pipe mounting
70 (2.75)
84 (3.31)
70 (2.75)
204 (8.03)
98 (3.86)
+
25 (0.98)
47 (1.85)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
70 (2.75)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
70 (2.75)
70 (2.75)
25 (1)
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
12
Electrical connections
HART Version
FIELDBUS Versions
+
+
-
-
+
+
-
-
691HT
A B C
1D E F
2G H I
3
J K L
4M N O
5P Q R
6
S T U
7V W X
8Y Z #
9
@ % & /
0+
-
PV
REVIEW SERIAL
LINK
TRIM
F1 F2 F3 F4
CONF
M
Kent-Taylor
0
4
3
5
6
7
8
9
10
20
40
0
60
100
%
2
80
M+
-
-
1
54 6
238
7
+
TEST COMM
Internal ground
termination point
Fieldbus line
(polarity independent)
External ground
termination point
Test points
4 to 20mA
Harting
pin (male)
identification
Internal ground
termination point
External ground
termination point
Hand-held
communicator
GND
Line load
Remote
indicator
Power
source
250 ohm min
Receiver
HART hand-held communicator may be connected at any wiring termination point in the loop, providing the minimum resistance
is 250 ohm. If this is less than 250 ohm, additional resistance should be added to allow communications
Optional
BUS CONNECTIONS
2
1
4
3
13
42
7/8” connector
M12 x 1 connector
NOITACIFITNEDI)elam(NIP
NOITADNUOF
subdleiF
SUBIFORP
AP
11
1
11
22
2
22
33
3
33
44
4
44
-FF
+FF
DLEIHS
DNUORG
+AP
DNUORG
AP
DLEIHS
Mating female plug NOT SUPPLIED
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
13
BASIC ORDERING INFORMATION model 264DS Differential Pressure Transmitter
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
LEDOMESAB 1
ts
5ot
ht
sretcarahc 2 6 4 D SXSXXXXX
%570.0YCARUCCAESABrettimsnarTerusserPlaitnereffiD
stimilnapS-ROSNES 6
ht
retcarahc
aPk4dna41.0
aPk61dna72.0
aPk04dna4.0
aPk56dna56.0
aPk061dna6.1
aPk006dna6
aPk0042dna42
aPk0008dna08
aPk00061dna061
rabm04dna4.1
rabm061dna7.2
rabm004dna4
rabm056dna5.6
rabm0061dna61
rab6dna60.0
rab42dna42.0
rab08dna8.0
rab061dna6.1
Hni61dna65.0
2
O
Hni46dna80.1
2
O
Hni061dna6.1
2
O
Hni062dna6.2
2
O
Hni246dna4.6
2
O
isp78dna78.0
isp843dna5.3
isp0611dna6.11
isp0232dna2.32
B
E
F
G
H
M
P
Q
S
edocesU 7
ht
retcarahc
)strapdettew(diulflliF/lairetammgarhpaiD 8
ht
retcarahc
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
004lenoM
mulatnaT
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
004lenoM
mulatnaT
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
004lenoM
mulatnaT
lioenociliS
lioenociliS
lioenociliS
lioenociliS
lioenociliS
nedlaG-diulftrenI
nedlaG-diulftrenI
nedlaG-diulftrenI
nedlaG-diulftrenI
nedlaG-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
)2etoN(
)2etoN(
)2etoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
S
H
K
M
T
A
B
F
C
D
L
Q
P
4
5
)strapdettew(noitcennocdnalairetamsretpada/segnalfssecorP –9
ht
retcarahc
)noitcennoclatnoziroH(ssL613ISIA
)noitcennoclatnoziroH(ssL613ISIA
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
A
B
)noitcennoclatnoziroH(672CyolletsaH
)noitcennoclatnoziroH(672CyolletsaH
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
D
E
)noitcennoclatnoziroH(004lenoM
)noitcennoclatnoziroH(004lenoM
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
G
H
)noitcennoclacitreV(ssL613ISIA
)noitcennoclacitreV(ssL613ISIA
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
Q
T
)noitcennoclacitreV(672CyolletsaH
)noitcennoclacitreV(672CyolletsaH
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
M
S
)noitcennoclacitreV(004lenoM
)noitcennoclacitreV(004lenoM
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
U
V
)strapdettew(teksaG/stloB 01
ht
retcarahc
ss613ISIA
ss613ISIA
)aPM61=PWM()ECAN(ss613ISIA
)aPM61=PWM()ECAN(ss613ISIA
notiV
EFTP
notiV
EFTP
)1etoN(
)1etoN(
ECAN
ECAN
1
2
3
4
noitcennoclacirtcelednalairetamgnisuoH 11
ht
retcarahc
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg(
)ylnoesopruplareneg(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
A
B
D
C
E
G
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
H
L
N
M
P
R
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocsubdleiF
S
T
V
U
Z
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)02MC(5.1x02M
5.31gP
rotcennocnaHgnitraH
rotcennocsubdleiF
J
Y
K
W
snoitpolanoitiddA/tuptuO 21
ht
retcarahc
Am02ot4dnanoitacinummoclatigidTRAH
Am02ot4dnanoitacinummoclatigidTRAH
APSUBIFORP
APSUBIFORP
subdleiFNOITADNUOF
subdleiFNOITADNUOF
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)5,4setoN(
)4etoN(
)5,4setoN(
)5etoN(
)5,4setoN(
)5etoN(
H
1
P
2
F
3
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
14
ADDITIONAL ORDERING INFORMATION for model 264DS
Add one or more 2-digit code(s) after the basic ordering information to select all required options
XXXX XXXX XXXX XXXX XXXX XXdeunitnoC
)strapdettew()noitisopdnalairetam(evlavtnev/niarD
ssL613ISIA
ssL613ISIA
ssL613ISIA
672CyolletsaH
672CyolletsaH
672CyolletsaH
004lenoM
004lenoM
004lenoM
sixassecorpno
potedisegnalfno
mottobedisegnalfno
sixassecorpno
potedisegnalfno
mottobedisegnalfno
sixassecorpno
potedisegnalfno
mottobedisegnalfno
)6etoN(
)7etoN(
)7etoN(
)8etoN(
)9etoN(
)9etoN(
)01etoN(
)11etoN(
)11etoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
1V
2V
3V
4V
5V
6V
7V
8V
9V
noitacifitreclacirtcelE aixEEytefaScisnirtnIDG1yrogetaCIIpuorGXETA
dxEEfoorpemalFDG2/1yrogetaCIIpuorGXETA
)21etoN(ecnailpmocngisedLnxEE"N"noitcetorpfoepyTDG3yrogetaCIIpuorGXETA
ylno()ASC(noitaicossAdradnatSnaidanaC
1
/
2
)gnisuoh5.31gPdna02M,TPNni
)21etoN(5T/6TCIIdxE+4T/5T/6TCIIaixEAASailartsuAsdradnatSotfoorpemalFytefaScisnirtnI
htiwylno(lavorppa)MF(lautuMyrotcaF
1
/
2
)noitcennoclacirtcele5.31gPdna02M,TPNni
1E
2E
3E
4E
5E
6E
retemtuptuO
noitarbilacdradnatS,reteMorP
noitarbilaclaicepS,reteMorP
elacs%0010raenilrotacidnituptuogolanA
elacs010toorerauqsrotacidnituptuogolanA
)elacsraenilrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)elacstoorerauqsrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)noitarugifnocremotsucreteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
1D
2D
3D
4D
5D
6D
7D
8D
DCLlargetnI
yalpsidlargetniDCLlatigiD 1L
)lairetamdnaepahs(tekcarbgnitnuoM
gnitnuomepiproF
gnitnuomepiproF
gnitnuomllawroF
gnitnuomllawroF
xobrofepyttalF
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
leetsnobraC
ssL613ISIA
leetsnobraC
ssL613ISIA
ssL613ISIA
1B
2B
3B
4B
5B
egruS
rotcetorPtneisnarT/egruS )21etoN( 1S
launamgnitarepO
namreG
nailatI
hcnerF
1M
2M
4M
egaugnalgat&slebaL
namreG
nailatI
hcnerF
1T
2T
4T
etalpgatlanoitiddA
etalpleetssselniatsnogatfognitnirpresaL 2I
noitarugifnoC
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°4taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°4taisp/O
motsuC
2N
3N
4N
5N
6N
erudecorpnoitaraperP
P)teksagEFTPdnalliftrenihtiwelbaliavaylno(gninaelcecivresnegyxO
xam
T;nobracolaHrofaPM9ronedlaGrofaPM21=
xam
F°041/C°06=
noitaraperpecivresnegordyH
noitaraperpsecivreslaicepS
1P
2P
4P
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
15
Note 1: Suitable for oxygen service
Note 2: Not available with sensor code B
Note 3: Select type in additional ordering code
Note 4: Not available with Electronic Housing code Z, R, G and W
Note 5: Not available with Electronic Housing code P, E and K
Note 6: Not available with Process flanges/adapters code D, E, G, H, Q, T, M, S, U, V
Note 7: Not available with Process flanges/adapters code D, E, G, H, M, S, U, V
Note 8: Not available with Process flanges/adapters code A, B, G, H, Q, T, M, S, U, V
Note 9: Not available with Process flanges/adapters code A, B, G, H, Q, T, U, V
Note 10: Not available with Process flanges/adapters code A, B, D, E, Q, T, M, S, U, V
Note 11: Not available with Process flanges/adapters code A, B, D, E, Q, T, M, S
Note 12: Not available with PROFIBUS PA and FF output code 2 or 3
Note 13: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B, J, Y
Hastelloy is a Cabot Corporation trademark
Monel is an International Nickel Co. trademark
Viton is a Dupont de Nemour trademark
Galden is a Montefluos trademark
Halocarbon is a Halocarbon Products Co. trademark
Standard delivery items (can be differently specified by additional ordering code)
Adapters supplied loose
Plug on axis of horizontal connection flange; nothing for vertical connection blind flange (no drain/vent valves)
General purpose (no electrical certification)
No meter/display, no mounting bracket, no surge protection
English manual and labels
Configuration with kPa and deg. C units
No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S
RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
SD462ledomrofNOITAMROFNIGNIREDROLANOITIDDA XXXX XX
setacifitreC
)tniop-9(noitarbilacfoB.1.340201NEetacifitrecnoitcepsnI
ngisedtnemurtsnifo1.240201NEredroehthtiwecnailpmocfoetacifitreC
1C
6C
ytilibaecartlairetaM
strapdettewssecorpfo1.240201NEredroehthtiwecnailpmocfoetacifitreC
strapdettewssecorpfoB.1.340201NEetacifitrecnoitcepsnI
1H
3H
rotcennoC
8/7subdleiF
1x21MsubdleiF
yrtnethgiartsnaHgnitraH
yrtneelgnanaHgnitraH
)subdleiFNOITADNUOFrofDEDNEMMOCER(
)APSUBIFORProfDEDNEMMOCER(
)31,5setoN(
)31,5setoN(
)31,4setoN(
)31,4setoN(
1U
2U
3U
4U
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
16
BASIC ORDERING INFORMATION model 264PS Gauge Pressure Transmitter
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
LEDOMESAB 1
ts
5ot
ht
sretcarahc 2 6 4 P SXSXXXXX
%570.0YCARUCCAESABrettimsnarTerusserPeguaG
stimilnapS-ROSNES 6
ht
retcarahc
aPk4dna41.0
aPk61dna72.0
aPk04dna4.0
aPk56dna56.0
aPk061dna6.1
aPk006dna6
aPk0042dna42
aPk0008dna08
aPk00061dna061
rabm04dna4.1
rabm061dna7.2
rabm004dna4
rabm056dna5.6
rabm0061dna61
rab6dna60.0
rab42dna42.0
rab08dna8.0
rab061dna6.1
Hni61dna65.0
2
O
Hni46dna80.1
2
O
Hni061dna6.1
2
O
Hni062dna6.2
2
O
Hni246dna4.6
2
O
isp78dna78.0
isp843dna5.3
isp0611dna6.11
isp0232dna2.32
B
E
F
G
H
M
P
Q
S
edocesU 7
ht
retcarahc
)strapdettew(diulflliF/lairetammgarhpaiD 8
ht
retcarahc
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
004lenoM
mulatnaT
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
004lenoM
mulatnaT
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
004lenoM
mulatnaT
lioenociliS
lioenociliS
lioenociliS
lioenociliS
lioenociliS
nedlaG-diulftrenI
nedlaG-diulftrenI
nedlaG-diulftrenI
nedlaG-diulftrenI
nedlaG-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
)2etoN(
)2etoN(
)2etoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
S
H
K
M
T
A
B
F
C
D
L
Q
P
4
5
)strapdettew(noitcennocdnalairetamsretpada/segnalfssecorP –9
ht
retcarahc
)noitcennoclatnoziroH(ssL613ISIA
)noitcennoclatnoziroH(ssL613ISIA
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
A
B
)noitcennoclatnoziroH(672CyolletsaH
)noitcennoclatnoziroH(672CyolletsaH
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
D
E
)noitcennoclatnoziroH(004lenoM
)noitcennoclatnoziroH(004lenoM
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
G
H
)noitcennoclacitreV(ssL613ISIA
)noitcennoclacitreV(ssL613ISIA
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
Q
T
)noitcennoclacitreV(672CyolletsaH
)noitcennoclacitreV(672CyolletsaH
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
M
S
)noitcennoclacitreV(004lenoM
)noitcennoclacitreV(004lenoM
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
U
V
)strapdettew(teksaG/stloB 01
ht
retcarahc
ss613ISIA
ss613ISIA
)aPM61=PWM()ECAN(ss613ISIA
)aPM61=PWM()ECAN(ss613ISIA
notiV
EFTP
notiV
)1etoN(EFTP
)1etoN(
)1etoN(
ECAN
ECAN
1
2
3
4
noitcennoclacirtcelednalairetamgnisuoH 11
ht
retcarahc
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg(
)ylnoesopruplareneg(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
A
B
D
C
E
G
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
H
L
N
M
P
R
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocsubdleiF
S
T
V
U
Z
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)02MC(5.1x02M
5.31gP
rotcennocnaHgnitraH
rotcennocsubdleiF
J
Y
K
W
snoitpolanoitiddA/tuptuO 21
ht
retcarahc
Am02ot4dnanoitacinummoclatigidTRAH
Am02ot4dnanoitacinummoclatigidTRAH
APSUBIFORP
APSUBIFORP
subdleiFNOITADNUOF
subdleiFNOITADNUOF
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)5,4setoN(
)4etoN(
)5,4setoN(
)5etoN(
)5,4setoN(
)5etoN(
H
1
P
2
F
3
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
17
ADDITIONAL ORDERING INFORMATION for model 264PS
Add one or more 2-digit code(s) after the basic ordering information to select all required options
XXXX XXXX XXXX XXXX XXXX XXdeunitnoC
)strapdettew()noitisopdnalairetam(evlavtnev/niarD
ssL613ISIA
ssL613ISIA
ssL613ISIA
672CyolletsaH
672CyolletsaH
672CyolletsaH
004lenoM
004lenoM
004lenoM
sixassecorpno
potedisegnalfno
mottobedisegnalfno
sixassecorpno
potedisegnalfno
mottobedisegnalfno
sixassecorpno
potedisegnalfno
mottobedisegnalfno
)6etoN(
)7etoN(
)7etoN(
)8etoN(
)9etoN(
)9etoN(
)01etoN(
)11etoN(
)11etoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
1V
2V
3V
4V
5V
6V
7V
8V
9V
noitacifitreclacirtcelE aixEEytefaScisnirtnIDG1yrogetaCIIpuorGXETA
dxEEfoorpemalFDG2/1yrogetaCIIpuorGXETA
)21etoN(ecnailpmocngisedLnxEE"N"noitcetorpfoepyTDG3yrogetaCIIpuorGXETA
ylno()ASC(noitaicossAdradnatSnaidanaC
1
/
2
)gnisuoh5.31gPdna02M,TPNni
)21etoN(5T/6TCIIdxE+4T/5T/6TCIIaixEAASailartsuAsdradnatSotfoorpemalFytefaScisnirtnI
htiwylno(lavorppa)MF(lautuMyrotcaF
1
/
2
)noitcennoclacirtcele5.31gPdna02M,TPNni
1E
2E
3E
4E
5E
6E
retemtuptuO
noitarbilacdradnatS,reteMorP
noitarbilaclaicepS,reteMorP
elacs%0010raenilrotacidnituptuogolanA
)elacsraenilrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)noitarugifnocremotsucreteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
1D
2D
3D
5D
7D
8D
DCLlargetnI
yalpsidlargetniDCLlatigiD 1L
)lairetamdnaepahs(tekcarbgnitnuoM
gnitnuomepiproF
gnitnuomepiproF
gnitnuomllawroF
gnitnuomllawroF
xobrofepyttalF
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
leetsnobraC
ssL613ISIA
leetsnobraC
ssL613ISIA
ssL613ISIA
1B
2B
3B
4B
5B
egruS
rotcetorPtneisnarT/egruS )21etoN( 1S
launamgnitarepO
namreG
nailatI
hcnerF
1M
2M
4M
egaugnalgat&slebaL
namreG
nailatI
hcnerF
1T
2T
4T
etalpgatlanoitiddA
etalpleetssselniatsnogatfognitnirpresaL 2I
noitarugifnoC
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°4taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°4taisp/O
motsuC
2N
3N
4N
5N
6N
erudecorpnoitaraperP
P)teksagEFTPdnalliftrenihtiwelbaliavaylno(gninaelcecivresnegyxO
xam
T;nobracolaHrofaPM9ronedlaGrofaPM21=
xam
F°041/C°06=
noitaraperpecivresnegordyH
noitaraperpsecivreslaicepS
1P
2P
4P
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
18
Note 1: Suitable for oxygen service
Note 2: Not available with sensor code B
Note 3: Select type in additional ordering code
Note 4: Not available with Electronic Housing code Z, R, G and W
Note 5: Not available with Electronic Housing code P, E and K
Note 6: Not available with Process flanges/adapters code D, E, G, H, Q, T, M, S, U, V
Note 7: Not available with Process flanges/adapters code D, E, G, H, M, S, U, V
Note 8: Not available with Process flanges/adapters code A, B, G, H, Q, T, M, S, U, V
Note 9: Not available with Process flanges/adapters code A, B, G, H, Q, T, U, V
Note 10: Not available with Process flanges/adapters code A, B, D, E, Q, T, M, S, U, V
Note 11: Not available with Process flanges/adapters code A, B, D, E, Q, T, M, S
Note 12: Not available with PROFIBUS PA and FF output code 2 or 3
Note 13: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B, J, Y
Hastelloy is a Cabot Corporation trademark
Monel is an International Nickel Co. trademark
Viton is a Dupont de Nemour trademark
Galden is a Montefluos trademark
Halocarbon is a Halocarbon Products Co. trademark
Standard delivery items (can be differently specified by additional ordering code)
Adapters supplied loose
Plug on axis of horizontal connection flange; nothing for vertical connection blind flange (no drain/vent valves)
General purpose (no electrical certification)
No meter/display, no mounting bracket, no surge protection
English manual and labels
Configuration with kPa and deg. C units
No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS
MEDIA IS A CUSTOMER'S RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
SP462ledomrofNOITAMROFNIGNIREDROLANOITIDDA XXXX XX
setacifitreC
)tniop-9(noitarbilacfoB.1.340201NEetacifitrecnoitcepsnI
ngisedtnemurtsnifo1.240201NEredroehthtiwecnailpmocfoetacifitreC
1C
6C
ytilibaecartlairetaM
strapdettewssecorpfo1.240201NEredroehthtiwecnailpmocfoetacifitreC
strapdettewssecorpfoB.1.340201NEetacifitrecnoitcepsnI
1H
3H
rotcennoC
8/7subdleiF
1x21MsubdleiF
yrtnethgiartsnaHgnitraH
yrtneelgnanaHgnitraH
)subdleiFNOITADNUOFrofDEDNEMMOCER(
)APSUBIFORProfDEDNEMMOCER(
)31,5setoN(
)31,5setoN(
)31,4setoN(
)31,4setoN(
1U
2U
3U
4U
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
19
BASIC ORDERING INFORMATION model 264VS Absolute Pressure Transmitter
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
LEDOMESAB 1
ts
5ot
ht
sretcarahc 2 6 4 V SXSXXXXX
%570.0YCARUCCAESAB-rettimsnarTerusserPetulosbA
stimilnapSROSNES retcarahcht6
aPk61dna72.0
aPk04dna76.0
aPk56dna1.1
aPk061dna76.2
aPk006dna01
aPk0042dna04
aPk0008dna431
aPk00061dna762
rabm061dna7.2
rabm004dna7.6
rabm056dna11
rabm0061dna7.62
rab6dna1.0
rab42dna4.0
rab08dna43.1
rab061dna76.2
gHmm021dna2
gHmm003dna5
gHmm084dna8
gHmm0021dna02
isp78dna54.1
isp843dna8.5
isp0611dna4.91
isp0232dna7.83
E
F
G
H
M
P
Q
S
edocesU 7
ht
retcarahc
)strapdettew(diulflliF/lairetammgarhpaiD 8
ht
retcarahc
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
lioenociliS
lioenociliS
lioenociliS
nedlaG-diulftrenI
nedlaG-diulftrenI
nedlaG-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
)2,1setoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
S
H
K
A
B
F
L
Q
P
)strapdettew(noitcennocdnalairetamsretpada/segnalfssecorP –9
ht
retcarahc
)noitcennoclatnoziroH(ssL613ISIA
)noitcennoclatnoziroH(ssL613ISIA
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
A
B
)noitcennoclatnoziroH(672CyolletsaH
)noitcennoclatnoziroH(672CyolletsaH
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
D
E
)noitcennoclatnoziroH(004lenoM
)noitcennoclatnoziroH(004lenoM
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
G
H
)noitcennoclacitreV(ssL613ISIA
)noitcennoclacitreV(ssL613ISIA
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
Q
T
)noitcennoclacitreV(672CyolletsaH
)noitcennoclacitreV(672CyolletsaH
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
M
S
)noitcennoclacitreV(004lenoM
)noitcennoclacitreV(004lenoM
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
U
V
)strapdettew(teksaG/stloB 01
ht
retcarahc
ss613ISIA
ss613ISIA
)aPM61=PWM()ECAN(ss613ISIA
)aPM61=PWM()ECAN(ss613ISIA
notiV
EFTP
notiV
EFTP
)1etoN(
)1etoN(
ECAN
ECAN
1
2
3
4
noitcennoclacirtcelednalairetamgnisuoH 11
ht
retcarahc
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
A
B
D
C
E
G
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
H
L
N
M
P
R
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocsubdleiF )ylnoesopruplareneg()3etoN(
S
T
V
U
Z
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)02MC(5.1x02M
5.31gP
rotcennocnaHgnitraH
rotcennocsubdleiF
)ylnoesopruplareneg(
)ylnoesopruplareneg(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
J
Y
K
W
snoitpolanoitiddA/tuptuO 21
ht
retcarahc
Am02ot4dnanoitacinummoclatigidTRAH
Am02ot4dnanoitacinummoclatigidTRAH
APSUBIFORP
APSUBIFORP
subdleiFNOITADNUOF
subdleiFNOITADNUOF
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)5,4setoN(
)4etoN(
)5,4setoN(
)5etoN(
)5,4setoN(
)5etoN(
H
1
P
2
F
3
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
20
ADDITIONAL ORDERING INFORMATION for model 264VS
Add one or more 2-digit code(s) after the basic ordering information to select all required options
XXXX XXXX XXXX XXXX XXXX XXdeunitnoC
)strapdettew()noitisopdnalairetam(evlavtnev/niarD
ssL613ISIA
ssL613ISIA
ssL613ISIA
672CyolletsaH
672CyolletsaH
672CyolletsaH
004lenoM
004lenoM
004lenoM
sixassecorpno
potedisegnalfno
mottobedisegnalfno
sixassecorpno
potedisegnalfno
mottobedisegnalfno
sixassecorpno
potedisegnalfno
mottobedisegnalfno
)6etoN(
)7etoN(
)7etoN(
)8etoN(
)9etoN(
)9etoN(
)01etoN(
)11etoN(
)11etoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
1V
2V
3V
4V
5V
6V
7V
8V
9V
noitacifitreclacirtcelE aixEEytefaScisnirtnIDG1yrogetaCIIpuorGXETA
dxEEfoorpemalFDG2/1yrogetaCIIpuorGXETA
)21etoN(ecnailpmocngisedLnxEE"N"noitcetorpfoepyTDG3yrogetaCIIpuorGXETA
ylno()ASC(noitaicossAdradnatSnaidanaC
1
/
2
)gnisuoh5.31gPdna02M,TPNni
)21etoN(5T/6TCIIdxE+4T/5T/6TCIIaixEAASailartsuAsdradnatSotfoorpemalFytefaScisnirtnI
htiwylno(lavorppa)MF(lautuMyrotcaF
1
/
2
)noitcennoclacirtcele5.31gPdna02M,TPNni
1E
2E
3E
4E
5E
6E
retemtuptuO
noitarbilacdradnatS,reteMorP
noitarbilaclaicepS,reteMorP
elacs%0010raenilrotacidnituptuogolanA
)elacsraenilrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)noitarugifnocremotsucreteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
1D
2D
3D
5D
7D
8D
DCLlargetnI
yalpsidlargetniDCLlatigiD 1L
)lairetamdnaepahs(tekcarbgnitnuoM
gnitnuomepiproF
gnitnuomepiproF
gnitnuomllawroF
gnitnuomllawroF
xobrofepyttalF
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
leetsnobraC
ssL613ISIA
leetsnobraC
ssL613ISIA
ssL613ISIA
1B
2B
3B
4B
5B
egruS
rotcetorPtneisnarT/egruS )21etoN( 1S
launamgnitarepO
namreG
nailatI
hcnerF
1M
2M
4M
egaugnalgat&slebaL
namreG
nailatI
hcnerF
1T
2T
4T
etalpgatlanoitiddA
etalpleetssselniatsnogatfognitnirpresaL 2I
noitarugifnoC
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°4taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°4taisp/O
motsuC
2N
3N
4N
5N
6N
erudecorpnoitaraperP
P)teksagEFTPdnalliftrenihtiwelbaliavaylno(gninaelcecivresnegyxO
xam
T;nobracolaHrofaPM9ronedlaGrofaPM21=
xam
F°041/C°06=
noitaraperpecivresnegordyH
noitaraperpsecivreslaicepS
1P
2P
4P
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
21
Note 1: Suitable for oxygen service
Note 2: Not available with sensor code E
Note 3: Select type in additional ordering code
Note 4: Not available with Electronic Housing code Z, R, G and W
Note 5: Not available with Electronic Housing code P, E and K
Note 6: Not available with Process flanges/adapters code D, E, G, H, Q, T, M, S, U, V
Note 7: Not available with Process flanges/adapters code D, E, G, H, M, S, U, V
Note 8: Not available with Process flanges/adapters code A, B, G, H, Q, T, M, S, U, V
Note 9: Not available with Process flanges/adapters code A, B, G, H, Q, T, U, V
Note 10: Not available with Process flanges/adapters code A, B, D, E, Q, T, M, S, U, V
Note 11: Not available with Process flanges/adapters code A, B, D, E, Q, T, M, S
Note 12: Not available with PROFIBUS PA and FF output code 2 or 3
Note 13: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B, J, Y
Hastelloy is a Cabot Corporation trademark
Monel is an International Nickel Co. trademark
Viton is a Dupont de Nemour trademark
Galden is a Montefluos trademark
Halocarbon is a Halocarbon Products Co. trademark
Standard delivery items (can be differently specified by additional ordering code)
Adapters supplied loose
Plug on axis of horizontal connection flange; nothing for vertical connection blind flange (no drain/vent valves)
General purpose (no electrical certification)
No meter/display, no mounting bracket, no surge protection
English manual and labels
Configuration with kPa and deg. C units
No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S
RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
SV462ledomrofNOITAMROFNIGNIREDROLANOITIDDA XXXX XX
setacifitreC
)tniop-9(noitarbilacfoB.1.340201NEetacifitrecnoitcepsnI
ngisedtnemurtsnifo1.240201NEredroehthtiwecnailpmocfoetacifitreC
1C
6C
ytilibaecartlairetaM
strapdettewssecorpfo1.240201NEredroehthtiwecnailpmocfoetacifitreC
strapdettewssecorpfoB.1.340201NEetacifitrecnoitcepsnI
1H
3H
rotcennoC
8/7subdleiF
1x21MsubdleiF
yrtnethgiartsnaHgnitraH
yrtneelgnanaHgnitraH
)subdleiFNOITADNUOFrofDEDNEMMOCER(
)APSUBIFORProfDEDNEMMOCER(
)31,5setoN(
)31,5setoN(
)31,4setoN(
)31,4setoN(
1U
2U
3U
4U
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
22
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
23
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_2
ABB Ltd
Howard Road, St. Neots
Cambridgeshire, PE19 3EU
UK
Tel: +44(0)1480 475321
Fax: +44(0)1480 217948
ABB Inc.
125 E. County Line Road
Warminster, PA 18974
USA
Tel: +1 215 674 6000
Fax: +1 215 674 7183
ABB SACE spa
Business Unit Instrumentation
Via Statale 113
22016 Lenno (CO) Italy
Tel: +39 0344 58111
Fax: +39 0344 56278
SS/264XS_2
ABB has Sales & Customer Support
expertise in over 100 countries worldwide
www.abb.com/instrumentation
The Company’s policy is one of continuous product
improvement and the right is reserved to modify the
information contained herein without notice.
Printed in Italy (01.04)
© ABB 2004