http://www.tracopower.com Page 2 of 5
Enclosed Power Supplies
TZL Series 60–300 Watt
Input Specifications
Input current (at full load) 19 Vin 36 Vin
TZL 060 models 4.6 A typ. 2.4 A typ.
TZL 100 models 8.0 A typ. 4.0 A typ.
TZL 150 models 12 A typ. 6.3 A typ.
TZL 300 models -- 30 A typ.
Recommended circuit breaker TZL 060 models 5 A
(characteristic C) or slow blow fuse TZL 100 models 10 A
TZL 150 models 15 A
TZL 300 models 20 A
Output Specifications
Output voltage adjustment range ±10 %
Regulation – Input variation 1 % max.
– Load variation (10–100%) 1 % max.
Minimum Load not required
Ripple and noise (20 MHz bandwidth) 12 VDC output <100mVpk-pk
24 VDC output <150mVpk-pk
Output current limitation 105 % – 150 % of Iout max.
Overload protection mode Fold back, automatic recovery
Over voltage protection (only output 1) 115 % – 140 % of Vout nom.
Short circuit protection foldback, automatic recovery
Capacitive load, max. TZL 060: 12 VDC / 24 VDC output models 11’000 µF / 2‘000 µF
TZL 100: 12 VDC / 24 VDC output models 14’200 µF / 1‘000 µF
TZL 150: 12 VDC / 24 VDC output models 8’600 µF / 470 µF
TZL 300: 12 VDC / 24VDC output models 2’700 µF / 1‘000 µF
General Specifications
Temperature ranges – Operating –10°C to +60°C
– Load derating above 50°C 2.5 %/K
– Storage (non operating) –10°C to +75°C
Temperature coefficient 0.03 %/°C
Efficiency ~80 % (depending on model and load)
Humidity (non condensing) 85 % rel max. (non condensing)
Switching frequency 50 kHz typ. (pulse width modulation)
Hold-up time 20 ms min.
Isolation voltage (60sec.) – Input/Output 1‘500 VAC
– Input/Case 1‘500 VAC
– Output/Case 500 VAC
Reliability /calculated MTBF (MIL-HDBK-217F, at+25°C, ground benign) >250’000 h
Electromagnetic compatibility
(EMC) EN 61000-6-1
Electromagnetic compatibility
(EMC), radiated emission EN 55022, class B
Casing material cover: nickel plated steel
chassis: natural aluminium
Environmental compliance – Reach www.tracopower.com/overview/tzl
– RoHS RoHS directive 2011/65/EU
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.