MINI-PS-100-240AC/24DC/1.3 Order No.: 2866446
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866446
PHOENIX CONTACT Inc., USA Page 3 / 7
http://www.phoenixcon.com Apr 15, 2009
Current limitation Approx. 5 A (for short circuit)
Control deviation < 1 % (change in load, static 10% ... 90%)
< 3 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Residual ripple < 20 mVPP
Peak switching voltages nominal load < 50 mVPP
Maximum power dissipation idling 1.5 W
Power loss nominal load max. 6.5 W
General data
Width 22.5 mm
Height 99 mm
Depth 107 mm
Weight 0.2 kg
Operating voltage display LED green
Efficiency > 85 % (At 230 V AC and nominal values)
Insulation voltage input/output 3 kV (routine test)
4 kV (type test)
Degree of protection IP20
Class of protection II (in an enclosed control cabinet)
MTBF > 500 000 h in acc. with IEC 61709 (SN 29500)
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25°C, no condensation)
Mounting position Horizontal DIN rail NS 35, EN 60715
Assembly instructions Can be aligned: Horizontal 0 cm, vertical 5 cm
Electromagnetic compatibility Conformance with EMC guideline 2004/108/EC and for low-
voltage guideline 2006/95/EC
Immunity to interference EN 61000-6-2:2005
Standard – Electrical equipment of machines EN 60204
Standard - Safety of transformers EN 61558-2-17
Standard - Electrical safety EN 60950/VDE 0805 (SELV)
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage EN 60950 (SELV)
EN 60204 (PELV)