C251-01-01B SPECIFICATIONS
MODEL
ITEMS
1 Nominal Output Voltage (*1) V12 28 48
2 Maximum Output Current A60 36 21
3 Maximum Output Power W720 1008 1008
4 Efficiency (Typ.) (*1) %80 / 82 84 / 86 84 / 86
5 Input Voltage Range (*2) (*3) -85 - 265 VAC
6 Input Frequency (*2) Hz 47 - 63
7 Input Current (*1) A9.8 / 4.8 13.6 / 6.6 13.4 / 6.5
8 Power Factor (*1)(*3) -0.95 min
9 Output Voltage Accuracy %+/-2
10 Output Voltage Range %-20 / +20
11 Maximum Ripple & Noise (*3) mV 120 280 480
12 Maximum Line Regulation mV 48 56 96
13 Maximum Load Regulation mV 48 56 96
14 Over Current Protection (*4)(*5) -105% - 140%
15 Over Voltage Protection (*5) -125% - 145% (Inverter shutdown method)
16 In-rush Current (Typ.) (*1)(*3) A20A / 40A peak
17 Remote Sensing (*6) -Possible
18 Remote ON/OFF Control (*6) -Possible
19 Parallel Operation (*6) -Possible
20 Series Operation (*6) -Possible
21 Operating Temperature (*7)(*8) -
22 Operating Humidity - 20 - 95%RH (No Dewdrop)
23 Storage Temperature --40°C - +100°C
24 Storage Humidity - 10 - 95%RH (No Dewdrop)
25 Cooling (*9) -Conduction Cooled
26 Withstand Voltage -Input-Baseplate : 2.5kVAC, Input-Output : 3.0kVAC for 1min.
Output-Baseplate : 500VDC for 1min.
27 Isolation Resistance -Output to Baseplate 500VDC more than 100MΩ (25°C,70%RH)
28 Vibration -At no operating, 10-55Hz (Sweep for 1min.)
Amplitude 0.825mm constant (Maximum 49.0m/s
) X,Y,Z 1 hour each
29 Shock -196.1m/s
30 Safety -Approved by UL60950-1, CSA60950-1, EN60950-1
31 Weight (Typ.) g 500
32 Size (W x H x D) mm 100 x 13.4 x 160 (Refer to Outline Drawing)
* Read instruction manual carefully, before using the power module.
=NOTES=
*1. At 100VAC/200VAC and maximum output power. (Baseplate Temperature = +25°C.)
*2. For cases where conformance to various safety specs
(UL, CSA, EN) are required, input voltage range will be 100 - 240VAC(50/60Hz).
*3. External components are needed for operation.
(Refer to basic connection and instruction manual.)
*4. Constant current limiting.
(The unit automatically shutdown when left in OCP condition, with the output voltage
less than the LVP level. Refer to instruction manual.)
*5. Reset : Line off or Control off. (Refer to instruction manual.)
*6. Refer to Instruction manual.
*7. Ambient Temperature min=-40°C
*8. Ratings - refer to Derating Curve (C251-01-02_).
*9. Heatsink has to be chosen according to Instruction manual.
PFE1000F-12 PFE1000F-28 PFE1000F-48
-40°C - +100°C(Baseplate)