SPECIFICATION
MDR-60-5 MDR-60-12 MDR-60-24 MDR-60-48
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
OUTPUT VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME Note.5
HOLDUP TIME (Typ.)
VOLTAGERANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
ACCURRENT (Typ.)
INPUT
INRUSHCURRENT (Typ.)
SAFETY STANDARDS
HARMONICCURRENT
EMSIMMUNITY
WORKINGHUMIDITY
WORKINGTEMP.
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
5V 12V 24V 48V
10A 5A 2.5A 1.25A
0~10A 0~5A 0~2.5A 0~1.25A
50W 60W 60W 60W
80mVp-p 120mVp-p 150mVp-p
24~30V
200mVp-p
48~56V
2.0% 1.0% 1.0% 1.0%
12~15V5~6V
1.0% 1.0% 1.0% 1.0%
1.5% 1.0% 1.0% 1.0%
500ms,30ms/230VAC500ms,30ms/115VAC atfullload
50ms/230VAC20ms/115VAC atfullload
85~264VAC120~370VDC
47~63Hz
78% 86% 88% 87%
1.8A/115VAC1A/230VAC
COLDSTART 30A/115VAC60A/230VAC
105~150% ratedoutputpower
Protectiontype: Constantcurrentlimiting,recoversautomaticallyafterfaultconditionisremoved
6.25~7.25V
Protectiontype:Shutdowno/pvoltage,re-powerontorecover
15.6~18V 31.2~36V 57.6~64.8V
-20~+70 (Refertooutputloadderatingcurve)
20~90%RHnon-condensing
-40~+85 ,10~95%RH
0.03%/ (0~50
Component: eachalongX, Y,Zaxes;Mounting:CompliancetoIEC60068-2-610~500Hz,2G10min./1cycle,periodfor60min.
299.2Khrsmin.MIL-HDBK-217F(25 )
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
FileName:MDR-60-SPEC2010-12-07
UL508,UL60950-1, pproved,NECclass2/LPScompliant(24V,48Vonly)TUVEN60950-1a
Complianceto EN61000-3-2,-3
60WSingleOutputIndustrialDINRailPowerSupply MDR-60 seri e s
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
ENVIRONMENT
PROTECTION
SAFETY &
EMC
(Note4)
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
EMICONDUCTION&RADIATION
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
NEC class 2 / LPS compliant (24V,48V only)
LED indicator for power on
DC OK relay contact
No load power consumption<0.75W
100% full load burn-in test
3 years warranty
Features :
40*90*100mm(W*H*D)
0.33Kg;42pcs/14.8Kg/0.82CUFT
LEAKAGECURRENT <1mA /240VAC
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:>100MOhms/500VDC/25 /70%RH
FUNCTION DCOKSIGNAL Relaycontactrating(max.):30V/1A resistive
CompliancetoEN55011,EN55022(CISPR22),EN61204-3ClassB
CompliancetoEN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2,EN61204-3,heavyindustrylevel,criteria A
http://store.iiic.cc/