Output Current Ratings
The continuous current-source capability is 40mA per
output. Outputs can drive up to 75mA as a repetitive
peak current, subject to the on-time (output high) being
no longer than 1ms, and the duty cycle being such that
the output power dissipation is no more than the dissipa-
tion for the continuous case. The repetitive peak rating
allows outputs to drive a higher current in multiplex grid
driver applications, where only one grid is on at a time,
and the multiplex time per grid is no more than 1ms.
Since dissipation is proportional to current squared, the
maximum current that can be delivered for a given mul-
tiplex ratio is given by:
IPEAK = (grids x 1600)1/2 mA
where grids is the number of grids in a multiplexed
display.
This means that a duplex application (two grids) can use
a repetitive peak current of 56.5mA, a triplex (three grids)
application can use a repetitive peak current of 69.2mA,
and higher multiplex ratios are limited to 75mA.
Paralleling Outputs
Any number of outputs within the same package can
be paralleled in order to raise the current drive or
reduce the output resistance. Only parallel outputs
directly (by shorting outputs together) if the interface
control can be guaranteed to set the outputs to the
same level. Although the sink output is relatively weak
(typically 750Ω), that resistance is low enough to dissi-
pate 530mW when shorted to an opposite level output
at a VBB voltage of only 20V. A safe way to parallel out-
puts is to use diodes to prevent the outputs from sink-
ing current (Figure 5). Because the outputs cannot sink
current from the VFD tube, an external discharge resis-
tor, R, is required. For static tubes, R can be a large
value such as 100kΩ. For multiplexed tubes, the value
of the resistor can be determined by the load capaci-
tance and timing characteristics required. Resistor R
discharges tube capacitance C to 10% of the initial
voltage in 2.3 x RC seconds. So, for example, a 15kΩ
value for R discharges 100pF tube grid or anode from
40V to 4V in 3.5µs, but draws an additional 2.7mA from
the driver when either output is high.
Power Dissipation
Take care to ensure that the maximum package dissi-
pation ratings for the chosen package are not exceed-
ed. Over-dissipation is unlikely to be an issue when
driving static tubes, but the peak currents are usually
higher for multiplexed tubes. When using multiple dri-
ver devices, try to share the average dissipation evenly
between the drivers.
Determine the power dissipation (PD) for the
MAX6921/MAX6931 for static tube drivers with the fol-
lowing equation:
PD= (VCC x ICC) + (VBB x IBB) + ((VBB - VH)
x IANODE x A)
where:
A = number of anodes driven (the MAX6921/MAX6931
can drive a maximum of 20).
IANODE = maximum anode current.
(VBB - VH) is the output voltage drop at the given maxi-
mum anode current IOUT.
A static tube dissipation example follows:
VCC = 5V ±5%, VBB = 10V to 18V, A = 20, IOUT = 2mA
PD= (5.25V x 1mA)+ (18V x 1.4mA) +
((2.5V x 2mA/25mA) x 2mA x 20) = 38mW
Determine the power dissipation (PD) for the MAX6921/
MAX6931 for multiplex tube drivers with the following
equation:
PD= (VCC x ICC) + (VBB x IBB) + ((VBB - VH)
x IANODE x A) + ((VBB - VH) x IGRID)
where:
A = number of anodes driven.
G = number of grids driven.
IANODE = maximum anode current.
IGRID = maximum grid current.
The calculation presumes all anodes are on, but only
one grid is on. The calculated PDis the worst case,
presuming one digit is always being driven with all its
anodes lit. Actual PDcan be estimated by multiplying
this PDfigure by the actual tube drive duty cycle, taking
into account interdigit blanking and any PWM intensity
control.
MAX6921/MAX6931
20-Output, 76V, Serial-Interfaced
VFD Tube Drivers
_______________________________________________________________________________________ 9