09/64
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Instrument Transformers
Through-type CT/CC3M
AF00-107
Notes: *1 Busbar mounting brackets are sold separately. When ordering, specify
the CT type number and rated primary current. If the rated primary
current is 1000 to 2000A, also specify the number of busbars required.
*2 Epoxy resin mold is used to isolate rated primary currents of 5000 or 6000A.
CC3M rectangular hole through-
type current transformers
Primary current: 150 to 6000A
Secondary current: 5A
■Description
CC3M CTs can be mounted vertically or
horizontally by changing the position of
the mounting base. Also, the busbar can
be mounted directly using a mounting
bracket as illustrated, so a busbar
mounting angle or holes are not
required.
Vertical mounting
Horizontal mounting
Busbar connectoin
Busbar
bracket *1
CC3M
■
Types and ratings
Secondary
current
(A)
5 or 1
5 or 1
5 or 1
5 or 1
5 or 1
5 or 1
5 or 1
5
5
Rated primary
current
(A)
150
200
250
300
200
250
300
400
500
600
750
800
1000
1200
1500
2000
2500
3000
4000
5000
6000
*
2
*
2
Type
CC3M2-150
CC3M2-200
CC3M2-250
CC3M2-300
CC3M2-400
CC3M2-500
CC3M2-600
CC3M2-750
CC3M2-800
CC3M2-10X
CC3M2-12X
CC3M2-15X
CC3M2-20X
400
500
600
750
800
1000
1200
1500
2000
CC3M3-200
CC3M3-250
CC3M3-300
CC3M3-400
CC3M3-500
CC3M3-600
CC3M3-750
CC3M3-800
CC3M3-10X
CC3M3-12X
CC3M3-15X
CC3M3-20X
CC3M3-25X5
CC3M3-30X5
CC3M3-40X5
CC3M3-50X5
CC3M3-60X5
Accuracy
class
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Thermal limit
current
40 times rated
primary current
40 times rated
primary current
Max. voltage
(kV rms.)
1.15kV
1.15kV
1.15kV
1.15kV
1.15kV
1.15kV
1.15kV
1.15kV
1.15kV
Burden
(VA)
15
40
Dielectric
strength
(kV 1 min.)
4.0kV
4.0kV
4.0kV
4.0kV
4.0kV
4.0kV
4.0kV
4.0kV
4.0kV
Mass
(kg)
2.1
5CC3M1-1505
CC3M1-2005
CC3M1-3005
CC3M1-4005
CC3M1-5005
CC3M1-6005
150
200
300
400
500
600
1.0 40 times rated
primary current
1.15kV 5 4.0kV 2.1
1.1
0.6
1.2
0.5
2.3
1.1
1.1
0.9
1.3
1.2
1.5
1.1
0.6
4.8
6.3
14
• CC3M CTs are mounted vertically at the factory.
• Replace the mark by the secondary current code.
5: 5A 1: 1A