AMPERE WATTS AMPERE WATTS AMPERE WATTS
RATING LOSS (w) RATING LOSS (w) RATING LOSS (w)
70 4.4 250 19 1000 57
80 5.1 300 22 1200 70
90 5.5 350 26 1500 88
100 6.5 400 30 2000 122
125 7.6 450 32 2500 142
150 9.3 500 37 3000 164
175 11 600 45 3500 191
200 13 700 55 4000 198
225 15 800 51 4500 211
5000 228
Watts Loss at Rated Current
Percent Rated Current
Correction Factor for Watts Loss
Watts Loss Correction vs. Percent Rated Current
I2t Data – 250 Volts AC
I2t DATA
FUSE CLEARING AT 250V
AMPERE MELTING 1 FUSE 2 FUSES IN
RATING (FIG. A) SERIES (FIG. B)
(A2s) (A2s) (A2s)
1 .033 .27 .18
2 .17 1.5 .98
3 .32 3.8 2.5
4 .85 6.9 4.6
5 1.3 8.7 5.8
6 1.9 9.6 6.4
7 2.7 13 8.4
8 5.0 24 16
9 8.6 31 21
10 13 39 26
12 18 54 36
15 20 60 40
20 36 110 72
25 56 170 110
30 81 240 160
35 95 540 380
40 120 690 460
50 190 960 640
60 280 1,400 960
70 420 3,500 2,100
80 550 4,600 2,300
90 700 5,800 2,500
100 860 7,200 3,000
125 1,300 11,000 4,100
150 2,000 16,000 6,000
175 2,600 22,000 8,000
200 3,400 29,000 11,000
225 4,300 36,000 13,000
250 5,400 45,000 16,000
300 7,700 65,000 24,000
350 11,000 88,000 32,000
400 14,000 110,000 42,000
450 18,000 140,000 53,000
500 22,000 180,000 66,000
600 31,000 260,000 95,000
700 42,000 350,000 130,000
800 55,000 460,000 170,000
1,000 86,000 720,000 260,000
1,200 125,000 1,000,000 380,000
1,500 200,000 1,600,000 600,000
1,600 220,000 1,800,000 680,000
2,000 350,000 2,900,000 1,100,000
2,500 550,000 4,500,000 1,600,000
Load
250 VAC Fault
Fig. A
Load
250 VAC Fault
Fig. B
AMP-TRAP®–Form 101
A25X SEMICONDUCTOR PROTECTION FUSES