Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
G-TWIN Standard Series (IEC/EN/GB/JIS conformed)
Line protection
• 2-pole
AC230V (Icu) EW32 EW50 EW100
2.5kA AAG-2P AAG-2P
10kA EAG-2P
• 2-pole
AC230V (Icu) EW100
10kA EAGU-2P
• 3-pole
AC415V (Icu) EW50 EW100 EW125 EW250 EW400 EW630
10kA RAGU-3P EAGU-3P
30kA JAGU-3P JAGU-3P
36kA SAGU-3P
50kA RAGU-3P RAGU-3P RAGU-3P RAGU-3P
70kA HAGU-3P
HG Series
Line protection (3-pole)
AC415V (Icu) 50AF 100AF 225AF
65kA HG53B HG103B HG203B
Earth Leakage Circuit Breakers
List of products
Motor protection
• 3-pole
AC415V (Icu) EW32 EW50 EW63 EW100 EW125 EW250
1.5kA EAM-3P
2.5kA SAM-3P EAM-3P EAM-3P
7.5kA SAM-3P SAM-3P
10kA EAM-3P
18kA EAM-3P
30kA JAM-3P JAM-3P
50kA RAM-3P RAM-3P
• 3-pole
AC415V (Icu) EW32 EW50 EW63 EW100 EW125 EW160 EW250 EW400 EW630 EW800
1.5kA EAG-3P
2.5kA SAG-3P EAG-3P EAG-3P
7.5kA SAG-3P SAG-3P
10kA RAG-3P RAG-3P EAG-3P
18kA EAG-3P EAG-3P
30kA JAG-3P JAG-3P JAG-3P EAG-3P
36kA SAG-3P SAG-3P SAG-3P SAG-3P EAG-3P EAG-3P
50kA RAG-3P RAG-3P RAG-3P RAG-3P RAG-3P RAG-3P
70kA HAG-3P HAG-3P HAG-3P
• 4-pole
AC415V (Icu) EW125 EW160 EW250 EW400
30kA JAG-4P JAG-4P JAG-4P
36kA SAG-4P SAG-4P SAG-4P
50kA RAG-4P RAG-4P RAG-4P RAG-4P
70kA HAG-4P
G-TWIN Global Series (IEC/EN/GB/JIS/UL/CSA conformed)
Line protection
07/2 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Type number nomenclature
Earth Leakage Circuit Breakers
G-TWIN series
Type number nomenclature
Rated current
See page 07/29.
Rated sensitive current
A: 15mA J: 100/300/500/1000mA
B: 30mA K: 100/200mA
C: 100mA 100/200/500mA
D: 50mA 100/200/500/1000mA
No. of poles
2P: 2-pole 3P: 3-pole 4P: 4-pole
G-TWIN series
Blank: Standard U: Global
Model
G: Line protection M: Motor protection
Breaking capacity
Rated breaking capacity Icu (440V AC) *(at 230V AC)
32AF 50AF 63AF 100AF 125AF 160AF 250AF 400AF 630AF 800AF
AA 2.5kA* 2.5kA* 5kA*
EA 1.5kA 2.5kA 2.5kA 10kA 18kA 18kA 30kA 36kA 36kA
JA 30kA 30kA 30kA
SA 2.5kA 7.5kA 7.5kA 36kA 36kA 36kA 36kA
RA 10kA 10kA 50kA 50kA 50kA 50kA 50kA 50kA
HA 70kA 70kA 70kA
Frame size
32: 32AF 63: 63AF 125: 125AF 250: 250AF 630: 630AF
50: 50AF 100: 100AF 160: 160AF 400: 400AF 800: 800AF
Series
EW: G-TWIN series ELCB
EW 250 EA G - 3P 225 B X
Mounting and connection
• Standard type
Blank: Front mounting, front connection
X: Front mounting, rear connection
E: Flush mounting, rear connection
Y: Flush mounting, top & buttom connection
P: Plug-in mounting
Auxiliary switch*
W: Standard SPDT
V: Standard 2PDT
1: For low level circuit SPDT
2: For low level circuit 2PDT
Alarm switch*
K: Standard SPDT
J: Standard 2PDT
8: For low level circuit SPDT
9: For low level circuit 2PDT
Undervoltage trip device (Internal)*
125/160/250AF
: DC24V
: DC48V
: DC100-110V
:
DC125V / AC100-110V
: AC110-130V
: AC200-240V
: AC277V
: AC380-415V
Undervoltage trip device (External)*
32/50/63/100AF
: DC24V
: DC100-110V
: AC100V (50Hz) / AC100-110V (60Hz)
: AC200V (50Hz) / AC200-220V (60Hz)
: AC400V (50Hz) / AC400-440V (60Hz)
Connection method (internal accessories)
Blank: Lead-wire system
A: Terminal block system
W K F R A Q2 M UC
* For the available configuration of accessory,
see page 07/62.
Shunt trip device (Internal)*
125/160/250AF 400/630/800AF
: AC/DC24V : AC/DC24-48V
: AC/DC48V :
AC100-240V / DC100-220V
: AC
100-120V / DC100-110V
: AC277V
: AC120-130V : AC380-550V
: AC
200-240V / DC200-220V
: AC277V
: AC380-440V
: AC440-480V
: AC500-550V
Shunt trip device (External)*
32/50/63/100AF
: DC24V
: DC100-110V
: AC100 (50Hz) / AC100-110V (60Hz)
: AC200 (50Hz) / AC200-220V (60Hz)
: AC400 (50Hz) / AC400-440V (60Hz)
Pad locking device
Q2: Plate type
With motor operating device (32 - 100AF)
: DC100V
AC100-110V
AC200-220V
Enclosure
UC: Standard
UV: Dust-proof
UW: Rain-proof
Terminal combination (Global type)
Terminal position Applicable breaker type
Code
Blank
Blank
SB
SF
S3
S4
S5
S6
S7
S8
Line
Screw
Flat teminal
Block terminal
Flat teminal
Screw
Flat teminal
Screw
Block terminal
Flat teminal
Block terminal
Load
Screw
Flat teminal
Block terminal
Flat teminal
Flat terminal
Screw
Block terminal
Screw
Block terminal
Flat terminal
EW50, 100
EW125, 250
EW400, 630
400/630/800AF
: AC/DC24V
: AC/DC48V
: AC/DC100-110V
:
AC120-130V / DC125V
:
AC200-240V / DC200-220V
: AC277V
: AC380-480V
07/3
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Rated current
See page 07/29.
Rated sensitive current
A: 15mA J: 100/300/500/1000mA
B: 30mA K: 100/200mA
C: 100mA 100/200/500mA
D: 50mA 100/200/500/1000mA
No. of poles
2P: 2-pole 3P: 3-pole 4P: 4-pole
G-TWIN series
Blank: Standard U: Global
Model
G: Line protection M: Motor protection
Breaking capacity
Rated breaking capacity Icu (440V AC) *(at 230V AC)
32AF 50AF 63AF 100AF 125AF 160AF 250AF 400AF 630AF 800AF
AA 2.5kA* 2.5kA* 5kA*
EA 1.5kA 2.5kA 2.5kA 10kA 18kA 18kA 30kA 36kA 36kA
JA 30kA 30kA 30kA
SA 2.5kA 7.5kA 7.5kA 36kA 36kA 36kA 36kA
RA 10kA 10kA 50kA 50kA 50kA 50kA 50kA 50kA
HA 70kA 70kA 70kA
Frame size
32: 32AF 63: 63AF 125: 125AF 250: 250AF 630: 630AF
50: 50AF 100: 100AF 160: 160AF 400: 400AF 800: 800AF
Series
EW: G-TWIN series ELCB
EW 250 EA G - 3P 225 B X
Mounting and connection
• Standard type
Blank: Front mounting, front connection
X: Front mounting, rear connection
E: Flush mounting, rear connection
Y: Flush mounting, top & buttom connection
P: Plug-in mounting
Auxiliary switch*
W: Standard SPDT
V: Standard 2PDT
1: For low level circuit SPDT
2: For low level circuit 2PDT
Alarm switch*
K: Standard SPDT
J: Standard 2PDT
8: For low level circuit SPDT
9: For low level circuit 2PDT
Undervoltage trip device (Internal)*
• 125/160/250AF
: DC24V
: DC48V
: DC100-110V
:
DC125V / AC100-110V
: AC110-130V
: AC200-240V
: AC277V
: AC380-415V
Undervoltage trip device (External)*
• 32/50/63/100AF
: DC24V
: DC100-110V
: AC100V (50Hz) / AC100-110V (60Hz)
: AC200V (50Hz) / AC200-220V (60Hz)
: AC400V (50Hz) / AC400-440V (60Hz)
Connection method (internal accessories)
Blank: Lead-wire system
A: Terminal block system
W K F R A Q2 M UC
* For the available configuration of accessory,
see page 07/62.
Shunt trip device (Internal)*
• 125/160/250AF • 400/630/800AF
: AC/DC24V : AC/DC24-48V
: AC/DC48V :
AC100-240V / DC100-220V
: AC
100-120V / DC100-110V
: AC277V
: AC120-130V : AC380-550V
: AC
200-240V / DC200-220V
: AC277V
: AC380-440V
: AC440-480V
: AC500-550V
Shunt trip device (External)*
• 32/50/63/100AF
: DC24V
: DC100-110V
: AC100 (50Hz) / AC100-110V (60Hz)
: AC200 (50Hz) / AC200-220V (60Hz)
: AC400 (50Hz) / AC400-440V (60Hz)
Pad locking device
Q2: Plate type
With motor operating device (32 - 100AF)
: DC100V
AC100-110V
AC200-220V
Enclosure
UC: Standard
UV: Dust-proof
UW: Rain-proof
Terminal combination (Global type)
Terminal position Applicable breaker type
Code
Blank
Blank
SB
SF
S3
S4
S5
S6
S7
S8
Line
Screw
Flat teminal
Block terminal
Flat teminal
Screw
Flat teminal
Screw
Block terminal
Flat teminal
Block terminal
Load
Screw
Flat teminal
Block terminal
Flat teminal
Flat terminal
Screw
Block terminal
Screw
Block terminal
Flat terminal
EW50, 100
EW125, 250
EW400, 630
• 400/630/800AF
: AC/DC24V
: AC/DC48V
: AC/DC100-110V
:
AC120-130V / DC125V
:
AC200-240V / DC200-220V
: AC277V
: AC380-480V
Earth Leakage Circuit Breakers
G-TWIN series
Type number nomenclature
07/4 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Ampere frame 32A
Type EW32AAG EW32EAG EW32SAG
Pole 2 3 3 3
Rated current Reference amb. temp. (40°C)
In(A) 5, 10, 15, 20, 30, 32 5, 10, 15, 20, 30, 32 5, 10, 15, 20, 30, 32 3, 5, 10, 15, 20, 30, 32
Rated impulse withstand voltage Uimp(kV) 2.5 4 4 4
Isolation compliant
Rated voltage Ue (AC V) 100-230 100-230 100-230-440 100-230-440
Rated sensitive current (mA) 15, 30, 100 15, 30, 100 15, 30, 100
30, 100/200/500 changeover
Tripping time (s) 0.1 or less 0.1 or less 0.1 or less 0.1 or less
Rated breaking
capacity
Icu/Ics (kA)
IEC 60947-2
EN 60947-2
JIS C 8201-2-2
AC 440V 1.5/1 2.5/2
415V 1.5/1 2.5/2
400V 1.5/1 2.5/2
380V 1.5/1 2.5/2
230V 2.5/2 2.5/2 2.5/2 5/3
200V 2.5/2 2.5/2 2.5/2 5/3
100V 2.5/2 5/3 5/3 5/3
GB14048.2 AC 400V 1.5/1 2.5/2
230V 2.5/2 2.5/2 2.5/2 5/3
Conforming to
standards CE Marking (TÜV) (TÜV) (TÜV) (TÜV)
CCC certificate
Electrical Appliance and Material Safety Law *1
Dimensions (mm) a 50 75 75 75
b 100 100 100
c 60 60 60
d 84 84 84
Mass (kg) 0.4 0.5 0.5 0.6
Tripping device Hydraulic-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Flush mounting, top & bottom connection Y
Plug-in mounting P
IEC 35mm wide rail mounting No-mark
Internal accessories Page 07/57
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Handle padlocking device Cap type QN
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Earth BL
Handle locking cover L1
Flat terminal SS
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan
G-TWIN Standard Series
c
a d
b
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
Rated voltage (V) Operational voltage range (V)
100–230 80–264
100–230–440 80–484
07/5
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Ampere frame 50A
Type EW50AAG EW50EAG EW50SAG EW50RAG
Pole 2 3 3 3 3
Rated current Reference amb. temp. (40°C)
In(A)
5, 10, 15, 20, 30, 32, 40, 50 5, 10, 15, 20, 30, 32, 40, 50 5, 10, 15, 20, 30, 32, 40, 50
10, 15, 20, 30, 32, 40, 50
Rated impulse withstand voltage Uimp(kV) 2.5 4 6 6 6
Isolation compliant
Rated voltage Ue (AC V) 100-230 100-230-440 100-230-440 100-230-440
Rated sensitive current (mA) 15, 30, 100
15, 30, 100/200 changeover 30, 100/200/500 changeover 30, 100/200/500 changeover
Tripping time (s) 0.1 or less 0.1 or less 0.1 or less 0.1 or less
Rated breaking
capacity
Icu/Ics (kA)
IEC 60947-2
EN 60947-2
JIS C 8201-2-2
AC 440V 2.5/2 7.5/4 10/5
415V 2.5/2 7.5/4 10/5
400V 2.5/2 7.5/4 10/5
380V 2.5/2 7.5/4 10/5
230V 2.5/2 5/3 10/5 25/13
200V 2.5/2 5/3 10/5 25/13
100V 2.5/2 5/3 5/3 10/5 25/13
GB14048.2 AC 400V 2.5/2 7.5/4 10/5
230V 2.5/2 5/3 10/5 25/13
Conforming to
standards CE Marking (TÜV) (TÜV) (TÜV) (TÜV)
CCC certificate
Electrical Appliance and Material Safety Law *1
Dimensions (mm) a 50 75 75 75 75
b 100 100 100 100
c 60 60 60 60
d 84 84 84 84
Mass (kg) 0.4 0.6 0.6 0.6 0.6
Tripping device Hydraulic-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Flush mounting, top & bottom connection Y
Plug-in mounting P
IEC 35mm wide rail mounting No-mark
Internal accessories Page 07/57
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Handle padlocking device Cap type QN
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Earth BL
Handle locking cover L1
Flat terminal SS
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan
c
a d
b
G-TWIN Standard Series
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
Rated voltage (V) Operational voltage range (V)
100–230 80–264
100–230–440 80–484
07/6 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
G-TWIN Standard Series
Ampere frame 63A
Type EW63EAG EW63SAG EW63RAG
Pole 3 3 3
Rated current Reference amb. temp. (40°C)
In(A) 60, 63 60, 63 60, 63
Rated impulse withstand voltage Uimp(kV) 6 6 6
Isolation compliant
Rated voltage Ue (AC V) 100-230-440 100-230-440 100-230-440
Rated sensitive current (mA) 15, 30, 100/200 changeover 30, 100/200/500 changeover 30, 100/200/500 changeover
Tripping time (s) 0.1 or less 0.1 or less 0.1 or less
Rated breaking
capacity
Icu/Ics (kA)
IEC 60947-2
EN 60947-2
JIS C 8201-2-2
AC 440V 2.5/2 7.5/4 10/5
415V 2.5/2 7.5/4 10/5
400V 2.5/2 7.5/4 10/5
380V 2.5/2 7.5/4 10/5
230V 5/3 10/5 25/13
200V 5/3 10/5 25/13
100V 5/3 10/5 25/13
GB14048.2 AC 400V 2.5/2 7.5/4 10/5
230V 5/3 10/5 25/13
Conforming to
standards CE Marking (TÜV) (TÜV) (TÜV)
CCC certificate
Electrical Appliance and Material Safety Law *1
Dimensions (mm) a 75 75 75
b 100 100 100
c 60 60 60
d 84 84 84
Mass (kg) 0.6 0.6 0.6
Tripping device Hydraulic-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Flush mounting, top & bottom connection Y
Plug-in mounting P
IEC 35mm wide rail mounting No-mark
Internal accessories Page 07/57
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Handle padlocking device Cap type QN
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Earth BL
Handle locking cover L1
Flat terminal SS
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan
c
a d
b
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
Rated voltage (V) Operational voltage range (V)
100–230 80–264
100–230–440 80–484
07/7
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
G-TWIN Standard Series
Ampere frame 100A
Type EW100AAG EW100EAG
Pole 3 2 3
Rated current Reference amb. temp. (40°C)
In(A) 60, 63, 75, 100 50, 60, 63, 75, 100 50, 60, 63, 75, 100
Rated impulse withstand voltage Uimp(kV) 4 4 6
Isolation compliant
Rated voltage Ue (AC V) 100-230 100-230 100-230-400
Rated sensitive current (mA) 30, 100/200/500 changeover 30, 100/200 changeover 30, 100/200/500 changeover
Tripping time (s) 0.1 or less 0.1 or less 0.1 or less
Rated breaking
capacity
Icu/Ics (kA)
IEC 60947-2
EN 60947-2
JIS C 8201-2-2
AC 440V 10/5
415V 10/5
400V 10/5
380V 10/5
230V 5/3 10/5 25/13
200V 5/3 10/5 25/13
100V 5/3 10/5 25/13
GB14048.2 AC 400V 10/5
230V 5/3 10/5 25/13
Conforming to
standards CE Marking (TÜV) (TÜV) (TÜV)
CCC certificate
Electrical Appliance and Material Safety Law *1
Dimensions (mm) a 75 75 75
b 100 100 100
c 60 60 60
d 84 84 84
Mass (kg) 0.6 0.6 0.6
Tripping device Thermal -magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Flush mounting, top & bottom connection Y
Plug-in mounting P
IEC 35mm wide rail mounting No-mark
Internal accessories Page 07/57
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Handle padlocking device Cap type QN
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Earth BL
Handle locking cover L1
Flat terminal SS
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan
c
a d
b
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
Rated voltage (V) Operational voltage range (V)
100–230 80–264
100–230–440 80–484
07/8 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
G-TWIN Standard Series
c
a d
b
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
Ampere frame 125A
Type EW125JAG EW125SAG EW125RAG
Pole 3 4 3 4 3 4
Rated current Reference amb. temp. (40°C)
In(A) 15, 20, 30, 40, 50, 60, 75, 100, 125
Rated impulse withstand voltage Uimp(kV) 6 6 6
Isolation compliant
Rated voltage Ue (AC V) 100-230-440
Type of earth leakage trip action AC type
Instantaneous trip
type Rated sensitive current (mA) 30
Tripping time (s) 0.1 or less
Instantaneous/time-
delay trip type Rated sensitive current (mA) 100/300/500/1000 changeover
Tripping time (s) 0.1/0.4/1/2 changeover
Inertia non-tripping time (s) (2l n) 0/0.2/0.5/1
Rated breaking
capacity
Icu/Ics (kA)
IEC60947-2
EN60947-2
JISC8201-2-2
AC 440V 30/15 36/18 50/25
415V 30/15 36/18 50/25
400V 30/15 36/18 50/25
380V 30/15 36/18 50/25
230V 50/25 85/43 100/50
200V 50/25 85/43 100/50
100V 50/25 85/43 100/50
GB14048.2 AC 400V 30/15 36/18 50/25
230V 50/25 85/43 100/50
Conforming to
standards CE Marking (TÜV) (TÜV) (TÜV)
CCC certificate
Electrical Appliance and Material Safety Law *
1
(except for 125A) (except for 125A) (except for 125A)
Dimensions (mm) a 90 120 90 120 90 120
b 155 155 155
c 68 68 68
d 95 95 95
Mass (kg) 1.3 1.7 1.2 1.6 1.3 1.7
Tripping device Thermal-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Plug-in mounting P
Internal accessories Page 07/58
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Handle padlocking device Cap type Q1
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Handle locking cover L1
Flat terminal SS
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan Rated voltage (V) Operational voltage range (V)
100–230–440 80–484
07/9
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
G-TWIN Standard Series
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
Ampere frame 160A
Type EW160EAG EW160JAG EW160SAG EW160RAG
Pole 3 3 4 3 4 3 4
Rated current Reference amb. temp. (40°C)
In(A) 125, 150, 160
Rated impulse withstand voltage Uimp(kV) 6 6 6 6
Isolation compliant
Rated voltage Ue (AC V) 100-230-440
Type of earth leakage trip action AC type
Instantaneous trip
type Rated sensitive current (mA) 30
Tripping time (s) 0.1 or less
Instantaneous/time-
delay trip type Rated sensitive current (mA) 100/300/500/1000 changeover
Tripping time (s) 0.1/0.4/1/2 changeover
Inertia non-tripping time (s) (2l n) 0/0.2/0.5/1
Rated breaking
capacity
Icu/Ics (kA)
IEC60947-2
EN60947-2
JISC8201-2-2
AC 440V 18/9 30/15 36/18 50/25
415V 18/9 30/15 36/18 50/25
400V 18/9 30/15 36/18 50/25
380V 18/9 30/15 36/18 50/25
230V 36/18 50/25 85/43 100/50
200V 36/18 50/25 85/43 100/50
100V 36/18 50/25 85/43 100/50
GB14048.2 AC 400V 18/9 30/15 36/18 50/25
230V 36/18 50/25 85/43 100/50
Conforming to
standards CE Marking certified (TÜV) (TÜV) (TÜV) (TÜV) (TÜV)
CCC certificate
Dimensions (mm) a 105 105 140 105 140 105 140
b 165 165 165 165
c 68 68 68 68
d 95 95 95 95
Mass (kg) 1.8 1.8 2.3 1.8 2.3 1.8 2.3
Tripping device Thermal-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Plug-in mounting P
Internal accessories Page 07/58
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Handle padlocking device Cap type Q1
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Handle locking cover L1
Flat terminal SS
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan
c
a d
b
Rated voltage (V) Operational voltage range (V)
100–230–440 80–484
07/10 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
G-TWIN Standard Series
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
Ampere frame 250A
Type EW250EAG EW250JAG EW250SAG EW250RAG
Pole 3 3 4 3 4 3 4
Rated current Reference amb. temp. (40°C)
In(A) 175, 200, 225, 250
175,200,225 175,200,225,250 175,200,225 175,200,225,250 175,200,225
Rated impulse withstand voltage Uimp(kV) 6 6 6 6
Isolation compliant
Rated voltage Ue (AC V) 100-230-440
Type of earth leakage trip action AC type
Instantaneous trip
type Rated sensitive current (mA) 30
Tripping time (s) 0.1 or less
Instantaneous/time-
delay trip type Rated sensitive current (mA) 100/300/500/1000 changeover
Tripping time (s) 0.1/0.4/1/2 changeover
Inertia non-tripping time (s) (2l n) 0/0.2/0.5/1
Rated breaking
capacity
Icu/Ics (kA)
IEC60947-2
EN60947-2
JISC8201-2-2
AC 440V 18/9 30/15 36/18 50/25
415V 18/9 30/15 36/18 50/25
400V 18/9 30/15 36/18 50/25
380V 18/9 30/15 36/18 50/25
230V 36/18 50/25 85/43 100/50
200V 36/18 50/25 85/43 100/50
100V 36/18 50/25 85/43 100/50
GB14048.2 AC 400V 18/9 30/15 36/18 50/25
230V 36/18 50/25 85/43 100/50
Conforming to
standards CE Marking (TÜV) (TÜV) (TÜV) (TÜV)
CCC certificate
Dimensions (mm) a 105 105 140 105 140 105 140
b 165 165 165 165
c 68 68 68 68
d 95 95 95 95
Mass (kg) 1.8 1.8 2.3 1.8 2.3 1.8 2.3
Tripping device Thermal-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Plug-in mounting P
Internal accessories Page 07/58
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Handle padlocking device Cap type Q1
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Handle locking cover L1
Flat terminal SS
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan
c
a d
b
Rated voltage (V) Operational voltage range (V)
100–230–440 80–484
07/11
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
G-TWIN Standard Series
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
Ampere frame 400A
Type EW400EAG EW400SAG EW400RAG EW400HAG
Pole 3 3 3 4 3 4
Rated current Reference amb. temp. (40°C)
In(A) 250, 300, 350, 400
Rated impulse withstand voltage Uimp(kV) 6 6 6 6
Isolation compliant
Rated voltage Ue (AC V) IEC 100-230-440
Type of earth leakage trip action AC type
Instantaneous trip
type Rated sensitive current (mA) 30
Tripping time (s) 0.1 or less
Instantaneous/time-
delay trip type Rated sensitive current (mA) 100/300/500/1000 changeover
Tripping time (s) 0.1/0.4/1/2 changeover
Inertia non-tripping time (s) (2l n) 0/0.2/0.5/1
Rated breaking
capacity
Icu/Ics (kA)
IEC60947-2
EN60947-2
JISC8201-2-2
AC 440V 30/15 36/18 50/25 70/35
415V 30/15 36/18 50/25 70/35
400V 30/15 36/18 50/25 70/35
380V 30/15 36/18 50/25 70/35
230V 50/25 85/43 100/50 125/63
200V 50/25 85/43 100/50 125/63
100V 50/25 85/43 100/50 125/63
GB14048.2 AC 400V 30/15 36/18 50/25 70/35
230V 50/25 85/43 100/50 125/63
Conforming to
standards CE Marking (TÜV) (TÜV) (TÜV) (TÜV)
CCC certificate
Dimensions (mm) a 140 140 140 185 140 185
b 257 257 257 257
c 103 103 103 103
d 146 146 146 146
Mass (kg) 5.8 5.8 5.8 7.8 5.8 7.8
Tripping device Thermal-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Plug-in mounting P
Internal accessories Page 07/59
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Handle padlocking device Cap type QN
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Handle locking cover L1
Flat terminal SS *2*2*2*2*2*2
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan
*2 Standard provided
c
a d
b
Rated voltage (V) Operational voltage range (V)
100–230–440 80–484
07/12 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
G-TWIN Standard Series
Ampere frame 630A 800A
Type EW630EAG EW630RAG EW630HAG EW800EAG EW800RAG EW800HAG
Pole 3 3 3 3 3 3
Rated current Reference amb. temp. (40°C)
In(A) 500, 600, 630 700, 800
Rated impulse withstand voltage Uimp(kV) 6 6 6 6 6 6
Isolation compliant
Rated voltage Ue (AC V) 100-230-440
Type of earth leakage trip action AC type
Instantaneous/time-
delay trip type Rated sensitive current (mA) 100/300/500/1000 changeover
Tripping time (s) 0.1/0.4/1/2 changeover
Inertia non-tripping time (s) (2l n) 0/0.2/0.5/1
Rated breaking
capacity
Icu/Ics (kA)
IEC60947-2
EN60947-2
JISC8201-2-2
AC 440V 36/18 50/25 70/35 36/18 50/25 70/35
415V 36/18 50/25 70/35 36/18 50/25 70/35
400V 36/18 50/25 70/35 36/18 50/25 70/35
380V 36/18 50/25 70/35 36/18 50/25 70/35
230V 50/25 100/50 125/63 50/25 100/50 125/63
200V 50/25 100/50 125/63 50/25 100/50 125/63
100V 50/25 100/50 125/63 50/25 100/50 125/63
GB14048.2 AC 400V 36/18 50/25 70/35 36/18 50/25 70/35
230V 50/25 100/50 125/63 50/25 100/50 125/63
Conforming to
standards CE Marking (TÜV) (TÜV) (TÜV) (TÜV) (TÜV) (TÜV)
CCC certificate
Dimensions (mm) a 210 210 210 210 210 210
b 275 275 275 275 275 275
c 103 103 103 103 103 103
d 146 146 146 146 146 146
Mass (kg) 9.1 9.1 9.1 9.6 9.6 9.6
Tripping device Thermal-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Plug-in mounting P
Internal accessories Page 07/59
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Handle padlocking device Cap type QN
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Handle locking cover L1
Flat terminal SS *2*2*2*2*2*2
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan
*2 Standard provided
c
a d
b
Rated voltage (V) Operational voltage range (V)
100–230–440 80–484
07/13
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
Ampere frame 50A 100A
Type EW50RAGU EW100EAGU
Pole 3 2 3
Rated current Reference amb. temp. (40°C)
In(A) 3, 5, 10, 15, 20, 30, 32, 40, 50 60, 63, 70, 75, 80, 90, 100
Rated impulse withstand voltage Uimp(kV) 6 4 6
Isolation compliant
Rated voltage Ue (AC V) IEC 100-230-440 100-230 100-230-440
UL 240 240 240
Rated sensitive current (mA) 30, 50, 100/200/500 changeover 30, 100/200 changeover 30, 50, 100/200/500 changeover
Tripping time (s) 0.1 or less 0.1 or less 0.1 or less
Rated breaking
capacity IEC 60947-2
EN 60947-2
JIS C 8201-2-2
Icu/Ics (kA)
AC 440V 10/5 7.5/4 10/5
415V 10/5 7.5/4 10/5
400V 10/5 7.5/4 10/5
380V 10/5 7.5/4 10/5
230V 25/13 7.5/4 25/13
200V 25/13 7.5/4 25/13
100V 25/13 10/5 25/13
GB14048.2
Icu/Ics(kA) AC 400V 10/5 7.5/4 10/5
230V
25/13
10/5 25/13
UL489
CAN/CSA C22.2 NO.5
(kA)
AC
480V/
480V/Y
240V 14 14 14
Conforming to
standards CE Marking (TÜV) (TÜV) (TÜV)
CCC certificate
UL Listed (NEMA AB1)
Electrical Appliance and Material Safety Law *
1
Dimensions (inch(mm)) a 2.953 (75) 2.953 (75) 2.953 (75)
b 4.724 (120) 4.724 (120) 4.724 (120)
c 2.362 (60) 2.362 (60) 2.362 (60)
d 3.307 (84) 3.307 (84) 3.307 (84)
Mass (kg) 0.6 0.6 0.6
Tripping device Hydraulic-magnetic
Connecting terminal Page 07/26
Screw S
Flat
Block
Internal accessories Page 07/57
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S *2
Terminal cover Long BT L
Insulation barrier Interphase BP
: Approved : Available –: Not available
Note: *1 Electrical Appliance and Material Safety Law of Japan
*2 Standard provided
c
a d
b
G-TWIN Global Series
Rated voltage (V) Operational voltage range (V)
100–230 80–264
240 80–264
100–230–440 80-484
07/14 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
G-TWIN Global Series
Ampere frame 125A
Type EW125JAGU EW125RAGU
Pole 3 3
Rated current Reference amb. temp. (40°C)
In(A) 15, 20, 30, 40, 50, 60, 75, 100, 125
Rated impulse withstand voltage Uimp(kV) 6 6
Isolation compliant
Rated voltage Ue (AC V) IEC 100-230-440
UL 240-480
Type of earth leakage trip action AC type
Instantaneous trip
type Rated sensitive current (mA) 30
Tripping time (s) 0.1 or less
Instantaneous/time-
delay trip type Rated sensitive current (mA) 100/200/500/1000 changeover
Tripping time (s) 0.1/0.4/1/2 changeover
Inertia non-tripping time (s) (2l n) 0/0.2/0.5/1
Rated breaking
capacity IEC60947-2
EN60947-2
JISC8201-2-2
Icu/Ics (kA)
AC 440V 30/15 50/25
415V 30/15 50/25
400V 30/15 50/25
380V 30/15 50/25
230V 50/25 100/50
200V 50/25 100/50
100V 50/25 100/50
GB14048.2
Icu/Ics (kA) AC 400V 30/15 50/25
230V 50/25 100/50
UL489
CAN/CSA C22.2 NO.5
(kA)
AC
480V/
30 50
480V/Y
30 50
240V 50 100
Conforming to
standards CE Marking (TÜV) (TÜV)
CCC certificate
UL Listed (NEMA AB1)
Electrical Appliance and Material Safety Law *
1
(except for 125A) (except for 125A)
Dimensions (inch(mm)) a 3.543 (90) 3.543 (90)
b 6.732 (171) 6.732 (171)
c 2.677 (68) 2.677 (68)
d 3.740 (95) 3.740 (95)
Mass (kg) 1.3 1.3
Tripping device Thermal-magnetic
Connecting terminal Page 07/26
Screw S
Flat
Block
Internal accessories Page 07/58
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Operating handle N-type N
Operating handle V-type V
Operating handle F-type F
Terminal cover Short BT S *2 *2
Terminal cover Long BT L
Insulation barrier Interphase BP
: Approved : Available –: Not available
Note: *1 Electrical Appliance and Material Safety Law of Japan
*2 Standard provided
c
a d
b
Rated voltage (V) Operational voltage range (V)
240–480 80–504
100–230–440 80-484
07/15
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
G-TWIN Global Series
Ampere frame 250A
Type EW250JAGU EW250RAGU
Pole 3 3
Rated current Reference amb. temp. (40°C)
In(A) 125, 150, 160, 175, 200, 225, 250
Rated impulse withstand voltage Uimp(kV) 6 6
Isolation compliant
Rated voltage Ue (AC V) IEC 100-230-440
UL 240-480
Type of earth leakage trip action AC type
Instantaneous trip
type Rated sensitive current (mA) 30
Tripping time (s) 0.1 or less
Instantaneous/time-
delay trip type Rated sensitive current (mA) 100/200/500/1000 changeover
Tripping time (s) 0.1/0.4/1/2 changeover
Inertia non-tripping time (s) (2l n) 0/0.2/0.5/1
Rated breaking
capacity IEC60947-2
EN60947-2
JISC8201-2-2
Icu/Ics (kA)
AC 440V 30/15 50/25
415V 30/15 50/25
400V 30/15 50/25
380V 30/15 50/25
230V 50/25 100/50
200V 50/25 100/50
100V 50/25 100/50
GB14048.2
Icu/Ics (kA) AC 400V 30/15 50/25
230V 50/25 100/50
UL489
CAN/CSA C22.2 NO.5
(kA)
AC
480V/
30 50
480V/Y
30 50
240V 50 100
Conforming to
standards CE Marking (TÜV) (TÜV)
CCC certificate
UL Listed (NEMA AB1)
Dimensions (inch(mm)) a 4.134 (105) 4.134 (105)
b 7.126 (181) 7.126 (181)
c 2.677 (68) 2.677 (68)
d 3.740 (95) 3.740 (95)
Mass (kg) 1.8 1.8
Tripping device Thermal-magnetic
Connecting terminal Page 07/26
Screw S
Flat
Block
Internal accessories Page 07/58
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Operating handle N-type N
Operating handle V-type V
Operating handle F-type F
Terminal cover Short BT S *1 *1
Terminal cover Long BT L
Insulation barrier Interphase BP
: Approved : Available –: Not available
Note: *1 Standard provided
Rated voltage (V) Operational voltage range (V)
240–480 80–504
100–230–440 80-484
c
a d
b
07/16 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
G-TWIN Global Series
Ampere frame 400A
Type EW400SAGU EW400RAGU EW400HAGU
Pole 3 3 3
Rated current Reference amb. temp. (40°C)
In(A) 250, 300, 350, 400
Rated impulse withstand voltage Uimp(kV) 6 6 6
Isolation compliant
Rated voltage Ue (AC V) IEC 100-230-440
UL 240-480
Type of earth leakage trip action AC type
Instantaneous trip
type Rated sensitive current (mA) 30
Tripping time (s) 0.1 or less
Instantaneous/time-
delay trip type Rated sensitive current (mA) 100/200/500/1000 changeover
Tripping time (s) 0.1/0.4/1/2 changeover
Inertia non-tripping time (s) (2l n) 0/0.2/0.5/1
Rated breaking
capacity IEC60947-2
EN60947-2
JISC8201-2-2
Icu/Ics (kA)
AC 440V 36/18 50/25 70/35
415V 36/18 50/25 70/35
400V 36/18 50/25 70/35
380V 36/18 50/25 70/35
230V 85/43 100/50 125/63
200V 85/43 100/50 125/63
100V 85/43 100/50 125/63
GB14048.2
Icu/Ics (kA) AC 400V 36/18 50/25 70/35
230V 85/43 100/50 125/63
UL489
CAN/CSA C22.2 NO.5
(kA)
AC
480V/
35 50 65 (with block terminal: 50)
480V/Y
35 50 65 (with block terminal: 50)
240V 50 100 100
Conforming to
standards CE Marking (TÜV) (TÜV) (TÜV)
CCC certificate
UL Listed (NEMA AB1)
Dimensions (inch(mm)) a 5.512 (140) 5.512 (140) 5.512 (140)
b 10.12 (257) 10.12 (257) 10.12 (257)
c 4.055 (103) 4.055 (103) 4.055 (103)
d 5.748 (146) 5.748 (146) 5.748 (146)
Mass (kg) 6.3 6.3 6.3
Tripping device Thermal-magnetic
Connecting terminal Page 07/26
Screw S
Flat
Block
Internal accessories Page 07/58
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories Page 07/60
Operating handle N-type N
Operating handle V-type V
Operating handle F-type F
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
: Approved : Available –: Not available : Factory-mounted accessory
Rated voltage (V) Operational voltage range (V)
240–480 80–504
100–230–440 80-484
c
a d
b
07/17
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
G-TWIN Global Series
Ampere frame 630A
Type EW630RAGU
Pole 3
Rated current Reference amb. temp. (40°C)
In(A) 500, 600, 630*1
Rated impulse withstand voltage Uimp(kV) 6
Isolation compliant
Rated voltage Ue (AC V) IEC 100-230-440
UL 240-480
Instantaneous/time-
delay trip type Rated sensitive current (mA) 100/200/500/1000 changeover
Tripping time (s) 0.1/0.4/1/2 changeover
Inertia non-tripping time (s) (2l n) 0/0.2/0.5/1
Rated breaking
capacity IEC60947-2
EN60947-2
JISC8201-2-2
Icu/Ics (kA)
AC 440V 50/25
415V 50/25
400V 50/25
380V 50/25
230V 100/50
200V 100/50
100V 100/50
GB14048.2
Icu/Ics (kA) AC 400V 50/25
230V 100/50
UL489
CAN/CSA C22.2 NO.5
(kA)
AC
480V/
50
480V/Y
50
240V 100
Conforming to
standards CE Marking (TÜV)
CCC certificate
UL Listed (NEMA AB1)
Dimensions (inch(mm)) a 8.268 (210)
b 10.83 (275)
c 4.055 (103)
d 5.748 (146)
Mass (kg) 10.2
Tripping device Thermal-magnetic
Connecting terminal Page 07/27
Screw S
Flat
Block
Internal accessories Page 07/59
Alarm switch K *2
Auxiliary switch W *2
Undervoltage trip R *2
Shunt trip F *2
Earth alarm switch L
External accessories Page 07/60
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Breakers for 630A cannot be manufactured with block terminals.
*2 Block terminals are not available.
c
a d
b
Rated voltage (V) Operational voltage range (V)
240–480 80–504
100–230–440 80-484
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/18
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
n G-TWIN Standard Series / Motor protection
Ampere frame 32A
Type EW32EAM EW32SAM
Pole 3 3
Rated current Reference amb. temp. (40°C)
In(A) 1.4, 2.6, 4, 5, 8, 10, 16, 24, 32 0.7, 1.4, 2, 2.6, 4, 5, 8, 10, 12, 16, 24, 32
Rated impulse withstand voltage Uimp(kV) 4 4
Isolation compliant
Rated voltage Ue(AC V) 100-230-440 100-230-440
Rated sensitive current (mA) 30, 100 30, 100/200/500 changeover
Tripping time (s) 0.1 or less 0.1 or less
Rated breaking
capacity
Icu/Ics (kA)
IEC 60947-2
EN 60947-2
JIS C 8201-2-2
AC 440V 1.5/1 2.5/2
415V 1.5/1 2.5/2
400V 1.5/1 2.5/2
380V 1.5/1 2.5/2
230V 2.5/2 5/3
200V 2.5/2 5/3
100V 5/3 5/3
GB14048.2 AC 400V 1.5/1 2.5/2
230V 2.5/2 5/3
Conforming to
standards CE Marking
CCC certificate
Electrical Appliance and Material Safety Law*
1
Dimensions (mm)
c
a d
b
a 75 75
b 100 100
c 60 60
d 84 84
Mass (kg) 0.5 0.5
Tripping device Hydraulic-magnetic Hydraulic-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Flush mounting, top & buttom connection Y
Plug-in mounting P
IEC 35mm wide rail mounting No-mark
Internal accessories
Page 07/57
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories
Page 07/60
Handle padlocking device Cap type QN
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Insulation barrier Earth BL
Handle locking cover L1
Flat terminal SS
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan Rated voltage (V) Operational voltage range (V)
100–230–440 80–484
07/19
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
Ampere frame 50A
Type EW50EAM EW50SAM
Pole 3 3
Rated current Reference amb. temp. (40°C)
In(A) 45 0.7, 1.4, 2, 2.6, 4, 5, 8, 10, 12, 16, 24, 32, 40, 45
Rated impulse withstand voltage Uimp(kV) 4 6
Isolation compliant
Rated voltage Ue (AC V) 100-230-440 100-230-440
Rated sensitive current (mA) 30, 100/200 changeover 30, 100/200/500 changeover
Tripping time (s) 0.1 or less 0.1 or less
Rated breaking
capacity
Icu/Ics (kA)
IEC 60947-2
EN 60947-2
JIS C 8201-2-2
AC 440V 2.5/2 7.5/4
415V 2.5/2 7.5/4
400V 2.5/2 7.5/4
380V 2.5/2 7.5/4
230V 5/3 10/5
200V 5/3 10/5
100V 5/3 10/5
GB14048.2 AC 400V 2.5/2 7.5/4
230V 5/3 10/5
Conforming to
standards CE Marking
CCC certificate
Electrical Appliance and Material Safety Law*
1
Dimensions (mm)
c
a d
b
a 75 75
b 100 100
c 60 60
d 84 84
Mass (kg) 0.6 0.6
Tripping device Hydraulic-magnetic Hydraulic-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Flush mounting, top & buttom connection Y
Plug-in mounting P
IEC 35mm wide rail mounting No-mark
Internal accessories
Page 07/57
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories
Page 07/60
Handle padlocking device Cap type QN
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Insulation barrier Earth BL
Handle locking cover L1
Flat terminal SS
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan
n G-TWIN Standard Series / Motor protection
Rated voltage (V) Operational voltage range (V)
100–230–440 80–484
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/20
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
n G-TWIN Standard Series / Motor protection
Ampere frame 63A 100A
Type EW63EAM EW63SAM EW100EAM
Pole 3 3 3
Rated current Reference amb. temp. (40°C)
In(A) 63 63 63, 75, 90
Rated impulse withstand voltage Uimp(kV) 6 6 6
Isolation compliant
Rated voltage Ue (AC V) 100-230-440 100-230-440 100-230-440
Rated sensitive current (mA) 30, 100/200 changeover 30, 100/200/500 changeover 30, 100/200/500 changeover
Tripping time (s) 0.1 or less 0.1 or less 0.1 or less
Rated breaking
capacity
Icu/Ics (kA)
IEC 60947-2
EN 60947-2
JIS C 8201-2-2
AC 440V 2.5/2 7.5/4 10/5
415V 2.5/2 7.5/4 10/5
400V 2.5/2 7.5/4 10/5
380V 2.5/2 7.5/4 10/5
230V 5/3 10/5 25/13
200V 5/3 10/5 25/13
100V 5/3 10/5 25/13
GB14048.2 AC 400V 2.5/2 7.5/4 10/5
230V 5/3 10/5 25/13
Conforming to
standards CE Marking
CCC certificate
Electrical Appliance and Material Safety Law*
1
Dimensions (mm)
c
a d
b
a 75 75 75
b 100 100 100
c 60 60 60
d 84 84 84
Mass (kg) 0.6 0.6 0.6
Tripping device Hydraulic-magnetic Hydraulic-magnetic Hydraulic-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Flush mounting, top & buttom connection Y
Plug-in mounting P
IEC 35mm wide rail mounting No-mark
Internal accessories
Page 07/57
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories
Page 07/60
Handle padlocking device Cap type QN
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Insulation barrier Earth BL
Handle locking cover L1
Flat terminal SS
Block terminal SL
: Approved : Available –: Not available : Factory-mounted accessory
Note: *1 Electrical Appliance and Material Safety Law of Japan Rated voltage (V) Operational voltage range (V)
100–230–440 80–484
07/21
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
Earth Leakage Circuit Breakers
G-TWIN series
Quick reference guide
n G-TWIN Standard Series / Motor protection
Ampere frame 125A 250A
Type EW125JAM EW125RAM EW250EAM EW250JAM EW250RAM
Pole 3 3 3 3 3
Rated current Reference amb. temp. (40°C)
In(A) 16, 24, 32, 40, 45, 60, 75, 90 125, 150, 175, 225
Rated impulse withstand voltage Uimp(kV) 6 6 6 6 6
Isolation compliant
Rated voltage Ue (AC V) 100-230-440 100-230-440 100-230-440 100-230-440 100-230-440
Type of earth leakage trip action AC type AC type
Instantaneous trip
type Rated sensitive current (mA) 30 30
Tripping time (s) 0.1 or less 0.1 or less
Instantaneous/
time-delay trip
type
Rated sensitive current (mA) 100/200/500/1000 changeover 100/200/500/1000 changeover
Tripping time (s) 0.1/0.4/1/2 changeover 0.1/0.4/1/2 changeover
Inertia non-tripping time (s) (2l n) 0/0.2/0.5/1 0/0.2/0.5/1
Rated breaking
capacity
Icu/Ics (kA)
IEC 60947-2
EN 60947-2
JIS C 8201-2-2
AC 440V 30/15 50/25 18/9 30/15 50/25
415V 30/15 50/25 18/9 30/15 50/25
400V 30/15 50/25 18/9 30/15 50/25
380V 30/15 50/25 18/9 30/15 50/25
230V 50/25 100/50 36/18 50/25 100/50
200V 50/25 100/50 36/18 50/25 100/50
100V 50/25 100/50 36/18 50/25 100/50
GB14048.2 AC 400V 30/15 50/25 18/9 30/15 50/25
230V 50/25 100/50 36/18 50/25 100/50
Conforming to
standards CE Marking
CCC certificate
Electrical Appliance and Material Safety Law*
1
–––
Dimensions (mm)
c
a d
b
a 90 90 105 105 105
b 155 155 165 165 165
c 68 68 68 68 68
d 95 95 95 95 95
Mass (kg) 1.3 1.3 1.8 1.8 1.8
Tripping device Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic
Front mounting, front connection No-mark
Front mounting, rear connection X
Flush mounting, front connection E
Flush mounting, top & buttom connection Y
Plug-in mounting P
Internal accessories
Page 07/58
Alarm switch K
Auxiliary switch W
Undervoltage trip R
Shunt trip F
Earth alarm switch L
External accessories
Page 07/60
Handle padlocking device Cap type Q1
Handle padlocking device Plate type Q2
Operating handle N-type N
Operating handle V-type V
Terminal cover Short BT S
Terminal cover Long BT L
Insulation barrier Interphase BP
Insulation barrier Earth BL
Handle locking cover L1
Flat terminal SS
Block terminal SL
: Approved : Available –: Not available
Note: *1 Electrical Appliance and Material Safety Law of Japan Rated voltage (V) Operational voltage range (V)
100–230–440 80–484
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/22
Earth Leakage Circuit Breakers
G-TWIN series
Mounting modifications
n Mounting modifications
• Standard series
Standard type FUJI breakers are front
mounting with front connections. The
standard breaker can easily be modified to
become front mounting rear connection type,
flush mounting type and plug-in type. The
additional parts such as insulation bases,
barriers, covers and similar parts are added
as required.
Front mounting
Front connection
Additional
main parts
Bar stud
terminal
Additional
main parts
Bar stud
terminal
Front mounting
Rear connection (X type) Flush mounting
Rear connection (E type) Additional
main parts Plug-in mounting
(P type)
Additional
main parts Flush mounting
Top and bottom
connection (Y type)
EW32
EW50
EW63
EW100
EW32
EW50
EW63
EW100
Round stud
terminal
EW32
EW50
EW63
EW100
EW125
Each stud can be
turned by 90° Each stud can be
turned by 90°
Each stud can be
turned by 90°
Bar stud
terminal Bar stud
terminal
EW125
EW160
EW250
EW400
EW630
EW800
EW125
EW160
EW250
EW400
EW630
EW800
Bar stud
terminal
Bar stud
terminal
EW32
EW50
EW63
EW100
EW160
EW250
EW400
EW630
EW800
Decorative
flush plate
BASIC DESIGN
07/23
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
• Global series
Screw Flat terminal Block terminal
BASIC DESIGN
Front mounting
Front connection
Earth Leakage Circuit Breakers
G-TWIN series
Mounting modifications
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/24
Earth Leakage Circuit Breakers
G-TWIN series
Terminal connection
n Terminal connection/Front mounting, front connection
Front
Front
Flat terminal
Breaker type Size (mm)
M12 35
M12 40
M8 16
M8 16
Hexagonal head bolt
EW400
EW630
EW800
Tightening
torque (N•m)
Tightening
torque (N•m)
40 to 50
40 to 50
Type of connection/up to 250AF
Front mounting front connection
Direct connection
Flat terminal connection
Flat terminals are required.
Pan-head screw
Hexagonal socket
head bolt
Breaker type
Flat bar studs/1-hole type
EW125
EW160
EW250
Tightening
torque (N•m)
5.5 to 7.5
8.0 to 13.0
Size (mm) Flat terminal
Breaker type Pole Type of flat terminal
EW125
EW160
EW250
3
4
3
4
BW9SS0CA-3
BW9SS0CA-4
BW9SS0GA-3
BW9SS0GA-4
EW32
EW50
EW63
EW100*
2
3
2
3
BZ6S10C502
BZ6S10C503
BZ6S10C1002
BZ6S10C1003
Front
Flat terminal
Self lifting screw
Pan-head screw
Breaker type
EW32
EW50
EW100*
2.3 to 2.8
Size
M5 14
M8 15
EW63
EW100 5.5 to 7.5
* EW100 breaker of rated current 50A: BZ6S10C502 or 503.
* Breaker of rated current : 50A
• 32AF to 100AF • 400AF to 800AF
• 125AF to 250AF
07/25
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
Earth Leakage Circuit Breakers
G-TWIN series
Wire size and terminal
n Breaker termination
n Wire size and crimp terminal
The following is the size recommendations for crimp terminals. Crimp terminal R : JIS C2805
CB : JEM-1399
JST : Product of Japan Crimp Terminal Co., Ltd.
Ampere
frame Breaker Wire size(mm2)
1.04
|
2.63
2.63
|
6.64
6.64
|
10.52
10.52
|
16.78
16.78
|
26.66
26.66
|
42.42
42.42
|
60.57
96.3
|
117.2
117.2
|
152.05
192.6
|
242.27
242.27
|
325
32 EW32 R2-5 R5.5-5 R8-5 R14-5
50 EW50 R2-5 R5.5-5 R8-5 R14-5
63 EW63 R2-8 R5.5-8 R8-8 R14-8 JST22-S8
100 EW100 R2-8 R5.5-8 R8-8 R14-8 JST22-S8 JST38-S8
125 EW125 R2-8 R5.5-8 R8-8 R14-8 R22-8 JST38-S8 CB60-8
160
250 EW160
EW250 R22-8 R38-8 R60-8 CB100-8
400 EW400 R38-12 R60-12 R100-12 R150-12 R200-12
JST325-12
630 EW630 R100-12 R150-12 R200-12
JST325-12
800 EW800 R100-12 R150-12 R200-12
JST325-12
• Standard
EW32
EW50
EW63
EW100
Self-lifiting
terminal
ELCB type Front connection
EW125
EW160
EW250
EW400
EW630
EW800
Rear connection
X Flush mounting
E
Y Plug-in mounting
P
Flat terminal
Flat terminal
Flat terminal 9 rotational stud 9 rotational stud 9 rotational stud
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/26
Terminal position Applicable breaker type
Code
Blank
Blank
SB
SF
S3
S4
S5
S6
S7
S8
Line
Screw
Flat teminal
Block terminal
Flat teminal
Screw
Flat teminal
Screw
Block terminal
Flat teminal
Block terminal
Load
Screw
Flat teminal
Block terminal
Flat teminal
Flat terminal
Screw
Block terminal
Screw
Block terminal
Flat terminal
EW125, 250
EW50, 100
EW400, 630, 800
Earth Leakage Circuit Breakers
G-TWIN series
Wire size and terminal
n Notes on wiring (global series)
Notes on connecting wires (conductors)
• Connect wires to the UL breaker according to NEC (National
Electric Code) or CEC (Canadian Electrical Code) Part 1.
• Use 75°C copper wires for wiring. UL-certied or CSA-
certified wires are recommended.
• If a large current (for example, a short-circuit current)
flows, it causes a huge electromagnetic force between wires.
Therefore, be sure to secure the wires sufficiently.
• Re-tighten terminal screws periodically.
Block terminal connection
• Choose from the stranded wires shown in Table.
Wire size: AWG or MCM [mm2] No. of wires stranded
14 to 2 [2.1 to 33.6] 7
1 to 4/0 [42.4 to 107.2] 19
250 to 500 [127 to 250] 37
Values in [ ] are those converted from AWG or MCM sizes to mm2.
* See the instruction manual that comes with the breaker for
more details.
Precautions
Two wires of different sizes cannot be connected to the
same block terminal.
• Be sure to use stranded wires according to Table "Number
of wires stranded."
• Multi-conductor wires cannot be connected.
• Do not solder wires together.
Wire size and crimp terminal
• Crimp terminal connection
ELCB Rated
current
(A)
Applicable crimp terminal
75˚C wire Connectable wire
size (AWG) Tightening
torque
(N•m)
Type of
screw head
and size
(mm)
J.S.T Mfg. Co., Ltd. Nichifu Co., Ltd. Daido Solderless Terminal
Mfg. Co., Ltd. 75˚C wire
EW50RAGU 3 R2-5 R2-5M
R2-5 2-S5, 2-5 14AWG 2.3-2.8 Cross/straight slotted
pan-head screw
M5 x 14
5
10
15
20 R5.5-5 R3.5-5S, R3.5-5L, 5.5-6N,
R5.5-5S, R5.5-5 3.5-5, 5.5-S5,
5.5-5, 5.5-L5 12AWG
30 10AWG
40 R8-5 R8-5S, R8-5 8-S5, 8-5 8AWG
50
EW100EAGU 60 R14-8 R14-8S, R14-8 R14-S8, R14-8 6AWG 5.5-7.5 Cross/straight slotted
pan-head screw
M8 x 15
75 22-S8 R22-8S, R22-8 R22-S8, 22-8 4AWG
100 38-S8 R38-8S 38-S8 3AWG
EW125JAGU
EW125RAGU 15 R2-8 R2-8 2-8, 2-B8 14AWG 5.8
(5.3-6.4) Cross/straight slotted
pan-head screw
M8 x 16
20 5.5-S8, R5.5-8 R3.5-8, R5.5-8 3.5-8, 5.5-8 12AWG
30 R5.5-8 5.5-8 10AWG
40 8-8NS, R8-8 R8-8 8-8 8AWG
50
60 14-8NS, 14-S8, R14-8 R14-8S, R14-8 14-S8, 14-8 6AWG
70 22-S8, R22-8, CB22-S8 R22-8S, R22-8, CB22-8S 22-S8, 22-8, CB22-8 4AWG
75
80
90 38-S8 R38-8S 38-S8 3AWG
100
125 1AWG
EW250JAGU
EW250RAGU 125 38-S8, R38-8 R38-8S, R38-8 38-S8, 38-8 1AWG 10.5
(8-13) Hexagon socket
head bolt
M8 x 16
150 60-S8, R60-8 R60-8, CB60-8, CB60-8S 60-8, CB60-8 1/0AWG
175 70-8 R70-8 70-8 2/0AWG
200 CB80-S8 CB80-8 3/0AWG
225 CB100-S8 CB100-8 4/0AWG
250 CB150-S8 CB150-8 CB150-8 250MCM
Notes: • AWG/MCM is the UL approved wire unit.
The allowable temperature of wire is 75˚C. (UL CSA approved)
• Be sure to use UL-certied or CSA-certied crimp tools commercially available.
07/27
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
Earth Leakage Circuit Breakers
G-TWIN series
Wire size and terminal
• Flat terminal connection
ELCB Rated
current
(A)
Applicable crimp terminal
75˚C wire Connectable
wire size (AWG) Tightening torque
(N•m) Type of
screw head
and size
(mm)
J.S.T Mfg. Co., Ltd. Nichifu Co., Ltd. Daido Solderless
Terminal Mfg. Co., Ltd. 75˚C wire Wire
side MCCB
side
EW50RAGU 3 R2-5 R2-5M
R2-5 2-S5, 2-5 14AWG 3.5 to 4.5 2.3 to 2.8 Hexagon socket
head bolt
M5 x 16
5
10
15
20 R5.5-5 R3.5-5S, R3.5-5L, 5.5-6N.
R5.5-5S, R5.5-5 3.5-5, 5.5-S5
5.5-5, 5.5-L5 12AWG
30 10AWG
40 R8-5 R8-5S, R8-5 8-S5, 8-5 8AWG
50
EW100EAGU 60 R14-8 R14-8S, R14-8 R14-S8, R14-8 6AWG 8 to 10 5.5 to 7.5 Hexagon socket
head bolt
M8 x 22
75 22-S8 R22-8S, R22-8 R22-S8, 22-8 4AWG
100 38-S8 R38-8S 38-S8 3AWG
EW125JAGU
EW125RAGU 15 R2-8 R2-8 2-8, 2-B8 14AWG 9
(8 to 10) 5.8
(5.3 to 6.4) Cross/straight
slotted pan-head
screw
M8 x 16
20 5.5-S8, R5.5-8 R3.5-8, R5.5-8 3.5-8, 5.5-8 12AWG
30 R5.5-8 5.5-8 10AWG
40 8-8NS, R8-8 R8-8 8-8 8AWG
50
60 14-8NS, 14-S8, R14-8 R14-8S, R14-8 14-S8, 14-8 6AWG
75 22-S8, R22-8, CB22-S8 R22-8S, R22-8, CB22-8S 22-S8, 22-8, CB22-8 4AWG
100 38-S8 R38-8S 38-S8 3AWG
125 1AWG
EW250JAGU
EW250RAGU 125 38-S8, R38-8 R38-8S, R38-8 38-S8, 38-8 1AWG 9
(8 to 10) 10.5
(8 to 13) Hexagon socket
head bolt
M8 x 16
150 60-S8, R60-8 R60-8, CB60-8, CB60-8S 60-8, CB60-8 1/0AWG
175 70-8 R70-8 70-8 2/0AWG
200 CB80-S8 CB80-8 3/0AWG
225 CB100-S8 CB100-8 4/0AWG
250 CB150-S8 CB150-8 CB150-8 250MCM
EW400SAGU
EW400RAGU
EW400HAGU
250 150-12 R150-12 250MCM 45
(40 to 50) 43.5
(39.2 to 48) Hexagon head
bolt
M12 x 35
300 180-12 R180-12 350MCM
350 325-12 R325-12N 500MCM
400 325-12 R325-12N 500MCM
R80-12 R80-12 3/0AWG(x2)
EW630RAGU 500 R150-12 R150-12 250MCM(x2) 47.04
(42.4 to 51.7)
47.04
(42.4 to 51.7)
Hexagon head
bolt
M12 x 40
600 180-12 R180-12 350MCM(x2)
630 325-12 R325-12N R325-12 500MCM(x2)
Notes: • AWG/MCM is the UL approved wire unit.
The allowable temperature of wire is 75˚C. (UL CSA approved)
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/28
Earth Leakage Circuit Breakers
G-TWIN series
Wire size and terminal
• Block terminal connection
ELCB Rated current (A) Connectable wire size (AWG) Tightening torque (N•m) Type of screw head
and size (mm) Figure
EW125JAGU
EW125RAGU 15 14AWG 5.8
(5.8 to 6.4) Slotted set screw
20 12AWG
30 10AWG
40 8AWG
50
60 6AWG
75 4AWG
100 3AWG
125 1AWG
EW250JAGU
EW250RAGU 125 1AWG 23
(23 to 25.3) Hexagon socket head
setscrew: 8 mm (5/16 inch)
Screw head size
150 1/0AWG
175 2/0AWG
200 3/0AWG
225 4/0AWG
250 250MCM
EW400SAGU
EW400RAGU
EW400HAGU
250 250MCM 43.5
(43.5 to 48) Hexagon socket head
setscrew: 9.53 mm (3/8 inch)
300 350MCM
350 500MCM
400 3/0AWG(x2) 31.9
(31.9 to 35.1) Hexagon socket head
setscrew: 8 mm (5/16 inch)
EW630RAGU 500 250MCM(x2) 31.1
(31.1 to 34.2) Hexagon socket head
setscrew: 8 mm (5/16 inch)
600 350MCM(x2)
Notes: • AWG/MCM is the UL approved wire unit.
The allowable temperature of wire is 75˚C. (UL CSA approved)
07/29
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
l AAG series, 2-pole IEC/EN/GB/JIS conformed
l EAG series, 2-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current
: Available
mounting and
connection
32 5 EW32AAG-2P005 A, B, C Blank, X, E, Y, P
10 EW32AAG-2P010
15 EW32AAG-2P015
20 EW32AAG-2P020
30 EW32AAG-2P030
32 EW32AAG-2P032
50 5 EW50AAG-2P005 A, B, C Blank, X, E, Y, P
10 EW50AAG-2P010
15 EW50AAG-2P015
20 EW50AAG-2P020
30 EW50AAG-2P030
32 EW50AAG-2P032
40 EW50AAG-2P040
50 EW50AAG-2P050
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current
: Available
mounting and
connection
100 50 EW100EAG-2P050 B, K Blank, X, E, Y, P
60 EW100EAG-2P060
63 EW100EAG-2P063
75 EW100EAG-2P075
100 EW100EAG-2P100
Mounting Connection
Front
Front
Flush
Front
Rear
Rear
Blank
X
E
Flush Top and buttom Y
Plug-in P
n Type number, Standard series (Line protection)
Type number/Line protection
l AAG series, 3-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current
: Available
mounting and
connection
32 5 EW32AAG-3P005 A, B, C Blank, X, E, Y, P
10 EW32AAG-3P010
15 EW32AAG-3P015
20 EW32AAG-3P020
30 EW32AAG-3P030
32 EW32AAG-3P032
50 5 EW50AAG-3P005 A, B, C Blank, X, E, Y, P
10 EW50AAG-3P010
15 EW50AAG-3P015
20 EW50AAG-3P020
30 EW50AAG-3P030
32 EW50AAG-3P032
40 EW50AAG-3P040
50 EW50AAG-3P050
100 60 EW100AAG-3P060 B, K Blank, X, E, Y, P
63 EW100AAG-3P063
75 EW100AAG-3P075
100 EW100AAG-3P100
l JAG series, 3-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current
: Available
mounting and
connection
125 15 EW125JAG-3P015 B, J Blank, X, E, P
20 EW125JAG-3P020
30 EW125JAG-3P030
40 EW125JAG-3P040
50 EW125JAG-3P050
60 EW125JAG-3P060
75 EW125JAG-3P075
100 EW125JAG-3P100
125 EW125JAG-3P125
160 125 EW160JAG-3P125 B, J Blank, X, E, P
150 EW160JAG-3P150
160 EW160JAG-3P160
250 175 EW250JAG-3P175 B, J Blank, X, E, P
200 EW250JAG-3P200
225 EW250JAG-3P225
250 EW250JAG-3P250
Rated sensitive current
15mA
30mA
100mA
A
B
C
50mA D
100/300/500/1000mA changeover J
100/200mA, 100/200/500mA changeover
K
100/200/500/1000mA changeover K
07/30 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
l EAG series, 3-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection *
32 5 EW32EAG-3P005 A, B, C Blank, X, E, Y, P
10 EW32EAG-3P010
15 EW32EAG-3P015
20 EW32EAG-3P020
30 EW32EAG-3P030
32 EW32EAG-3P032
50 5 EW50EAG-3P005 A, B, K Blank, X, E, Y, P
10 EW50EAG-3P010
15 EW50EAG-3P015
20 EW50EAG-3P020
30 EW50EAG-3P030
32 EW50EAG-3P032
40 EW50EAG-3P040
50 EW50EAG-3P050
63 60 EW63EAG-3P060 A, B, K Blank, X, E, Y, P
63 EW63EAG-3P063
100 50 EW100EAG-3P050 B, K Blank, X, E, Y, P
60 EW100EAG-3P060
63 EW100EAG-3P063
75 EW100EAG-3P075
100 EW100EAG-3P100
160 125 EW160EAG-3P125 B, J Blank, X, E, P
150 EW160EAG-3P150
160 EW160EAG-3P160
250 175 EW250EAG-3P175 B, J Blank, X, E, P
200 EW250EAG-3P200
225 EW250EAG-3P225
250 EW250EAG-3P250
400 250 EW400EAG-3P250 B, J Blank, X, E, P
300 EW400EAG-3P300
350 EW400EAG-3P350
400 EW400EAG-3P400
630 500 EW630EAG-3P500 J Blank, X, E, P
600 EW630EAG-3P600
630 EW630EAG-3P630
800 700 EW800EAG-3P700 J Blank, X, E, P
800 EW800EAG-3P800
* See page 07/29.
Type number/Line protection
l SAG series, 3-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection *
32 3 EW32SAG-3P003 B, K Blank, X, E, Y, P
5 EW32SAG-3P005
10 EW32SAG-3P010
15 EW32SAG-3P015
20 EW32SAG-3P020
30 EW32SAG-3P030
32 EW32SAG-3P032
50 5 EW50SAG-3P005 B, K Blank, X, E, Y, P
10 EW50SAG-3P010
15 EW50SAG-3P015
20 EW50SAG-3P020
30 EW50SAG-3P030
32 EW50SAG-3P032
40 EW50SAG-3P040
50 EW50SAG-3P050
63 60 EW63SAG-3P060 B, K Blank, X, E, Y, P
63 EW63SAG-3P063
125 15 EW125SAG-3P015 B, J Blank, X, E, P
20 EW125SAG-3P020
30 EW125SAG-3P030
40 EW125SAG-3P040
50 EW125SAG-3P050
60 EW125SAG-3P060
75 EW125SAG-3P075
100 EW125SAG-3P100
125 EW125SAG-3P125
160 125 EW160SAG-3P125 B, J Blank, X, E, P
150 EW160SAG-3P150
160 EW160SAG-3P160
250 175 EW250SAG-3P175 B, J Blank, X, E, P
200 EW250SAG-3P200
225 EW250SAG-3P225
250 EW250SAG-3P250
400 250 EW400SAG-3P250 B, J Blank, X, E, P
300 EW400SAG-3P300
350 EW400SAG-3P350
400 EW400SAG-3P400
07/31
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
l HAG series, 3-pole IEC/EN/GB/JIS conformed
l RAG series, 3-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection *
50 10 EW50RAG-3P010 B, K Blank, X, E, Y, P
15 EW50RAG-3P015
20 EW50RAG-3P020
30 EW50RAG-3P030
32 EW50RAG-3P032
40 EW50RAG-3P040
50 EW50RAG-3P050
63 60 EW63RAG-3P060 B, K Blank, X, E, Y, P
63 EW63RAG-3P063
125 15 EW125RAG-3P015 B, J Blank, X, E, P
20 EW125RAG-3P020
30 EW125RAG-3P030
40 EW125RAG-3P040
50 EW125RAG-3P050
60 EW125RAG-3P060
75 EW125RAG-3P075
100 EW125RAG-3P100
125 EW125RAG-3P125
160 125 EW160RAG-3P125 B, J Blank, X, E, P
150 EW160RAG-3P150
160 EW160RAG-3P160
250 175 EW250RAG-3P175 B, J Blank, X, E, P
200 EW250RAG-3P200
225 EW250RAG-3P225
250 EW250RAG-3P250
400 250 EW400RAG-3P250 B, J Blank, X, E, P
300 EW400RAG-3P300
350 EW400RAG-3P350
400 EW400RAG-3P400
630 500 EW630RAG-3P500 J Blank, X, E, P
600 EW630RAG-3P600
630 EW630RAG-3P630
800 700 EW800RAG-3P700 J Blank, X, E, P
800 EW800RAG-3P800
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection *
400 250 EW400HAG-3P250 B, J Blank, X, E, P
300 EW400HAG-3P300
350 EW400HAG-3P350
400 EW400HAG-3P400
630 500 EW630HAG-3P500 J Blank, X, E, P
600 EW630HAG-3P600
630 EW630HAG-3P630
800 700 EW800HAG-3P700 J Blank, X, E, P
800 EW800HAG-3P800
* See page 07/29.
Type number/Line protection
l JAG series, 4-pole IEC/EN/GB/JIS conformed
l SAG series, 4-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection *
125 15 EW125JAG-4P015 B, J Blank, X, E
20 EW125JAG-4P020
30 EW125JAG-4P030
40 EW125JAG-4P040
50 EW125JAG-4P050
60 EW125JAG-4P060
75 EW125JAG-4P075
100 EW125JAG-4P100
125 EW125JAG-4P125
160 125 EW160JAG-4P125 B, J Blank, X, E
150 EW160JAG-4P150
160 EW160JAG-4P160
250 175 EW250JAG-4P175 B, J Blank, X, E
200 EW250JAG-4P200
225 EW250JAG-4P225
250 EW250JAG-4P250
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection *
125 15 EW125SAG-4P015 B, J Blank, X, E
20 EW125SAG-4P020
30 EW125SAG-4P030
40 EW125SAG-4P040
50 EW125SAG-4P050
60 EW125SAG-4P060
75 EW125SAG-4P075
100 EW125SAG-4P100
125 EW125SAG-4P125
160 125 EW160SAG-4P125 B, J Blank, X, E
150 EW160SAG-4P150
160 EW160SAG-4P160
250 175 EW250SAG-4P175 B, J Blank, X, E
200 EW250SAG-4P200
225 EW250SAG-4P225
07/32 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
l HAG series, 4-pole IEC/EN/GB/JIS conformed
l RAG series, 4-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection *
125 15 EW125RAG-4P015 B, J Blank, X, E
20 EW125RAG-4P020
30 EW125RAG-4P030
40 EW125RAG-4P040
50 EW125RAG-4P050
60 EW125RAG-4P060
75 EW125RAG-4P075
100 EW125RAG-4P100
125 EW125RAG-4P125
160 125 EW160RAG-4P125 B, J Blank, X, E
150 EW160RAG-4P150
160 EW160RAG-4P160
250 175 EW250RAG-4P175 B, J Blank, X, E
200 EW250RAG-4P200
225 EW250RAG-4P225
400 250 EW400RAG-4P250 B, J Blank, X, E
300 EW400RAG-4P300
350 EW400RAG-4P350
400 EW400RAG-4P400
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection*
400 250 EW400HAG-4P250 B, J Blank, X, E
300 EW400HAG-4P300
350 EW400HAG-4P350
400 EW400HAG-4P400
* See page 07/29.
Type number/Line protection
07/33
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Type number/Line protection
l EAGU series, 2-pole UL489 Listed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection
100 60 EW100EAGU-2P060
B, K Blank, SF, S3, S4
63 EW100EAGU-2P063
70 EW100EAGU-2P070
75 EW100EAGU-2P075
80 EW100EAGU-2P080
90 EW100EAGU-2P090
100 EW100EAGU-2P100
: Terminal position Breaker type
Code Line Load
EW50, 100 EW125,250 EW400,630
Blank
Blank
SB
Screw
Flat terminal
Block terminal
Screw
Flat terminal
Block terminal
l
l
l
l
l
SF
S3
S4
S5
S6
S7
S8
Flat terminal
Screw
Flat terminal
Screw
Block terminal
Flat terminal
Block terminal
Flat terminal
Flat terminal
Screw
Block terminal
Screw
Block terminal
Flat terminal
l
l
l
l
l
l
l
l
l
l
l
l
n Type number, Global series (Line protection)
Terminal combination
l EAGU series, 3-pole UL489 Listed
l JAGU series, 3-pole UL489 Listed
l SAGU series, 3-pole UL489 Listed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection
100 60 EW100EAGU-3P060
B,D, K Blank, SF, S3, S4
63 EW100EAGU-3P063
70 EW100EAGU-3P070
75 EW100EAGU-3P075
80 EW100EAGU-3P080
90 EW100EAGU-3P090
100 EW100EAGU-3P100
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection
125 15 EW125JAGU-3P015
B, K Blank, SB, SF, S3
20 EW125JAGU-3P020
S4, S5, S6, S7, S8
30 EW125JAGU-3P030
40 EW125JAGU-3P040
50 EW125JAGU-3P050
60 EW125JAGU-3P060
75 EW125JAGU-3P075
100 EW125JAGU-3P100
125 EW125JAGU-3P125
250 125 EW250JAGU-3P125
B, K Blank, SB, SF, S3
150 EW250JAGU-3P150
S4, S5, S6, S7, S8
160 EW250JAGU-3P160
175 EW250JAGU-3P175
200 EW250JAGU-3P200
225 EW250JAGU-3P225
250 EW250JAGU-3P250
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection
400 250 EW400SAGU-3P250 B, K
Blank, SB, S7, S8
300 EW400SAGU-3P300
350 EW400SAGU-3P350
400 EW400SAGU-3P400
* See page 07/29.
l RAGU series, 3-pole UL489 Listed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection
50 3 EW50RAGU-3P003
B, D, K Blank, SF, S3, S4
5 EW50RAGU-3P005
10 EW50RAGU-3P010
15 EW50RAGU-3P015
20 EW50RAGU-3P020
30 EW50RAGU-3P030
32 EW50RAGU-3P032
40 EW50RAGU-3P040
50 EW50RAGU-3P050
125 15 EW125RAGU-3P015
B, K Blank, SB, SF, S3
20 EW125RAGU-3P020
S4, S5, S6, S7, S8
30 EW125RAGU-3P030
40 EW125RAGU-3P040
50 EW125RAGU-3P050
60 EW125RAGU-3P060
75 EW125RAGU-3P075
100 EW125RAGU-3P100
125 EW125RAGU-3P125
250 125 EW250RAGU-3P125
B, K Blank, SB, SF, S3
150 EW250RAGU-3P150
S4, S5, S6, S7, S8
160 EW250RAGU-3P160
175 EW250RAGU-3P175
200 EW250RAGU-3P200
225 EW250RAGU-3P225
250 EW250RAGU-3P250
400 250 EW400RAGU-3P250 B, K
Blank, SB, S7, S8
300 EW400RAGU-3P300
350 EW400RAGU-3P350
400 EW400RAGU-3P400
630 500 EW630RAGU-3P500 K
Blank, SB, S7, S8
600 EW630RAGU-3P600
630 EW630RAGU-3P630
l HAGU series, 3-pole UL489 Listed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current *
: Available
mounting and
connection
400 250 EW400HAGU-3P250 B, K
Blank, SB, S7, S8
300 EW400HAGU-3P300
350 EW400HAGU-3P350
400 EW400HAGU-3P400
07/34 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
n Type number, Standard series (Motor protection)
Type number/Motor protection
l EAM series, 3-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current
: Available
mounting and
connection
32 1.4 EW32EAM-3P1P4 B, C Blank, X, E, Y, P
2.6 EW32EAM-3P2P6
4 EW32EAM-3P004
5 EW32EAM-3P005
8 EW32EAM-3P008
10 EW32EAM-3P010
16 EW32EAM-3P016
24 EW32EAM-3P024
32 EW32EAM-3P032
50 45 EW50EAM-3P045 B,K Blank, X, E, Y, P
63 63 EW63EAM-3P063 B,K Blank, X, E, Y, P
100 63 EW100EAM-3P063 B,K Blank, X, E, Y, P
75 EW100EAM-3P075
90 EW100EAM-3P090
100 EW100EAM-3P100
250 125 EW250EAM-3P125 B,K Blank, X, E, P
150 EW250EAM-3P150
175 EW250EAM-3P175
225 EW250EAM-3P225
l JAM series, 3-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current
: Available
mounting and
connection
125 75 EW125JAM-3P075 B,K Blank, X, E, P
90 EW125JAM-3P090
250 125 EW250JAM-3P125 B,K Blank, X, E, P
150 EW250JAM-3P150
175 EW250JAM-3P175
225 EW250JAM-3P225
* See page 07/29.
Mounting Connection
Front
Front
Flush
Front
Rear
Rear
Blank
X
E
Flush Top and buttom Y
Plug-in P
l SAM series, 3-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current
: Available
mounting and
connection
32 0.7 EW32SAM-3P0P7 B,K Blank, X, E, Y, P
1.4 EW32SAM-3P1P4
2 EW32SAM-3P002
2.6 EW32SAM-3P2P6
4 EW32SAM-3P004
5 EW32SAM-3P005
8 EW32SAM-3P008
10 EW32SAM-3P010
12 EW32SAM-3P012
16 EW32SAM-3P016
24 EW32SAM-3P024
32 EW32SAM-3P032
50 0.7 EW50SAM-3P0P7 B,K Blank, X, E, Y, P
1.4 EW50SAM-3P1P4
2 EW50SAM-3P002
2.6 EW50SAM-3P2P6
4 EW50SAM-3P004
5 EW50SAM-3P005
8 EW50SAM-3P008
10 EW50SAM-3P010
12 EW50SAM-3P012
16 EW50SAM-3P016
24 EW50SAM-3P024
32 EW50SAM-3P032
40 EW50SAM-3P040
45 EW50SAM-3P045
63 63 EW63SAM-3P063 B,K Blank, X, E, Y, P
l RAM series, 3-pole IEC/EN/GB/JIS conformed
Breaker
ampere
frame
Rated
current
(A)
Type : Rated
sensitive
current
: Available
mounting and
connection
125 45 EW125RAM-3P045 B,K Blank, X, E, P
60 EW125RAM-3P060
75 EW125RAM-3P075
90 EW125RAM-3P090
250 125 EW250RAM-3P125 B,K Blank, X, E, P
150 EW250RAM-3P150
175 EW250RAM-3P175
225 EW250RAM-3P225
Rated sensitive current
30mA
100mA B
C
100/200mA changeover K
100/200/500mA changeover K
100/200/500/1000mA changeover K
07/35
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
n Arc space, mm
Arc space
A
B
C
F
D 3
D 1
D 2
Frame
size
32A
50A
63A
100A
125A
160A
250A
400A
630A
800A
ELCB
basic type
EW32A
EW32E
EW32S
EW50A
EW50E
EW50S
EW50R
EW63E
EW63S
EW63R
EW100A
EW100E
EW125J
EW125S
EW125R
EW160E
EW160J
EW160S
EW160R
EW250E
EW250J
EW250S
EW250R
EW400E
EW400S
EW400R
EW400H
EW630E
EW630R
EW630H
EW800E
EW800R
EW800H
Ceiling distance
A
440V
10
10
10
30
50
10
30
50
50
40
40
40
40
40
40
40
40
40
40
40
100
100
100
100
100
100
120
100
100
120
230V
10
10
10
10
10
10
25
10
10
25
10
25
40
40
40
40
40
40
40
40
40
40
40
80
80
80
80
80
80
100
80
80
100
Vertical distance
B
440V
30
30
30
40
50
30
40
50
50
50
60
60
50
60
80
80
50
60
80
80
100
100
100
100
100
100
120
100
100
120
230V
10
10
30
10
30
40
50
30
40
50
20
50
50
60
60
50
60
80
80
50
60
80
80
80
80
80
80
80
80
100
80
80
100
Side plate
distance
C
440V
20
20
25
25
25
25
25
25
25
25
25
25
50
50
50
50
50
50
50
50
50
50
80
80
80
80
80
80
80
80
230V
10
15
15
10
15
15
15
15
15
15
15
15
20
20
20
15
20
20
20
15
20
20
20
20
20
40
40
40
40
40
40
40
40
Front plate distance
Painted
F
440V
0
0
0
0
0
0
0
0
0
0
5
5
0
0
5
5
0
0
5
5
0
0
5
5
0
5
5
0
5
5
230V
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Taping
Crimp type
terminal lug
D1
Bus-bar
D2
10
30
30
10
30
30
50
30
30
50
50
50
50
50
50
80
80
80
80
80
80
80
80
100
100
100
100
100
100
120
100
100
120
Barrier
D3
10
30
30
10
30
30
50
30
30
50
50
50
50
50
50
80
80
80
80
80
80
80
80
100
100
100
100
100
100
120
100
100
120
No painted
F
440V
0
0
0
0
10
0
0
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
10
20
20
10
20
20
230V
0
0
0
0
0
0
5
0
0
5
0
5
5
5
5
5
5
10
10
5
5
10
10
5
5
10
10
5
10
10
5
10
20
Exposed live part dimension +20
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/36
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
nDimensions, mm
Front mounting, front connection
EW32 -3P, EW50 -3P
EW32 -2P, EW50 -2P
EW63 -3P
Mounting hole ø4.9
Counterbore ø7.8
Trip button
Test button
EL trip indicating
button
M4 or ø5
R2 or less
52 or more
50 or more
Insulation barrier
Detachable
Panel drilling Front panel cutting Terminal section
50
84
100 50
C
L
40 42
C
L
25
47.5
50
10 8
C
L
ON
51
60 8 4 84
43
46 2.5
C
L C
L
C
L C
L
84
ELCB ELCB
Max. 15
7
t 4
ø5.5
7
17
M5×14
24
Insulation barriers
Standard provided: EW50SAG, EW50RAG
Optional: EW32AAG, EW50EAG
Mounting hole ø4.9
Counterbore ø7.8
Trip button
M4 or ø5
R2 or less
52 or more
74 or more
Insulation barrier
Detachable
Sensitive current
selective switch
Panel drilling Front panel cutting Terminal section
C
L
ON
51
6084 84
43
46 2.5
C
L
C
L
ELCB ELCB
Max. 15
7
t4
ø5.5
7
17
M5×14
24
50
84
100
C
L
4042
C
L
50
72
75
50
10
8
C
L
C
L
84
25
Insulation barriers
Standard provided: EW50SAG, EW50RAG
Optional: EW32AAG, EW32SAG, EW50EAG
Test button
EL trip indicating
button
Trip button
M4 or ø5
R2 or less
52 or more
74 or more
Insulation barrier
Detachable
Panel drilling Front panel cutting Terminal section
C
L
ON
51
60 8 4 84
43
46 2.5
C
L
C
L
ELCB ELCB
50
84
100
C
L
40 42
C
L
50
72
75
50
10
8
C
L
C
L
84
25
7
17
Max. 15
7
t6
24
M8 x 15
ø9
Sensitive current
selective switch
Test button
EL trip indicating
button
Mounting hole ø4.9
Counterbore ø7.8
07/37
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
EW100 -2P, 3P
EW125 -3P
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
nDimensions, mm
Front mounting, front connection
Trip button
M4 or ø5
R2 or less
52 or more
74 or more
Insulation barrier
Detachable
Panel drilling Front panel cutting Terminal section
C
L
ON
51
60 8 4 84
43
46 2.5
C
L
C
L
ELCB ELCB
50
84
100
C
L
40 42
C
L
50
72
75
50
10
8
C
L
C
L
84
25
Insulation barriers
Standard provided: EW100EAG
Optional: EW100AAG
7
17
Max. 15
7
t6
24
M8 x 15
ø9
M5 x 14 for EW100EAG-3P050
Sensitive current
selective switch
EL trip indicating
button
Mounting hole ø4.9
Counterbore ø7.8
Test button
Mounting hole
Trip button
M4 or ø5
R2 or less
52 or more
87 or more
Insulation barrier
Detachable
Panel drilling Front panel cutting Terminal section
50
90
85
60
38
22
155
135
15
50
102
50
ELCB
ELCB
132
30
M8 x 16
ø9
t<6
8
17
10 8.5
24
L
C
L
C
L
C
ø4.5
ø8.2
ON
60
64
57
3.5
68
7 95
4
L
C L
C
L
C
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/38
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
EW125 -4P
nDimensions, mm
Front mounting, front connection
Mounting hole
Trip button
M4 or ø5
R2 or less
52 or more
117 or more
73.5 or more 43.5 or
more
Insulation barrier
Detachable Panel drilling Front panel cutting Terminal section
L
C
50
75 120 45
72.5 42.5
30 30 30
38
22
155
135
15
50
102
50
ELCB
ELCB
132
30
M8 x 16
ø9
t<6
8
17
10 8.5
24
L
C
ø4.5
ø8.2
ON
60
64
57
3.5
68
7 95
4
L
C L
C
L
C
L
C
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Test button
Megger
test switch
ELCB
For N, V type handle
2 3 1
30 M4 or *5
L
C
L
C
30
07/39
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
EW160 -3P
EW250 -3P
EW160 -4P
EW250 -4P
nDimensions, mm
Front mounting, front connection
Mounting hole
Trip button
ø4.5
ø8.2
M4 or ø5
R2 or less
52 or more
102 or more
M8 x 16
ø9
t<6
Max. 25
Insulation barrier
Detachable
Panel drilling Front panel cutting Terminal section
80
105
100
70
45.5
22
165
144
15
50
102
80
60 4
ON
57
64
3.5
68
7 95
ELCB
126
35
ELCB
24 25.5
10.5 11
8
L
C
L
C
L
C
L
C
L
C
L
C
L
C
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
Mounting hole
Trip button
ø4.5
ø8.2
M4 or ø5
R2 or less
52 or more
137 or more
86 or more 51 or
more
Insulation barrier
Detachable Panel drilling Front panel cutting
L
C
80
87.5 140 52.5
85 50
35 35 35
45.5
22
165
144
15
50
102
80
ELCB
126
35
L
C L
C
ELCB
M8 x 16
ø9
t<6
Max. 25 24 25.5
10.5 11
8
Terminal section
L
C
L
C
L
C
60 4
ON
57
64
3.5
68
7 95
L
C
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/40
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
nDimensions, mm
Front mounting, front connection
EW400 -3P
EW400 -4P
Mounting hole
Trip button
ø13.5
ø7
M6 or ø7
R2 or less
92 or more
137 or more
Insulation barrier
Detachable Panel drilling Front panel cutting
225
215
257 105 105
44
88
56
135
56
140
25
60
52
16
41.5
41.5
24.5
ELCB
102
90
127
44
103
94.5
84
8
4
4
117.5
146
ELCB
215
44
L
C
L
C
L
C L
C
L
C
L
C
L
C
M12 x 35 bolt
55
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
Mounting hole
Trip button
ø13.5
ø7
M6 or ø7
R2 or less
92 or more
137 or more
Insulation barrier
Detachable Panel drilling Front panel cutting
ELCB
215
44
225
215
257 105 105
44
88
52.5
132
52.5
52.5
135
185
25
60
52
16 41.5
41.5
24.5
ELCB
L
C
L
C
102
90
127
44
103
94.5
84
8
4
4
117.5
146
L
C L
C
L
C L
C
L
C
M12 x 35 bolt
55
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
07/41
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
nDimensions, mm
Front mounting, front connection
EW630 -3P
EW800 -3P
Panel drilling Front panel cutting
24.5
7
7
38.5
87
105 105
93
90
102
127
94.5
103
4
4 117.5
146
205
243
275
44
87 15 32
8
ø13.5
ø7
84
ELCB
243
70
207 or more
min.92
M6 or ø7
ELCB
R2 or less
L
C
L
C
L
C
L
C
210
70
70
70
52
Mounting hole
Insulation barrier
Detachable
Trip button
M12 x 40
Hexagon head bolt
55
83.5
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger test switch
Test button
Panel drilling Front panel cutting
M12 x 40
Hexagon head bolt 10
87 105 105
93
90
102
127
94.5
103
4
4 117.5
146
210
70
70
70
52
205
243
275
24.5
44
87 15 32 8
10
41.5
ø13.5
ø7
84
Trip button
Insulation barrier
Detachable
Mounting hole ELCB
R2 or less
243
70
207 or more
min.92
M6 or ø7
ELCB
L
C
L
C
L
C
L
C
55
83.5
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger test switch
Test button
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/42
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
nDimensions, mm
Front mounting, rear connection (type X)
EW32 -3P, EW50 -3P
EW32 -2P, EW50 -2P
EW63 -3P
Mounting
hole
Trip button
M4 or ø5
ø22 ELCB
Panel drilling
Terminal
cover Terminal
cover
Pannel
ø6.5
(M6 x 18 bolt)
Note: Ex-works, studs are mounted on the ELCB unit as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90˚.
110
84
C
L
C
L
25
47.5
C
L
C
L
50
50
84
100
137
C
L
45 8
8 95
25
14
50.5
59
68
8
4
92
C
L
3
110
ON
Mounting
hole
Trip button
M4 or ø5
ø22
Panel drilling
Terminal
cover Terminal
cover
Pannel
ø6.5
(M6 x 18 bolt)
Note: Ex-works, studs are mounted on the ELCB unit as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90˚.
2-pole breaker is supplied in 3-pole frame with current carrying parts omitted from center pole.
72
75
50
84
100
137
C
L
C
L
50.5
59
68
8
4
92
C
L
3
110
ON
25
50
84
110
ELCB
C
L
C
L
45 8
95 8
14
25 25
C
L
Test button
EL trip indicating
button
Mounting
hole
Trip button
M4 or ø5
ø22
Panel drilling
Terminal
cover Terminal
cover
Pannel
ø6.5
(M6 x 18 bolt)
Note: Ex-works, studs are mounted on the ELCB unit as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90˚.
2-pole breaker is supplied in 3-pole frame with current carrying parts omitted from center pole.
72
75
50
84
100
137
C
L
C
L
50.5
59
68
8
4
92
C
L
3
110
ON
25
50
84
110
ELCB
C
L
C
L
45 8
95 8
14
25 25
C
L
Test button
EL trip indicating
button
07/43
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
EW100 -2P,3P
EW125 -3P
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
nDimensions, mm
Front mounting, rear connection (type X)
Mounting
hole
Trip button
M4 or ø5
ø22
Panel drilling
Terminal
cover Terminal
cover
Pannel
ø6.5
(M6 x 18 bolt)
Note: Ex-works, studs are mounted on the ELCB unit as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90˚.
2-pole breaker is supplied in 3-pole frame with current carrying parts omitted from center pole.
72
75
50
84
100
137
C
L
C
L
50.5
59
68
8
4
92
C
L
3
110
ON
25
50
84
110
ELCB
C
L
C
L
45 8
95 8
14
25 25
C
L
EL trip
indicating button
Test button
Mounting
hole
Trip button
M4 or ø5
Panel drilling
L
C
L
C
90
85
22
50
155
102
5 5
30
30
16
87 37
15 15
2.5
ELCB
L
C
L
C
30
60
135
132
Insulation tubu
ø8.5
(M8 x 25 bolt)
ø8.5
(M8 x 25 bolt)
ø18
Terminal
cover Pannel
L
C
ON
68
95
64
37
3.5
7
135 5
Note: Ex-works, studs are mounted on the ELCB unit as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90˚.
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/44
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
nDimensions, mm
Front mounting, rear connection (type X)
EW125 -4P
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
Mounting
hole
Trip button
M4 or ø5
Panel drilling
L
C
L
C
120
72.5 42.5
45
22
50
155
102
5 5
30
30
30
16
87 37
15
15
2.5
ELCB
L
C
L
C
30
30
45
90
135
132
Terminal
cover Pannel
L
C
ON
68
95
64
37
3.5
7
135 5
Insulation
tubu
ø8.5
(M8 x 25 bolt) ø18
Note: Ex-works, studs are mounted on the ELCB unit
as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90˚.
M4 or ø5
ø18
For V, N type handle
L
C
L
C
ELCB
30
30
45
90
5 3 1 2 3 1
30
07/45
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
EW160 -3P
EW250 -3P
EW160 -4P
EW250 -4P
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
nDimensions, mm
Front mounting, rear connection (type X)
Mounting
hole Terminal
cover Pannel
Trip button M4 or ø5
Panel drilling
ELCB
ø24
105
100
22
50
165
102
5 5
35
35
22
93.5
57.5
20 14
ON
68
64 Max. 6
37
3.5
7 95
144 5
35
70
144
126
L
C
L
C L
C L
C
L
C
ø9
(M8 x 25 bolt)
Note: Ex-works, studs are mounted on the ELCB unit as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90˚.
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
Mounting
hole
Trip
button
M4 or ø5
Panel drilling
ELCB
ø24
L
C
35 35 35
35
52.5
144
126
L
C
85 50
52.5
22
50
165
140
102
5 5
35 35 35
22
93.5
57.5
20
14
L
C
Terminal
cover Pannel
ON
68
64 Max. 6
37
3.5
7 95
144 5
L
C L
C
ø9
(M8 x 25 bolt)
Note: Ex-works, studs are mounted on the ELCB unit as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90˚.
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/46
EW400 -3P
EW400 -4P
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
nDimensions, mm
Front mounting, rear connection (type X)
Mounting
hole Panel
Angle
Angle
Special nut
(supplied)
M6 or ø7
ø7
ø35
M12 x 35 bolt
Live section
cover
Insulation
tube
Panel drilling Angle mounting
Note: Ex-works, studs are mounted on the ELCB unit as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90˚.
140
51
266
257 4.5 4.5
102
90
ON
4.5
60
110
115
106.5
158
16
15 27
12
4
225
31
13
8
225
215
5 5 5 5
44
44
44
ELCB
44 44
160 15 15
108
ELCB
L
C
L
C L
C
L
C
L
C
L
C
L
C
55
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
Mounting
hole
Angle
Special
nut
(supplied)
ø7
M6 or ø7
ø35
Live section
cover
Insulation
tube
Panel drilling Angle mounting
Note: Ex-works, studs are mounted on the ELCB unit as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90˚.
44
44 44
L
C
185
70.5
51
266
257 4.5
4.5
102
90
225
215
5 5 5 5
44
44
44 44
ELCB L
C
160 15
15
108
54
ELCB
L
C
Panel
Angle
M12 x 35 bolt
ON
4.5
60
110
115
106.5
158
16
15 27
12
4
225
31
13
8
L
C L
C L
C
L
C
55
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
07/47
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
EW630 -3P
EW800 -3P
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Standard
nDimensions, mm
Front mounting, rear connection (type X)
Panel drilling Angle mounting
Note: Ex-works, studs are mounted on the ELCB unit as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Specify the stud directions when ordering. Contact FUJI.
*1 Connectable area.
52
24.5
93
127
90
102
129.5
158
4
4
98
20 32 8
413
106.5
12
115 85*1 M12X40Bolt
180
125 243
70 70
275 11 11 297
210
243 5 5 10
70
140
160 15
178
15
ELCB
ø7
10
M6 or ø7 ø48
40X40X5
ELCB
Angle
L
C
C
L
L
C
L
C C
C
L
L
C
C
L
L
ON
Angle
Panel
Insulation
barrier
Live section cover
Mounting hole
43
ø13
10
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger test switch
Test button
83.5
55
Trip button
Panel drilling Angle mounting
Note: Ex-works, studs are mounted on the ELCB unit as shown in the figure for side view.
•Studs for line side terminal : Mounted horizontally.
•Studs for load-side terminal : Mounted vertically.
Specify the stud directions when ordering. Contact FUJI.
*1 Connectable area.
C
L
C
C
L
L
C
L
C
L C
C
L
L
C
C
L
L
ON
Trip button
Angle
Panel
Live section cover
Mounting hole
52
ø4
11.5
24.5
93
127
90
102
129.5
158
4
4
98
20 32 8
45
413
106.5
12
115 85*1 M12X40Bolt
180
125
243
70 70
275
11 11
297
210
243 5 5
10
70
140
160 15
178
15
ELCB
ø7
10
M6 or ø7 ø48
40X40X5
ELCB
Angle
Insulation
barrier
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger test switch
Test button
83.5
55
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/48
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Global
nDimensions, mm
Front mounting, front connection
EW50RAGU-3P
EW100EAGU-2P, -3P
Mounting hole Terminal cover
(Short type)
EL trip
indication button
Sensitive current
selective switch
Trip button
Test button
Panel drilling Front panel cutting Terminal section
L
C
C
L
75
50
9.8 9.8 100
84
50
40 42
C
L
84
4 8
60
51
ON 48.5
2.5 51
43 M4 or ø5
25
84
L
C
L
C
L
C
ELCB
74 or more
52 or more
R2 or less
ELCB
C
L
24
8 8.3
M5 x 14
17
Mounting hole Terminal cover
(Short type)
Trip button
Panel drilling Front panel cutting Terminal section
L
C
C
L
75
50
9.8 9.8 100
84
50
40 42
C
L
84
4 8
60
51
ON 48.5
2.5 51
43 M4 or ø5
25
84
L
C
L
C
L
C
ELCB
74 or more
52 or more
R2 or less
ELCB
C
L
M8 x 15
8 8.3
24
17
EL trip
indication button
Sensitive current
selective switch Test button
07/49
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07
EW125 U-3P
EW250 U-3P
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Global
nDimensions, mm
Front mounting, front connection
Panel drilling Front panel cutting
Terminal section
87 or more
52 or more
ELCB
R2 or less
17
M8 x 16
ø9
t<6
10 8.5
24
Max. 16.5
8
ELCB
132
30
L
C
L
C
L
C
L
C
38
22
90
60
85
L
C
50
15
Insuration barrier
Detachable
Mounting
hole
Trip button
M4 or ø5
135
155
8
5050
8
102
L
CL
C
460
ø4.5
ø8.2
57
64
687
3.5
95
ON
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
Panel drilling Front panel cutting
Terminal section
52 or more
R2 or less
M8 x 16
Insuration barrier
Detachable
Mounting hole
Trip button
M4 or ø5
ø4.5
ø8.2
24
25.5
10.5 11
ELCB
126
35
L
C
L
C
8
80
8
102
105
460
57
95
3.5
7 68
64
100
22
45.5
15
50
144
165
70
ON
80
L
C
L
C
L
C
102 or more
ELCB
L
C
L
C
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger
test switch
Test button
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
07/50
EW400 U-3P
Earth Leakage Circuit Breakers
G-TWIN series
Dimensions / Global
nDimensions, mm
Front mounting, front connection
EW630 U-3P
Mounting hole
Trip button
ø13.5
ø7
M6 or ø7
R2 or less
92 or more
137 or more
Insulation barrier
Detachable
Panel drilling Front panel cutting
225
215
257105 105
44
88
56
135
56
140
25
60
52
16
41.5
41.5
24.5
ELCB
102
90
127
44
103
94.5
84
8
4
4
117.5
146
ELCB
215
44
L
C
L
C
L
CL
C
L
C
L
C
L
C
M12 x 35 bolt
55
EL trip
indicating button
Sensitive current
selective switch
Operating time
selective switch
Megger test switch
Test button
7
7
38.5
87 105 105
93
90
102
127
94.5
103
4
4 117.5
146
205
243
275
44
87 15
32
8
ø13.5
ø7
84
ELCB
243
70
M6 or ø7
207 or more
92 or more
R2 or less
ELCB
L
C
L
C
L
C
L
C L
C
L
C
L
C
52
70 70
24.5
210
70
38.5
Mounting hole
Megger test switch
Test button
Trip button
M12 x 40
Hexagon head bolt
Insulation barrier
Detachable
EL trip
indication button
Sensitive current
selective switch
Operating time
selective switch
Panel drilling Front panel cutting
83.5
55
07/51
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
EW32/50/63/100
n Characteristic curves / Line protection
Characteristic curves
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
1
2
4
6
10
20
40
1
2
4
6
10
20
40
60
120
180
1 1.5 2 3 4 5 678 10 15 20 30 4050 70 100
Muitiple of rated current
Instantaneous
tripping
characteristic
960%-1440%
Max. value
Min. value
Minute
Second
Operating time
Rated current: 5, 10, 32, 40, 60, 63, 70, 75, 80, 90A
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
1
2
4
6
10
20
40
1
2
4
6
10
20
40
60
120
180
1 1.5 2 3 4 5 678 10 15 20 30 4050 70 100
Muitiple of rated current
Instantaneous
tripping
characteristic
800%-1200%
Max. value
Min. value
Minute
Second Operating time
Rated current: 3, 15, 20, 30, 50,100A
-10 010 20 30 40 50
400
300
350
250
200
150
100
50
Reference temp. 40
Operating time
correction ratio (%)
Ambient temperature ( )
Temperature correction curve
0.04
0.1
1
0.01
10 30 100 200 500 1000 3000 10000
30mA 15mA
Ground fault current
(Multiple of rated sensitive current %)
5I n 0.04s max. (15, 30mA types: At 250mA)
Min. 50mA
Rated sensitive current(I n)
Rated non-tripping current
Earth leakage tripping
EW32/50/63/100A
07/52 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
EW125
n Characteristic curves / Line protection
Temperature correction curve
• 15A • 20A
• 15-30A
• 30A
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 6 7 8
10 15 20 30 40 50 60 80
100
Muitiple of rated current
Instantaneous tripping
characteristic
500A±100A
Max. value
Min. value
Max. total fault
clearing time
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 6 7 8
10 15 20 30 40 50 60 80 100
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 6 7 8
10 15 20 30 40 50 60 80
100
-10 100 20 30 40 50
Ambient temp. (°C)
50
100
150
Minute
Second Operating time
Reference temp. 40°C
Rated current
correction ratio (%)
Muitiple of rated current
Max. value
Min. value
Max. total fault
clearing time
Instantaneous tripping
characteristic
500A±100A
Muitiple of rated current
Max. value
Min. value
Max. total fault
clearing time
Instantaneous tripping
characteristic
500A±100A
Minute
Second Operating time
Minute
Second Operating time
Temperature correction curve
• 40A • 50-125A
• 40-125A
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 6 7 8
10 15 20 30 40 50 60 80 100
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 6 7 8
10 15 20 30 40 50 60 80 100
-10 100 20 30 40 50
50
100
150 Reference temp. 40°C
Ambient temp. (°C)
Rated current
correction ratio (%)
Muitiple of rated current Muitiple of rated current
Max. value Max. value
Min. value
Min. value Max. total fault
clearing time Max. total fault
clearing time
Instantaneous tripping
characteristic
500A±100A
Instantaneous
tripping
characteristic
10In±20%
Minute
Second
Operating time
Minute
Second Operating time
Characteristic curves
07/53
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Characteristic curves
EW160/250
EW400
n Characteristic curves / Line protection
Temperature correction curve
Temperature correction curve
Reference temp. 40°C
Reference temp. 40°C
Ambient temp. (°C)
Ambient temp. (°C)
Rated current
correction ratio (%)
Rated current
correction ratio (%)
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 6 7 8
10 15 20 30 40 50 60 80 100
−10 100 20 30 40 50
50
100
150
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 678
10 15 20 30 40 5060 80 100
−10 100 20 30 40 50
50
100
150
Muitiple of rated current
Muitiple of rated current
Max. value
Min. value Max. total fault
clearing time
Instantaneous
tripping
characteristic
10In±20%
Max. value
Min. value Max. total fault
clearing time
Instantaneous
tripping
characteristic
10In±20%
Minute
Second
Operating time
Minute
Second
Operating time
EW630
Temperature correction curve
Reference temp. 40°C
Ambient temp. (°C)
Rated current
correction ratio (%)
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 6 7 8
10 15 20 30 40 50 60 80 100
−10 100 20 30 40 50
50
100
150
Muitiple of rated current
Max. value
Min. value Max. total fault
clearing time
Instantaneous
tripping
characteristic
10In±20%
Minute
Second
Operating time
07/54 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Characteristic curves
EW800
n Characteristic curves / Line protection
Temperature correction curve
Reference temp. 40°C
Ambient temp. (°C)
Rated current
correction ratio (%)
−10 100 20 30 40 50
50
100
150
Muitiple of rated current
Minute
Second
Operating time
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1 1.5 2 3 4 5 678 10 15 20 30 40506080100
Max. value
Min. value Max. total fault
clearing time
Instantaneous
tripping
characteristic
640-960%
240
120
60
30
10
4
2
1
30
20
10
5
2
1
0.5
0.2
0.1
0.04
0.02
0.01
240
120
60
30
10
4
2
1
30
20
10
5
2
1
0.5
0.2
0.1
0.04
0.02
0.01
25 50 100 500 1000 10000 25 50 100 500 1000 10000 25 50 100 500 1000 10000 25 50 100 500 1000
10000
Operating time
Operating time
Rated non-tripping current
Rated non-tripping current
Rated non-tripping current
Rated non-tripping current
Minute Second
Minute Second
Ground fault current
(Multiple of rated sensitive current %) Ground fault current
(Multiple of rated sensitive current %)
Instantaneous trip type
Time-delay trip type
Rated sensitive current (I n)
Rated sensitive current (I n)
Rated sensitive current (I n)
Rated sensitive current (I n)
Max. operating time: 0.4s Max. operating time: 1s Max. operating time: 2s
Inertia non-operating
time Inertia non-operating
time Inertia non-operating
time
Earth leakage tripping
EW125/160/250/400/630/800
07/55
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
EW32/50/63/100
EW125
n Characteristic curves / Motor protection
-10 010 20 30 40 50
400
300
350
250
200
150
100
50
Reference temp. 40
Operating time
correction ratio (%)
Ambient temperature ( )
Temperature correction curve
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
1
2
4
6
10
20
40
1
2
4
6
10
20
40
60
120
180
1 1.5 2 3 4 5 678 10 15 20 30 4050 70 100
Muitiple of rated current
Instantaneous
tripping
characteristic
960%-1440%
Max. value
Min. value
Minute
Second
Operating time
• 16A • 24A • 32A
• 40-90A
Temperature correction curve
• 15-32A
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 678
10 15 20 30 40 5060 80
100
Muitiple of rated current
Muitiple of rated current
Muitiple of rated current Muitiple of rated current
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 6 78
10 15 20 30 40 50 6080100
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5678
10 15 20 30 40 5060 80 100
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 6 78
10 15 20 30 40 5060 80100
−10 100 20 30 40 50
50
100
150
• 40-90A
-10 100 20 30 40 50
50
100
150 Reference temp. 40°CReference temp. 40°C
Ambient temp. (°C)Ambient temp. (°C)
Rated current
correction ratio (%)
Rated current
correction ratio (%)
Max. value
Max. value
Max. value Max. value
Min. value
Min. value
Min. value Min. value
Max. total fault
clearing time
Max. total fault
clearing time
Max. total fault
clearing time
Max. total fault
clearing time
Instantaneous
tripping
characteristic
500A±100A
Instantaneous
tripping
characteristic
1200-1800%
Instantaneous
tripping
characteristic
500A±100A
Instantaneous
tripping
characteristic
500A±100A
Minute
Second Operating time
Minute
Second Operating time
Minute
Second Operating time
Minute
Second Operating time
Characteristic curves
07/56 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
EW250
n Characteristic curves / Motor protection
Temperature correction curve
Muitiple of rated current
Reference temp. 40°C
Rated current
correction ratio (%)
Minute
Second Operating time
1
2
4
6
1
2
4
6
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
10
20
40
10
20
40
60
120
180
1
1.5
2 3 4 5 678
10 15 20 30 40 5060 80 100
−10 100 20 30 40 50
Ambient temp. (°C)
50
100
150
Max. value
Min. value Max. total fault
clearing time
Instantaneous
tripping
characteristic
1040A-1560A
Characteristic curves
0.04
0.1
1
10
0.01
10 30 100 200 500 1000 3000 10000
30mA 15mA
Ground fault current
(Multiple of rated sensitive current %)
5I n 0.04s max. (15, 30mA types: At 250mA)
Min. 50mA
Rated sensitive current(I n)
Rated non-tripping current
Earth leakage tripping
EW32/50/63
240
120
60
30
10
4
2
1
30
20
10
5
2
1
0.5
0.2
0.1
0.04
0.02
0.01
240
120
60
30
10
4
2
1
30
20
10
5
2
1
0.5
0.2
0.1
0.04
0.02
0.01
25 50 100 500 1000 10000 25 50 100 500 1000 10000 25 50 100 500 1000 10000 25 50 100 500 1000
10000
Operating time
Operating time
Rated non-tripping current
Rated non-tripping current
Rated non-tripping current
Rated non-tripping current
Minute Second
Minute Second
Ground fault current
(Multiple of rated sensitive current %) Ground fault current
(Multiple of rated sensitive current %)
Instantaneous trip type Time-delay trip type
Rated sensitive current (I n)
Rated sensitive current (I n)
Rated sensitive current (I n)
Rated sensitive current (I n)
Max. operating time: 0.4s Max. operating time: 1s Max. operating time: 2s
Inertia non-operating
time Inertia non-operating
time Inertia non-operating
time
EW125/250
07/57
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Auxiliary switch (Type W)
This switch is used for indicator lamp
or control circuit.
See page 07/63.
Alarm switch (Type K)
This switch can be connected to a
warning lamp or buzzer to indicate
when the breaker has been tripped.
See page 07/63.
Shunt trip device (Type F)
The purpose of this accessory is to trip
the breaker from a distance.
See page 07/64.
Undervoltage trip device (Type R)
The device is designed to protect circuits
from harmful voltage drops.
It can also be used for remote control
purposes. The trip operates when the
voltage drops to less than 70% of
nominal coil rating, and the breaker
cannot be reset until the voltage
recovers 85% of its normal rating.
See page 07/65.
Terminal block (Type A)
A wiring terminal for internal accessories
(Order with W, K or F)
See page 07/66.
Earth Leakage Circuit Breakers
G-TWIN series
Accessories
n Variation of internal accessory
• 32 to100AF
07/58 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Accessories
n Variation of internal accessory
• 125 to 250AF
Auxiliary switch (Type W)
This switch is used for indicator lamp
or control circuit.
See page 07/63.
Alarm switch (Type K)
This switch can be connected to a
warning lamp or buzzer to indicate
when the breaker has been tripped.
See page 07/63.
Shunt trip device (Type F)
The purpose of this accessory is to trip
the breaker from a distance.
See page 07/64.
Earth alarm switch (Type L)
This switch can be connected to a warning
lamp or buzzer to indicate when the
breaker has been tripped by leakage
current.
See page 07/63.
Undervoltage trip device (Type R)
The device is designed to protect circuits
from harmful voltage drops.
It can also be used for remote control
purposes. The trip operates when the
voltage drops to less than 70% of
nominal coil rating, and the breaker
cannot be reset until the voltage
recovers 85% of its normal rating.
See page 07/65.
Terminal block (Type A)
A wiring terminal for internal accessories
(Factory-mounted)
See page 07/66.
07/59
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Accessories
n Variation of internal accessory
• 400 to 800AF
Auxiliary switch (Type W)
This switch is used for indicator lamp
or control circuit.
See page 07/63.
Alarm switch (Type K)
This switch can be connected to a
warning lamp or buzzer to indicate
when the breaker has been tripped.
See page 07/63.
Shunt trip device (Type F)
The purpose of this accessory is to trip
the breaker from a distance.
See page 07/64.
Undervoltage trip device (Type R)
The device is designed to protect circuits
from harmful voltage drops.
It can also be used for remote control
purposes. The trip operates when the
voltage drops to less than 70% of
nominal coil rating, and the breaker
cannot be reset until the voltage
recovers 85% of its normal rating.
See page 07/65.
Terminal block (Type A)
A wiring terminal for internal accessories
(Factory-mounted)
See page 07/66.
Earth alarm switch (Type L)
This switch can be connected to a warning
lamp or buzzer to indicate when the
breaker has been tripped by leakage
current.
See page 07/63. (Factory-mounted)
07/60 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
n Variation of external accessory
Earth Leakage Circuit Breakers
G-TWIN series
Accessories
Terminal cover
Long type
See page 07/85.
Interphase barrier
See page 07/86.
Handle locking cover (L1)
See page 07/87.
Padlocking device
See page 07/87.
External operating handles
• N-type
See page 07/74.
V-type
See page 07/74.
• F-type
See page 07/74.
Terminal cover
Short type
See page 07/85.
• Cap type (Q1, QN)
• Plate type (Q2)
Steel enclosures
See page 07/83.
Motor-operating mechanism
See page 07/69.
Mechanical interlock device
See page 07/70.
07/61
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
n Terminal blocks for auxiliary circuit
• It indicates the terminal No. of internal accessory.The
connection method of internal accessory is lead-wire system
and terminal block system.
• For the available conguration of internal accessory, see
page 07/62.
Terminal number of internal accessory
Accessory
Auxiliary switch
Alarm switch
Shunt trip device : F
Undervoltage trip device : R
Earth alarm switch (125 to 800AF)
Note: * ( ) Code of Low level circuit
SPDT: W (1)*
2PDT: V (2)*
SPDT: K (8)*
2PDT: J (9)*
With 1NO contact
to prevent coil
burn-out
Continuous rating
32 – 250AF
Left side mounting
Right side mounting 400 – 800AF
Left side mounting
21
AXcR 22
AXbR 24
AXaR
21
AXcR 22
AXbR 24
AXaR
01
ALcR 02
ALbR 04
ALaR
01
ALcR 02
ALbR 04
ALaR
11
AXcL 12
AXbL 14
AXaL
21
AXc 22
AXb 24
AXa
11
AXc 12
AXb 14
AXa
11
AXcL 12
AXbL 14
AXaL 11
AXc 12
AXb 14
AXa
91
ALcL 92
ALbL 94
ALaL
01
ALc 02
ALb 04
ALa
91
ALc 92
ALb 94
ALa
91
ALcL 92
ALbL 94
ALaL 91
ALc 92
ALb 94
ALa
C2
S2 C1
S1
C2
S2 C1
S1
D2
P2 D1
P1
U<
71 72 74
Lead-wire wiring With terminal block
Earth Leakage Circuit Breakers
G-TWIN series
Internal accessories
07/62 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
n Available configurations
Auxliary switch
SPDT: W (1)*
Alarm switch
SPDT: K (8)*
Shunt trip: F
Undervoltage trip: R
W+K (1+8)
Auxliary switch
2PDT: V (2)
Alarm switch
2PDT: J (9)
V+K (2+8)
W+J (1+9)
V+J (2+9)
W+F (1+F)
W+R (1+R)
K+F (8+F)
K+R (8+R)
W+K+F (1+8+F)
W+K+R (1+8+R)
V+F (2+F)
V+R (2+R)
J+F (9+F)
J+R (9+R)
V+K+F (2+8+F)
V+K+R (2+8+R)
W+J+F (1+9+F)
W+J+R (1+9+R)
V+J+F (2+9+F)
V+J+R (2+9+R)
L
ECCB
Pole 2 2, 3 3 4 3, 4
Notes: •The above table is applied to front mounting type, rear mounting type, flush mounting type, and plug-in mounting type.
• Terminal block is attached on the same side of the accessory.
• ( ) Code of low level circuit :See page 07/2.
EW400
EW630
EW800
EW125
EW160
EW250
EW32-3P
EW50-3P
EW63-3P
EW100-2P
EW100-3P
EW32AAG-2P
EW50AAG-2P
*1
*1
*1
*1
*1
*2
*2
*2
*2
*2
*2
*2
*2
Handle Handle Handle
2-pole 3-pole 4-pole
Left
Right
Right
Shunt trip: F
(Internal)
Undervoltage trip
: R (Internal) Auxiliary switch: W
Alarm switch: K
Lead wire
Earth alarm switch
Undervoltage trip
: R (External) Shunt trip: F
(External)
Left
Right
Earth Leakage Circuit Breakers
G-TWIN series
Internal accessories
07/63
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit Breakers
G-TWIN series
Internal accessories
n Operation of auxiliary switches(W) and alarm switches(K)
Accessory
Auxiliary switch
Alarm switch
SPDT: W
(1)
SPDT: K
(8)
2PDT: J
(9)
2PDT: V
(2)
Handle position
ON OFF Trip
11/AXcL
12/AXbL
14/AXaL
11/AXcL
12/AXbL
14/AXaL
21/AXcR
22/AXbR
24/AXaR
91/ALcL 94/ALaL
92/ALbL
91/ALcL 94/ALaL
92/ALbL
01/ALcR 04/ALaR
02/ALbR
91/ALcL 94/ALaL
92/ALbL
91/ALcL 94ALaL
92/ALbL
01/ALcL 04/ALaL
02/ALbL
11/AXcL
12/AXbL
14/AXaL
11/AXcL
12/AXbL
14/AXaL
21/AXcR
22/AXbR
24/AXaR
Note: Ring mark indication
( ) Code of low level circuit
n Ratings of auxiliary switches(W) and alarm switches(K)
Minimum load
current
5V DC 160mA
30V DC 30mA
5V DC 1mA
Rated operational
Voltage (V)
24
48
125
250
30
Rated operational
Voltage (V)
24
48
125
250
30
Ind. load
5
5
3
2
Res. load
5
5
5
3
0.1
Ind. load
3
1
0.4
0.2
Res. load
4
2.5
0.4
0.2
0.1
Rated operational current (A)
AC DC
• 125-800AF
Rated thermal
current (A)
5
0.1
Standard
type
Low level
circuit
Standard
type
Low level
circuit
• 32-100AF
Voltage (V)
125 AC
250 AC
125 DC
250 DC
AC 15
5
5
DC 13
0.6
0.3
Voltage (V)
125 AC
250 AC
30 DC
125 DC
250 DC
30 DC
Res. load
5
3
4
0.4
0.2
0.1
IEC60947-5-1 NECA C4505
Make/break current (A) Make/break current (A) Minimum load
current
5V DC 160mA
30V DC 30mA
5V DC 1mA
n Operation of earth alarm switch (L)
Accessory
Earth alarm switch L
Handle position
ON/OFF/Overcurrent trip EL trip
71 74
72
71 74
72
07/64 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
n Rating of shunt trip (F)
7-13
13-21
8-20
AC DC Opearting
time
(ms)
ELCB type Installation
External
Internal
Internal
EW32
EW50
EW63
EW100
EW125
EW160
EW250
EW400
EW630
EW800
V
100(50Hz)/
100-110(60Hz)
200(50Hz)/
200-220(60Hz)
400(50Hz)/
400-440(60Hz)
24
48
100-120
120-130
200-240
277
380-440
440-480
500-550
24-48
100-240
277
380-550
VA
16
16
22
50
50
50
50
50
50
50
50
50
2
3
3
4
V
24
100-110
24
48
100-110
200-220
24-48
100-220
Code
FAC100V(50Hz)/
100-110V
(60Hz)
FAC200V(50Hz)/
200-220V
(60Hz)
FAC400V(50Hz)/
400-440V
(60Hz)
FDC24V
FDC100-110V
FAC/DC24V
FAC/DC48V
FAC100-120V/
DC100-110V
FAC120-130V
FAC200-240V/
DC200-220V
FAC277V
FAC380-440V
FAC440-480V
FAC500-550V
FAC/DC24-48V
FAC100-240V/
DC100-220V
FAC277V
FAC380-550V
W
36
23
50
50
50
50
2
3
Continuous
Continuous
(With 1NO contact to
prevent coil burn-out)
Continuous
(With 1NO contact to
prevent coil burn-out)
Continuous
Time rating
of coil
Note: The operating tripping voltage range for shunt trip devices is 70% to 110% of the rated operating voltage.
Earth Leakage Circuit Breakers
G-TWIN series
Internal accessories
07/65
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
n Rating of undervoltage trip (R)
100 (50Hz)/
100-110(60Hz)
200 (50Hz)/
200-220 (60Hz)
400 (50Hz)/
400-440 (60Hz)
100-110
110-130
200-240
277
380-415
440-480
40
5
5
5
5
2
2
3
3
3
24
100-110
24
48
100-110
125
EW32 *2
EW50 *2
EW63 *2
EW100 *2
EW125 *1
EW160 *1
EW250 *1
AC DC
ELCB type Installation
External
Internal
Internal
Code
RAC100V(50Hz)/
100-110V(60Hz)
RAC200V(50Hz)/
200-220V(60Hz)
RAC400V(50Hz)/
400-440V(60Hz)
RDC24V
RDC100-110V
RDC24V
RDC48V
RDC100-110V
RDC125V
RAC100-110V
RAC110V-130V
RAC200-240V
RAC277V
RAC380-415V
RAC440V-480V
RAC/DC24V
RAC/DC48V
RAC/DC100-110V
RAC120-130V/DC125V
RAC200-240V/DC200-220V
RAC277V
RAC380-480V
EW400 *2
EW630 *2
EW800 *2
V
24
48
100-110
120-130
200-240
277
380-480
24
48
100-110
125
200-220
VA V W
Notes: • The operating voltages of undervoltage tripping devices are as follows:
Tripping voltage: 35% to 70% of rated voltage, closing voltage: 85% to 110% of rated voltage.
*
1
Reset-allowed type: When the breaker handle is in the OFF or RESET state, tripping does not occur even if the R coil is not energized.
Turning ON with the R coil not energized causes normal tripping.
*
2
Reset-prohibited type: When the R coil is not energized, reset operation cannot reset the tripped breaker to the OFF state.
2.8
3.4
4.4
5
5
5
5
5
5
2
2
3
3
3
3
4
Earth Leakage Circuit Breakers
G-TWIN series
Internal accessories
07/66 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
n Lead wire specification
125AF, 160AF, 250AF
32AF, 50AF, 63AF, 100AF
400AF, 630AF, 800AF
Notes:
* If the chosen combination has more than 8 terminals, 2 terminal blocks are mounted.
• Mount the terminal block on the surface on which the accessories are mounted.
See the table of the combinations of internal accessories on pages 07/62.
for information on the accessory mounting position.
• Available wire: Solid wire: 1.6ø Stranded wire: 2mm2
Terminal blocks are available as factory mounted only.
100.5
77
53.5
30.5
M3.5
Load
Line
(Left)
Terminal block *
(Right)
38
19
88
6.5
81.5
69
56.5
44
9.5 80 11
117.5
CL
51.5
39.3
27 12
7
12.5
77.2
53.7
30.2
M3.5
L
C
L
C
L
C
L
C
C
LC
L
48.5
36
23.5
48 9
7
77.2
94
53.7
30.2
12.5
n Terminal blocks
n Undervoltage trip device, Shunt trip device
32AF, 50AF, 63AF, 100AF
AF Pole wire size Wire length
32 to 100AF Standard 2P, 3P 0.4mm2 (AWG22) Ca 500mm
Global 0.5mm2 (AWG20)
125 to 250AF 2P, 3P 0.5mm2 (AWG20)
4P
400 to 800AF 2P, 3P 0.5mm2 (AWG20) Ca 500mm
4P Ca 400 to 450mm
Earth Leakage Circuit Breakers
G-TWIN series
Internal accessories
7760
51
41
24
3
68
M3.5
2575
Mass: 0.15kg
10.5
4561
41.5 100
C
L
C
L
C
L
07/67
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Internal accessories (Sold separately)
• 32, 50, 63, 100AF IEC/EN/GB/JIS conformed
n Type number
Accessory Type Operating voltge
Lead wire system Terminal block system
Left side Right side Left side Right side
Auxiliary switch BZ6WL10C BZ6WR10C BZ6WL10CA BZ6WR10CA
Auxiliary switch (low level circuit) BZ6WDL10C BZ6WDR10C BZ6WDL10CA BZ6WDR10CA
Alarm switch BZ6KL10C BZ6KR10C BZ6KL10CA BZ6KR10CA
Alarm switch (low level circuit) BZ6KDL10C BZ6KDR10C BZ6KDL10CA BZ6KDR10CA
Auxiliary switch + Alarm switch BZ6WKL10C BZ6WKR10C BZ6WKL10CA BZ6WKR10CA
Auxiliary switch + Alarm switch (low level circuit)
BZ6WDKDL10C BZ6WDKDR10C BZ6WDKDL10CA BZ6WDKDR10CA
Shunt trip device BZ6F210C
100V AC 50Hz/100-110V AC 60Hz
BZ6F110C
110V AC 50Hz/100-127V AC 60Hz
BZ6F710C
200V AC 50Hz/200-220V AC 60Hz
BZ6F410C
220V AC 50Hz/220-240V AC 60Hz
BZ6F510C
230V AC 50Hz/230-240V AC 60Hz
BZ6FB10C 240V AC 50Hz
BZ6F010C
380V AC 50Hz 380-415V AC 60Hz
BZ6F810C
400V AC 50Hz 400-440V AC 60Hz
Undervoltage trip device BZ6R210C
100V AC 50Hz/100-110V AC 60Hz
BZ6R110C
110V AC 50Hz/110-127V AC 60Hz
BZ6RW10C
200V AC 50Hz/200-220V AC 60Hz
BZ6R410C
220V AC 50Hz/220-240V AC 60Hz
BZ6R510C
230V AC 50Hz/230-240V AC 60Hz
BZ6R810C 240V AC 50Hz
BZ6R010C
380V AC 50Hz 380-415V AC 60Hz
BZ6R910C
400V AC 50Hz 400-440V AC 60Hz
BZ6RF10C 24V DC
BZ6RT10C 100-110V DC
Earth Leakage Circuit Breakers
G-TWIN series
Internal accessories
Accessory Type Operating voltge
Lead wire system Terminal block system
Left side Right side Left side Right side
Auxiliary switch BZ6WL10CU BZ6WR10CU BZ6WL10CAU BZ6WR10CAU
Auxiliary switch (low level circuit) BZ6WDL10CU BZ6WDR10CU BZ6WDL10CAU BZ6WDR10CAU
Alarm switch BZ6KL10CU BZ6KR10CU BZ6KL10CAU BZ6KR10CAU
Alarm switch (low level circuit) BZ6KDL10CU BZ6KDR10CU BZ6KDL10CAU BZ6KDR10CAU
Auxiliary switch + Alarm switch BZ6WKL10CU BZ6WKR10CU BZ6WKL10CA BZ6WKR10CAU
Auxiliary switch + Alarm switch (low level circuit)
BZ6WDKDL10CU BZ6WDKDR10CU
BZ6WDKDL10CAU
BZ6WDKDR10CAU
Shunt trip device –– BZ6F210CAU
100V AC 50Hz/100-110V AC 60Hz
BZ6F710CAU
200V AC 50Hz/200-220V AC 60Hz
BZ6F810CAU
400V AC 50Hz/400-440V AC 60Hz
Undervoltage trip device –– BZ6R210CAU
100V AC 50Hz/100-110V AC 60Hz
BZ6RW10CAU
110V AC 50Hz/110-127V AC 60Hz
BZ6R910CAU
200V AC 50Hz/200-220V AC 60Hz
• 32, 50, 63, 100AF IEC/EN/GB/JIS/UL/CSA conformed
07/68 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Accessory Type Operating voltge
Lead wire system Terminal block system
Left side Right side Left side Right side *
Auxiliary switch BW9W1SG0 BW9W1SG0-R BW9W1SG0-A
Auxiliary switch (low level circuit) BW9W1DG0 BW9W1DG0-R – *
Alarm switch BW9K1SG0 BW9K1SG0-R BW9K1SG0-A
Alarm switch (low level circuit) BW9K1DG0 BW9K1DG0-R – *
Auxiliary switch + Alarm switch BW9WKSG0 BW9WK1SG0-R BW9WKSG0-A
Auxiliary switch + Alarm switch (low level circuit) BW9WKDG0 BW9WK1DG0-R – *
Earth alarm switch BW9L1SGA
Shunt trip device BW9FRG0 BW9FRG0 BW9FRG0-A 24V AC/DC
BW9FSG0 BW9FSG0 BW9FSG0-A 48V AC/DC
BW9FAG0 BW9FAG0 BW9FAG0-A 100-120V AC/100-110V DC
BW9F1G0 BW9F1G0 BW9F1G0-A 120-130V AC
BW9FKG0 BW9FKG0 BW9FKG0-A 200-240V AC/200-220V DC
BW9FBG0 BW9FBG0 BW9FBG0-A 277V AC
BW9FPG0 BW9FPG0 BW9FPG0-A 380-440V AC
BW9FHG0 BW9FHG0 BW9FHG0-A 440-480V AC
BW9FJG0 BW9FJG0 BW9FJG0-A 500-550V AC
Undervoltage trip devics BW9RGAR BW9RGAR-A 24V DC
BW9RGAS BW9RGAS-A 48V DC
BW9RGAL BW9RGAL-A 100-110V DC
BW9RGA5 BW9RGA5-A 125V DC
BW9RGAA BW9RGAA-A 100-110V AC
BW9RGAT BW9RGAT-A 110-130V AC
BW9RGAK BW9RGAK-A 200-240V AC
BW9RGAB BW9RGAB-A 277V AC
BW9RGAP BW9RGAP-A 380-415V AC
BW9RGAH BW9RGAH-A 440-480V AC
Note: * Factory-mounted
Note: * Factory-mounted
Accessory Type Operating voltge
Lead wire system Terminal block system *
Left side
Auxiliary switch x 1 BW9W1SHA
Auxiliary switch x 2 BW9W2SHA
Auxiliary switch (low level circuit) x 1 BW9W1DHA
Auxiliary switch (low level circuit) x 2 BW9W2DHA
Alarm switch x 1 BW9K1SHA
Alarm switch x 2 BW9K2SHA
Alarm switch (low level circuit) x 1 BW9K1DHA
Alarm switch (low level circuit) x 2 BW9K2DHA
Shunt trip device BW9FHA-R 24-48V AC/DC
BW9FHA-A 100-240V AC/100-220V DC
BW9FHA-B 277V AC
BW9FHA-P 380-550V AC
Undervoltage trip devics BW9RHA-R 24V AC/DC
BW9RHA-S 48V AC/DC
BW9RHA-A 100-110 AC/DC
BW9RHA-1 120-130V AC/125V DC
BW9RHA-K 200-240V AC/200-220V DC
BW9RHA-B 277V AC
BW9RHA-P 380-480V AC
• 400, 630, 800AF IEC/EN/GB/JIS/UL/CSA conformed
• 125, 160, 250AF IEC/EN/GB/JIS/UL/CSA conformed
Earth leakage Circuit Breakers
G-TWIN series
Internal accessories
07/69
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
Motor-operated breakers
n Description
The breaker is fitted with a motor operating mechanism which
enables ON, OFF and RESET operations to be carried out
electronically by remote control.
The breakers do not conform to IEC and EN standard.
n Type and ratings
n Ordering information
Specify the following:
1. Type number
2. Motor operating voltage
n Dimensions, mm / Front mounting, front connection
EW32 -3P, EW50 -3P, EW63 -3P, EW100 -2P, EW100 -3P
n Wiring diagrams
100/110V AC, 200/220V AC, 100V DC
Terminal cover
Mass: 1.2kg (EW32 or EW50 type with motor operating mechanism)
1.3kg (EW63 or EW100 type with motor operating mechanism)
Trip button
Insulation barrier
Mounting hole
ø4.5 Operating handle
Notes: • Trip button operation can be carried out at right side of the breaker.
• IEC 35mm wide mounting rail is not available.
L
C
C
LL
C
139
135
4
67
51
75
100
75
84
25
50
50
70
10
C
L
C
L
M4 or ø5
25
84
Panel drilling
C
L
Panel cutting
R2 or more
74 or more
C
ELCB
52 or more
L
DRIVE
UNIT
5
OFF ON
Power supply
(Non polarity)
4 3 E 2 1
CONTROL
CIRCUIT
ELCB type
EW32-3P M, EW50-3P M,
EW63-3P M, EW100-2P M,
EW100-3P M
Motor rating
Operating voltage
100V DC
100/110V AC
200/220V AC
Operating time
0.1s
Time rating
15s per
on-off operation
Power source
capacity
500VA
Mass (kg)
1.2
1.3
07/70 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
These interlocking devices are mounted on
the two separate breakers to prevent them
from both being closed at the same time.
A sliding mechanism that can be locked
with a padlock is used. (The padlock is not
included.)
They are designed for use when changing
over power supplies.
These can be mounted to 3 types of
breakers: front-mounting front-connection
type, front-mounting rear-connection type
(type X), and plug-in mounting type (type P).
Interlock devices for flush mounting type
breakers (type E, Y) are also available.
Mechanical interlocking devices
n Description
M1 types
n Type and applicable breakers
Type Breaker type
BZ6M110C2 EW32AAG-2P, EW50AAG-2P
BZ6M110C3 EW32 -3P, EW50 -3P, EW63 -3P, EW100 -2P, EW100 -3P
BW9M1CA-3 EW125 -3P
BW9M1CA-4 EW125 -4P
BW9M1GA-3 EW250 -3P
BW9M1GA-4 EW250 -4P
BW9M1HA-3 EW400 -3P
BW9M1HA-4 EW400 -4P
BW9M1JA-3 EW630 -3P, EW800 -3P
07/71
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
n Dimensions, mm
• 32AF to 100AF Panel drilling
Earth leakage Circuit Breakers
G-TWIN series
External accessories
2-ø4.5 mounting hole
Padlock
of breaker
of slider
C
L
C
L
(Not supplied)
26
35
9
13
11
56
100
A
68
BC
88
C
LC
L
C
LC
L
Breaker mounting hole
Breaker mounting hole
Breaker Breaker
BreakerBreaker
2-ø4.5 or M4
2-ø4.5 or M4
of breaker
C
L
of breaker
C
L
BZ6M110C2
BZ6M110C3
45
68
100
110
68
45
85
C
LC
L
C
LC
L
Type
BZ6M110C2
BZ6M110C3
Dimensions, mm
A
85
110
B
42.5
55
C
83
108
Mass (kg)
0.11
0.12
Notes: • BZ6M110C2 is not available for padlock.
• Applicable padlock(ø3.5) dimensions, mm
• External installation forms F and R are not applicable to the ELCB
on the left of the diagram.
   9.5
20
12
ø3.5 ø3.5
14
25
14
07/72 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
n Dimensions, mm
• 125AF to 250AF
ON
76
145
Fig.1
M4 or ø5
M4 or ø5 M4 or ø5
M4 or ø5
2-M4 or ø4.5
2-M4 or ø4.5 2-M4 or ø4.5
2-M4 or ø4.5
D
Breaker
Breaker
Breaker
Breaker
Breaker
Breaker
Breaker
Breaker
Mounting screw: M4 x 10 (x2)
11.7
25
15
15
35
ø19
165
145
87
37.6
70.6
93
A
P
NB
L
C
L of slider
C
Padlock
(Not supplied)
L of breaker
C
L of breaker
C
L of breaker
C
L of breaker
C
L of breaker
C
L
CL
C
L
C
L
CL
C
76
C
145
Fig.2
D
L
CL
C
76
C
145
Fig.3
D
L
CL
C
76
C
145
Fig.4
D
L
Handle
CL
Handle
C
Panel drilling
Type Dimensions, mm Panel Drilling Mass(Kg)
P N A B C D
BW9M1CA-2 90 88 150 60 132 Fig.1
BW9M1CA-3 120 118 210 90 30 132 Fig.2
BW9M1CA-4 150 148 270 102 30 132 Fig.4
BW9M1GA-3 135 133 240 105 35 126 Fig.3
BW9M1GA-4 170 168 310 140 35 126 Fig.4
Notes: The dimensions and Breaker mounting holes for back surface mounting are different from those given above. Inquire for details.
• If a padlock is required, use a commercially available padlock with the dimensions shown in the diagram at the right.
• External installation forms F and R are not applicable to the ELCB on the left of the diagram.
9.5
20
12
ø3.5
07/73
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
n Dimensions, mm
• 400AF to 800AF
Earth leakage Circuit Breakers
G-TWIN series
External accessories
D
B
A
CA′
K
J′J′ M6orø7
HJ J
Handle
C
L
Breaker Breaker
GL
F
E
Paneldrilling
Mountingscrew
Lofslider
CLofslider
C
Lofhandle
CLofhandle
C
Padlock
(Notsupplied)
Lofbreaker
CLofbreaker
C
Type Dimensions, mm Mass(Kg)
A (A') B C D E F G H J (J') K L
BW9M1HA-3 355 (70) 257 215 20 94.5 132.5 54.5 171 44 (70) 215 38
BW9M1HA-4 470 (140) 257 260 20 94.5 132.5 54.5 216 44 (140) 215 38
BW9M1JA-3 500 (105) 275 290 20 94.5 132.5 54.5 220 70 (105) 243 38
9.5
20
12
ø3.5
Notes: The dimensions and Breaker mounting holes for back surface mounting are different from those given above. Inquire for details.
• If a padlock is required, use a commercially available padlock with the dimensions shown in the diagram at the right.
• External installation forms F and R are not applicable to the ELCB on the left of the diagram.
07/74 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
N type handles
BW9N0CA
N type handles
BW9V0CA
V type handle
External operating handles
n Description
Molded case circuit breaker handles are
generally directly manual-operated but
when mounted in motor control centers
or on control panels they are sometimes
required to be operated externally. To
meet such applications FUJI offers the
following three types of handles.
N type handle
This type has a knob handle directly
attached to the breaker. It is easily
fitted by cutting a hole in the panel,
which is provided with a door interlock.
They may be fitted to all breakers up to
800 ampere frame sizes.
Conformed to EN60947-1 isolation
function.
Available for EN60204-1 power breaking
device.
Conformed to UL489 (File No.E93289)
V type handle
The V type handle may be fitted to
breakers of up to 800AF.
A separately sold extension shaft
provides distance adjustment between
the handle and breaker.
Conformed to EN60947-1 isolation
function.
Available for EN60204-1 power breaking
device.
Conformed to UL489 (File No.E93289)
F type handle
The F type handle may be fitted to
breakers of 125 to 400AF.
It is a flange type handle, which is
commonly used in the North American
market.
The drive section of the breaker and
the external operating handle are
connected with an optional cable.
Positioning between the breaker and
the external operating handle is not
required.
Conformed to UL489 (File No.E93289)
V type handles
Breaker
Decorative plate
N type handle on
breaker
Breaker
V type handle on
panel
F type handles
07/75
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
N type handles
ELCB N type handle
EW32 BZ6N10D
EW50
EW63
EW100
EW125 BW9N0CA
EW160 BW9N0GA
EW250
EW400 BW9N0HA
EW630
EW800 BW9N0JA
V type handles
ELCB V type handle
EW32 BZ6V10D
EW50
EW63
EW100
EW125 BW9V0CA
EW160 BW9V0GA
EW250
EW400 BW9V0HA
EW630
EW800 BW9V0JA
V type handle
BW9V0CA –
Mounting ( For BZ6V10D, BW9V0HA,
BW9V0JA)
Blank: Front mounting, front connection
X: Front mounting, rear connection
P: Plug-in mounting
Basic type
Note:
To order a V handle for front-mounting rear connection breakers, add “-X” to the
type number; for plug-in mounting breakers, add “-P” to the type number.
n Type number nomenclature
F type handles
ELCB F type handle
EW125 BW9F0CA
EW250 BW9F0GA
EW400 BW9F0HA
• F type handle
BW9F0 A
Breaker type
C: EW125 U
G: EW250 U
H: EW400 U
Basic type
Cable (For F type)
BW9FW A – A
Cable length
15: 1.5m
20: 2.0m
30: 3.0m
Breaker type
C: EW125 U
G: EW250 U
H: EW400 U
Basic type
Terminal cover (For F type)
BW9FBT A – L3
Breaker type
C: EW125 U
G: EW250 U
H: EW400 U
Basic type
• N type handle
BW9N0CA –
Mounting ( For BZ6N10D, BW9N0HA,
BW9N0JA)
Blank: Front mounting, front connection
X: Front mounting, rear connection
P: Plug-in mounting
Basic type
07/76 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Notes: • The handle lock bars do not hold the entire door. Obtain a support bracket for the panel separately.
• Remove the handle lock bar before opening the door. (Turn the handle in the open direction.)
The lock bar will be damaged if the door is opened with force while the lock bar is engaged.
• Engage the door interlock securely before turning ON the power.
*1 The terminal cover will cover the mounting screws for the Breaker. When attaching the terminal
cover, a portion of the terminal cover will need to be removed.
Remove portion in the following diagram.
Earth leakage Circuit Breakers
G-TWIN series
External accessories
• BZ6N10D
• BW9N0CA, BW9N0GA
n Dimensions, mm
N type handle
Note: Align the center of the hole cut in the panel
with the center of the breaker handle.
Handle C/L
Door panel cutting
2P 3P 4P
4-ø15
78
78
ELCB
Handle
C/L
Handle
C/L
Max.65
52.5
H 50
108
105
ELCB
handle C/L
ELCB
Load
Line Panel
Dust proof packing(Optional)
Thickness:
1.2 to 3.2
L
C
L
C
ø
90
Install the hinge in the shaded area.
85
200 200
1 5 1
9 3
8 2
4
6 3
49
Padlock size
ø4 to ø8
Handle C/L
85
1 2
7
ELCB Handle
type Dust proof
packing Mounting
screw H (mm) Mass
(kg)
EW32 BZ6N10D Provided M4 x 85 103±2 0.47
EW50 BZ6N10D-X Provided Contact FUJI. 111±2
EW63 BZ6N10D-P 111±2
EW100
ELCB Handle
type Dust proof
packing Mounting
screw H (mm) Mass
(kg)
EW125 BW9N0CA BZ-NP-1C M4 x 85 103±2 0.56
EW160 BW9N0GA*1BZ-NP-1C M4 x 85 103±2 0.56
EW250
105
105
78
78
ø90
4-ø15
H49
38
75
50
85
104
16 23
2.5
12
62.5 148
17 23
110 200200
85
L
C
L
C
L
C
L
C
L
C
Note: Align the center of the hole cut in the panel
with the center of the breaker handle.
Door panel cutting
Install the hinge in the shaded area.
Load
Line Panel
Thickness:1.2 to 3.2
Padlock size ø4 to ø8
07/77
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
• BW9N0HA, BW9N0JA
Line
Panel thickness:
1.6-3.2
Install the door hinge in the shaded area.
112
112
Mounting screw
4-ø15
150
150 96 96 17
53 157±2
65
Panel
Lock plate
Padlock size ø4 to ø8
(Up to 2 ø8 padlocks can
be mounted.)
25
35 7.5
65 35
25
15
100 100
200 200
Decorative
plate
ø138
ELCB
handle C/L
ELCB
handle C/L
ELCB
handle C/L
Load
Handle C/L
Door panel cutting
Note: Align the center of the hole cut in the panel
with the center of the breaker handle.
X-type 169±2
P-type 171±2 400AF
174±2 630AF
219±2 800AF
ELCB Handle
type Dust proof
packing Mounting
screw Mass
(kg)
EW400 BW9N0HA
BW9N0HA-X
BW9N0HA-P
BZ-NP-2 M6 x 110
M6 x 115
Contact FUJI.
1.9
EW630
EW800 BW9N0JA
BW9N0JA-X
BW9N0JA-P
BZ-NP-2 M6 x 110
M6 x 115
Contact FUJI.
1.9
Earth leakage Circuit Breakers
G-TWIN series
External accessories
Notes: • The handle lock bars do not hold the entire door. Obtain a support bracket for the panel separately.
• Remove the handle lock bar before opening the door. (Turn the handle in the open direction.)
The lock bar will be damaged if the door is opened with force while the lock bar is engaged.
• Engage the door interlock securely before turning ON the power.
Not available for side mounting.
07/78 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
• BW6V10D
• BW9V0CA, BW9V0GA
Door panel cutting
Handle
C/L
4-ø15
ø90
ELCB
Handle C/L
78
78
Padlock size ø4 to ø8
Panel thickness:
1.2 to 3.2
ELCB
handle
C/L
Line
Load
Panel
Note: Align the center of the hole cut in the panel
with the center of the breaker handle.
Handle C/L
2P3P
Door hinge installation area
Optional shaft BZ6VS1D
X = H - 105 Install the door hinge in the shaded area.
113
113
62 H
38
50
60 200
75
2015
73 56
L
C
L
C
L
C
X
Door panel cutting
Handle
C/L
4-ø15
ø90
ELCB
Handle C/L
78
78
49
Padlock size ø4 to ø8
L
C
113
113 68
L
C
65 H
Panel thickness:
1.2 to 3.2
ELCB
handle
C/L
ELCB
Line
Load
Panel
Note: Align the center of the hole cut in the panel
with the center of the breaker handle.
Handle C/L
2P3P4P
Door hinge installation area
Optional shaft BW9VSG0
X = H - 95
Install the door hinge in the shaded area.
60
120 120
872
14
94
03
51
C/L
60
72
1
Shaft
Latch (included with the handle)
X
n Dimensions, mm
V type handle
07/79
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
Area in which the hinge
with H can be installed
H
Standard type
H
ELCB Handle type With the optional shaft (X=154) Mounting
screw Mass (kg)
EW32
EW50
EW63
EW100
EW125
EW160
EW250
BZ6V10D
BZ6V10D-X
BZ6V10D-P
BW9V0CA
BW9V0GA*1
105±2
113±2
113±2
105±2
105±2
Optional
shaft
BZ6VS1D
BW9VSG0
250±2
258±2
258±2
250±2
250±2
140 to 250
150 to 258
150 to 258
140 to 250
140 to 250
M4 x 80
Contact FUJI.
Contact FUJI.
M4 x 85
M4 x 85
0.64
0.64
0.64
0.67
0.67
Notes: • The handle lock bars do not hold the entire door. Obtain a support bracket for the panel separately.
• Remove the handle lock bar before opening the door. (Turn the handle in the open direction.)
The lock bar will be damaged if the door is opened with force while the lock bar is engaged.
• Engage the door interlock securely before turning ON the power.
Not available for side mounting.
*1 The terminal cover will cover the mounting screws for the Breaker. When attaching the terminal cover, a portion of the terminal cover will need to be removed.
Remove portion A in the following diagram.
07/80 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
• BW9V0HA, BW9V0JA
X
Optional dhaft (BZ-VS2)
55
100
H 63
10
200
OFF
30
Panel Decorative
plate
Mounting
screw
Load
Install the door hinge in the shaded area.
Line
150
150
150
Lock plate
Padlock size ø4 to ø8
(Up to 2 ø8 padlocks can
be mounted.)
ELCB
handle C/L
112
112
4-ø10
ø138
ELCB
handle C/L
ELCB
handle C/L
Panel thickness: 1.6-3.2
Door panel cutting
Note: Align the center of the hole cut in the panel
with the center of the breaker handle.
When using the BZ-VS2 extension
shaft to adjust dimension H, cut it
according to the equation below.
X=H−161.5
ELCB Handle
type Optional
shaft Standard type
HWith the optional shaft (X=154) Mass
(kg)
H Area in which the hinge
with H can be installed
EW400 BW9V0HA BZ-VS2 190±2 250±2 202 to 250 2.2
BW9V0HA-X 202±2 262±2 214 to 262
BW9V0HA-P 204±2 264±2 216 to 264
EW630 BW9V0JA 190±2 250±2 202 to 250
BW9V0JA-X 202±2 262±2 214 to 262
BW9V0JA-P 207±2 267±2 219 to 269
EW800 BW9V0JA 190±2 250±2 202 to 250
BW9V0JA-X 202±2 262±2 214 to 262
BW9V0JA-P 252±2 312±2 264 to 312
Notes: • The handle lock bars do not hold the entire door. Obtain a support bracket for the panel separately.
• Remove the handle lock bar before opening the door. (Turn the handle in the open direction.)
The lock bar will be damaged if the door is opened with force while the lock bar is engaged.
• Engage the door interlock securely before turning ON the power.
Not available for side mounting.
07/81
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
• BW9F0CA
n Dimensions, mm
F type handle
Terminal
cover Mounting screw
M4 x 90
Drive section Operation section
Insulation
barrier
Protection
cover
To operation section
Panel drilling
M4 or ø5
Handle
Panel
Panel
Cable
Release lever
Lock lever
Release screw
OFF lock
Concave for
ON lock*2
28 or more RESET
155
132
22
27.5
12.5
27.5
132
275
Max. 69
149
145
150˚
75
119
29
65
100 104
70
90
30
117
60
45
80 ON 27
29
57
57
13
2-ø7
R6.5
2-ø5.5
*1
This product consists of a drive section and an operation section.
The operation section can be mounted either to the right or to the left on the panel depending
on the mounting position of the release lever.
• For the OFF lock, 3 ø10 padlocks can be mounted; for the ON lock, 2 ø10 padlocks.
*1 Set the height to 20 or 30. Adjust the lock lever depending on the setting.
*2 The ON lock can be realized by additionally creating a concave for the ON lock.
Breaker
Breaker
Breaker
Breaker
• BW9F0GA Operation section Drive section
To operation section
Panel drilling
Handle
Panel
Mounting screw
M4 x 90 Panel
Cable
Release lever
Lock lever
Release screw
OFF lock
Concave for
ON lock*2
28 or more RESET
22
126
27.5
12.5
27.5
132
275
165 88
Max. 69
149
145
150˚
75
119
29
60
45
80 ON 27
29
57
104 115 70
117 90
Insulation
barrier
Protection
cover 57
35
M4 or ø5
13
2-ø7
R6.5
2-ø5.5
*1
This product consists of a drive section and an operation section.
The operation section can be mounted either to the right or to the left on the panel depending
on the mounting position of the release lever.
• For the OFF lock, 3 ø10 padlocks can be mounted; for the ON lock, 2 ø10 padlocks.
*1 Set the height to 20 or 30. Adjust the lock lever depending on the setting.
*2 The ON lock can be realized by additionally creating a concave for the ON lock.
Breaker
Breaker
Breaker
Breaker
07/82 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
• BW9F0HA
Mounting screw
M6 x 110
Operation section Drive section
To operation section
Panel drilling
Handle
Panel
Panel
Cable
Release lever
Lock lever
Release screw
OFF lock
Concave for
ON lock*2
28 or more RESET
22
214 to 216
27.5
12.5
27.5
132
275
275
Max. 69
149
145
150˚
75
119
29
60
45
80 ON 27
29
57
155
108
190
Protection
cover
Breaker
Breaker
Breaker
Breaker
Insulation
barrier
171
140
57
44 M6 or ø7
13
2-ø7
R6.5
2-ø5.5
*1
This product consists of a drive section and an operation section.
The operation section can be mounted either to the right or to the left on the panel depending
on the mounting position of the release lever.
• For the OFF lock, 3 ø10 padlocks can be mounted; for the ON lock, 2 ø10 padlocks.
*
1
Set the height to 20 or 30. Adjust the lock lever depending on the setting.
*
2
The ON lock can be realized by additionally creating a concave for the ON lock.
ELCB * Handle type Cable Terminal cover
Type Length (m)
EW125JAGU-3P
EW125RAGU-3P BW9F0CA BW9FWCA-15A
BW9FWCA-20A
BW9FWCA-30A
1.5
2.0
3.0
BW9FBTCA-L3
EW250JAGU-3P
EW250RAGU-3P BW9F0GA BW9FWGA-15A
BW9FWGA-20A
BW9FWGA-30A
1.5
2.0
3.0
BW9FBTGA-L3
EW400SAGU-3P
EW400RAGU-3P
EW400HAGU-3P
BW9F0HA BW9FWHA-15A
BW9FWHA-20A
BW9FWHA-30A
1.5
2.0
3.0
BW9FBTHA-L3
Note: * Not available for BW125JAGU-2P
07/83
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
Steel enclosures
n Description
Steel enclosures are available in three types — two with V-type
handle which allows the operation from the outside and other
with the operating handle of the breaker extending from it to
allow it to be directly switched ON or OFF from outside the
enclosure.
Enclosures with V-type handles are provided with a door
interlocking mechanism which prevents the door from being
opened in the ON condition.
Knockout holes for wiring use are provided as shown in the
diagram. Standard Dustproof
AF96-175 Rainproof
CP97-2636
n Ordering information
Specify the following:
1. Type number of enclosures
n Type of enclosures
ELCB Enclosure
Standard *1With V-type handle
Dust-proof *1*2Rain-proof *1*2
EW32
EW50
EW63
BZ6C10C2 *3
BZ6C10C3
BW9UVBA-3A *3BW9UWBA-3A *3
EW100 BZ6C25C2 *3
BZ6C25C3 *3
BW9UVBA-3B *3BW9UWBA-3B *3
EW125 BW9UCCA-2
BW9UCCA-3
BW9UVCA-3 BW9UWCA-3
EW250 BW9UCGA-3 BW9UVGA-3 BW9UWGA-3
EW400 BZ-C60B BW9UVHA-3 BW9UWHA-3
EW630
EW800 BZ-C70B BW9UVJA-3
*1 No models are available for four-pole products.
*2 The appearance of dust-proof and rain-proof models differs from the photograph (400A frames and higher).
*3 Combination with external accessories(R) is not possible.
07/84 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
Fig.1 Standard Fig.2 With V type handle
BW9UVBA-3A, BW9UVBA-3B
BW9UVCA-3, BW9UVGA-3
Fig3. With V type handle
BW9UVHA-3, BW9UVJA-3
n Dimensions, mm
n Connection method diagrams
C
L
C
L
ELCB
E
A
J
R3.5(ø7)
R6.5(ø13)
C
Mounting hole
ø7
Neutral
terminal
(Special
order)
øL lead hole
Earth terminal
M6
H
J G
F
B
9
E
F
B
A
O
F
F
T
R
I
P
O
N
R
E
S
E
T
Mounting hole P
C
D
4-L lead hole
Earth terminal M6
2-K lead hole
G
H
C
L
C
L
2-K lead hole
4-L lead hole
H
Earth terminal M6
G
Mounting hole P
F
B
A
ED
C
LINE LINE LOAD
LOAD
a b
LINE
LOAD
c
Type Connection Fig. A B C D E F G H J K L P
BZ6C10C2 a, b, c 1 135 225 95 90 170 65 40 25 ø35, ø22
BZ6C10C3
BZ6C25C3 200 320 95 120 240 80 40 25 ø45, ø30
BW9UCCA-3 200 320 103 120 240 80 40 25 ø45, ø30
BW9UCGA-3 360 280 45 ø55, ø40
BZ-C60B 400 750 175 300 650 200 80 100 ø106, ø78, ø63
BZ-C70B
BW9UVBA-3A 2 180 300 114 178.5 100 220 70 40 ø28, ø35, ø43 ø7
BW9UVBA-3B 250 400 142 206.5 170 320 110 50 ø23 ø35, ø52, ø63 ø9
BW9UVCA-3 207
BW9UVGA-3
BW9UVHA-3 3 400 750 206 269 300 650 200 80 ø28 ø63, ø78, ø106 ø12
BW9UVJA-3
07/85
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
Type No. of poles ELCB Dimensions (mm) Packing
quantity
Appearance
Transparent Gray A B C
BW9BTAA-L2 BW9BTAA-L2W 2 EW32 -2P
EW50 -2P
50 40 53 2
• Preventing exposure of live section
when amplifier's terminals are connected
• Snap-on mounting
BW9BTAA-L3 BW9BTAA-L3W 2, 3 EW32 -3P
EW50 -3P
EW63 -3P
EW100 -2P
EW100 -3P
75 40 53 2
BW9BTCA-L3 BW9BTCA-L3W 3 EW125 -3P 90 40 66.5 2
BW9BTCA-C3
(For Flat terminal)
3 EW125 -3P 90 60 66.5 2
BW9BTCA-L4 BW9BTCA-L4W 4 EW125 -4P 120 40 66.5 2
BW9BTGA-L3 *1BW9BTGA-L3W *13 EW160 -3P
EW250 -3P
105 50 66.5 2
BW9BTGA-L4 *1BW9BTGA-L4W *14 EW160 -4P
EW250 -4P
140 50 66.5 2
BW9BTGA-C3
(For Flat terminal)
3 BW250 -3P 105 75 66.5 2
BW9BTHA-L3 *2BW9BTHA-L3W *13 EW400 -3P 172 110 98 2
BW9BTHA-L4 *24 EW400 -4P 220 110 98 2
BW9BTJA-L3 BW9BTJA-L3W 3 EW630 -3P
EW800 -3P
230 135 97.5 2
Terminal covers
n Description
These terminal covers are used as guards to prevent
accidental touch with live line terminations.
These terminal covers can be fitted to either line or load side.
l Up to 400AF
Short type: BW9BT A-S
• Snap-on fitting
Long type: BW9BT A-L
Crimp connection use
l 630, 800AF
Long type: BW9BTJA-L
Transparent
Short type Long type
Long type
MCCB
C
B
A
Type No. of poles ELCB Dimensions (mm) Packing
quantity
Appearance
Transparent Gray A B C
BW9BTAA-S2 BW9BTAA-S2W 2 EW32 -2P
EW50 -2P
50 10 53 2
• Preventing exposure of live section
when amplifier's terminals are connected
• Snap-on mounting
BW9BTAA-S3 BW9BTAA-S3W 2, 3 EW32 -3P
EW50 -3P
EW63 -3P
EW100 -2P
EW100 -3P
75 10 53 2
BW9BTCA-S3P20
BW9BTCA-S3WP20
3 EW125 -3P 90 8 66.5 2
BW9BTCA-S4P20
BW9BTCA-S4WP20
4 EW125 -4P 120 8 66.5 2
BW9BTGA-S3P20
*1
BW9BTGA-S3WP20
*13 EW160 -3P
EW250 -3P
105 8 66.5 2
BW9BTGA-S4P20
*1
BW9BTGA-S4WP20
*14 EW160 -4P
EW250 -4P
140 8 66.5 2
BW9BTHA-S3 *3BW9BTHA-S3W *22, 3 EW400 -2P
EW400 -3P
140 65 98 2
BW9BTHA-S4 *3BW9BTHA-S4W *24 EW400 -4P 185 65 98 2
Short type
MCCB
C
B
A
Notes: • A gray-white terminal cover comes standard with the Global Series 125AF and 250AF.
*1 When using the external operating handle, part of the terminal cover ( ) must be cut away.
*2 Crimp terminals for 325 mm2 are not available.
*3 This type of cover can be mounted on the 400AF when flat terminals are not used.
07/86 Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth leakage Circuit Breakers
G-TWIN series
External accessories
Insulation barriers
n Description
The interphase barriers are provided on frame size of 32AF to
800AF breakers for front mounting. The barriers are installed
in the molded slots between terminals.
The earth barrier is used to increase the insulation with the
mounting plate surface when two crimp terminals are wired.
Installation of these barriers after wiring is possible even when
an external accessory is installed.
Interphase barrier Earth barrier
Interphase barrier
ELCB Interphase barrier
Type Dimensions (mm) Packing
quantity Mass
(g)
A B
EW32
EW50
EW63
EW100
BZ6B10C 50 49 4 23
EW125 BW9BPCA 50 60 2 15
EW160
EW250 BW9BPGA 80 60 2 25
EW400
EW630
EW800
B-43A 105 95 4 130
Earth barrier
ELCB Earth barrier
Type Dimensions (mm) Packing
quantity Mass
(g)
A B
EW32 -2P
EW50 -2P BZ6BL10C2 100
(50, 75)*143
(30)*11 33
EW32 -3P
EW50 -3P
EW63 -3P
EW100 -2P
EW100 -3P
BZ6BL10C3 125
(75, 100)*143
(30)*11 41
Interphase barrier
A
B
Breaker
Breaker
B
A
Earth barrier
Note: *1 Can be cut to dimensions
07/87
07
Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Padlocking device
• Cap type Q1
Q1: BZ6L10CA (OFF-locking Padlocking device)
Padlocking device
• Cap type Q1,QN
• Plate type Q2
Padlocking device and handle locking cover
n Description
• Padlocking device
These padlocking device lock the Breaker handle in the OFF position.
Use a commercially available padlock with a shackle diameter of 3.5 to
5mm (5mm for the BZ6L10CA).
• Handle locking covers (Order Separately)
These simple handle locking covers can be easily installed by the user.
Tripping is possible while the Breaker is locked ON. Handle locking cover
Handle locking cover
ELCB Padlocking device Handle locking cover
Q1: Cap type QN: Scissors type Q2: Plate type
EW32 BZ6L10CA ▲*1*3BZ6L10C
EW50
EW63
EW100
EW125 BW9Q1CA *4BW9Q2CA BW9L1CA
EW160 BW9Q2GA
EW250
EW400 ▲*1BW9QNHA *2BW9Q2HA BW9L1HA
EW630 BW9Q2JA
EW800
Earth leakage Circuit Breakers
G-TWIN series
External accessories
Notes:
*1 Specify Locks when ordering the Breaker. (: Factory-mounted)
*2 ON and OFF locking is possible.
*3 If a padlock is required, use a commercially available padlock with the dimensions shown in the diagram at the right.
*4 Three padlocks with shackles from 3.5 to 8 mm in diameter can be attached.
ø5
35
(20)
9.5
C
LC
L
20
95
ELCB
21.8
5
3.5 7.8
3.5
ø3.5
12
46
22
OFF
3-ø4.5
29.566
Padlock
Padlock
(Obtain a commercially available lock
conforming to the diagram at the right.)