aHWS61
・Allspecificationsaresubjecttochangewithoutnotice.
Instruction Manual
HWS HWS HD HWS ME HWS-P
HWS 1500
InputVoltageRange
Input voltagerangeissinglephase 85−265VAC(47−
63Hz).Inputvoltage,whichisoutofspecification,may
causeunitdamage.Ratedinputvoltagerangefixdur-
ingsafetystandardapplicationisfrom100Vto240VAC
(50/60Hz).
Whileapplyinginputvoltagefrom85VACto90VAC,out-
putloadcurrentderatingisrequired.
OutputVoltageRange
Outputvoltageissettotheratedvalueatshipping.V.ADJ
trimmeronthefrontpanelsideisusetoadjusttheoutput
voltagewithintherangespecified.Outputvoltagetrimming
rangeiswithin-20% −+20%oftheratedoutputvolt-
age(48V,60VModel:-20% −+10%).Turnthetrimmer
clockwisetoincreaseoutputvoltage.Takenotewhenthe
outputvoltageisincreasedexcessivelyovervoltagepro-
tection(OVP)functionmaytriggerandoutputvoltagewill
shutdown.
Usetheoutputpowerofthepowersupplybelowtherated
outputpowervaluewhenyouraisetheoutputvoltage.
OverVoltageProtection(OVP)
TheOVPfunction(Invertershutdownmethod, manualreset
type)isprovided.OVPfunctionoperateswithin125-145%of
theratedDCoutputvoltagevaluevalue(3-7Vmodel:125-
140%,36Vtype:125-138%,48Vtype:115-135,60Vmodel:
115-125%),andtheoutputwillbeshutdownwhenOVPfunc-
tiontriggers. When OVPfunctionoperates,theinputpoweris
cutoffforafewminutes,andthenpowerisre-inputorremote
ON/OFFcontrolsignalshallbeinputforrecoveryoftheoutput.
OVPvalueisfixedandcannotbeadjusted.
OverCurrentProtection(OCP)
TheOCP function(Constantcurrentlimiting,Timedelay
shutdowntype)isprovided.OCPfunctionoperateswhen
theoutputcurrentexceeds105%ofmaximumDCoutput
currentspecificationandtheovercurrentorshortcircuit
conditioncontinues 5-second or more,theoutput willbe
shutdown.WhentheOCPistriggered,theinputpower
iscutoffforafewminutes,andthenpowerisre-inputor
remoteON/OFFcontrolsignalshould be inputforrecov-
eryoftheoutput.TheOCPsettingisfixedandnottobe
adjustedexternally.
OverTemperatureProtection(OTP)
Overtemperatureprotectionfunction(manualresettype)
isprovided.Whenambientorinternaltemperaturerises
abnormally,OTPwillshutdowntheoutput.WhenOTPis
triggered,inputpoweriscutoffandallowsufficientcooling
toresettheOTP function.Thenpowerisre-inputorre-
moteON/OFFcontrolsignalshouldbeinputforrecovery
oftheoutput.
LowOutputDetectionCircuit(PF
)
Lowoutputvoltagedetectioncircuitisprovided.Power
Failsignal(PFsignal)willoutputwhenoutputvoltagede-
creasebyeitherthedroporbrownoutoftheinputvoltage
orOCP,OVPandOTPfunctionoperation.PFsignalwill
turnHighleveltoindicatetheabnormalstatusofthe
powersupplywhentheoutputvoltagedecreaseto80%
oftheoutputvoltagesettingvalue.However,thereisa
possibilitythatPFsignalmaynotoutputduringparallelop-
eration.ThePFsignalcircuitisinsulatedfromthepower
supplyinputandoutputcircuitanditisanopencollector.
TOGterminalisgroundforPFterminal.
WhentheBuilt-inFanMotorofthispowersupplyunit
stops,PFsignalwillturntoHandtheoutputpowerwill
shutdown.TheBuilt-inFanMotorisacomponentwith
lifetime.Werecommendaperiodicreplacement.Please
contactoursalesoffice.Replacementisatcustomersex-
penses.
RemoteSensing(+S,-Sterminal)
Remotesensingfunctionis providedto compensatefor
voltagedropacrossthewiringfromthepowersupplyout-
putterminalstothe loadinput terminals.Connect+S
terminalto+terminaloftheloadand-Sterminalto-
terminaloftheloadwithsensingwires.Thetotallinevolt-
agedrop(+sidelineand-sideline)shallbelessthan0.3V.
Incasethatsensinglineistoolong,itisnecessarytoput
anelectrolyticcapacitoracrosstheloadterminals.
Pleasetakenotethat theelectrolytic capacitorhasgen-
erationofheatetc.donebytheripplecurrentdependingon
connectedload.Therefore,theelectrolyticcapacitormust
havearipplecurrent allowancehigher thentheoutput
ripplecurrent.IfCN01(orCN02)isinuse,terminal+S,-S
forCN02(orCN01)mustbeinopencondition.
+S
+
-
-
S
+
+
-
Whenthefunctionofremotesensingisnotinused,connect+S
terminalto+Vterminal,and‒Sterminalto‒Vterminalbytheat-
tachmentconnector.
Ifremotesensingterminalsareopened,thestabilityandtheac-
curacyoftheoutputdeteriorate.Therefore,terminal+S,-Smust
beconnected.
RemoteON/OFFControl
RemoteON/OFFcontrolis provided.Output canbere-
motelyswitchONand OFFby usingCNTterminaland
TOGterminaleventhough inputis connected.Theout-
putisturnedto ONwhen TOGandCNTterminalsare
shortedandoutputisturnedtoOFFwhentheseterminals
areopened.Whenthefunctionisnotused,connectTOG
andCNTterminalswith shortpiece. Thestandardsfor
thisfunctionare asfollows.TOGterminalisgroundfor
CNTterminal.
TOG
CNT
Sinkcurrent:3.5mA
Relay
Transistor
TTL,
andetc.
TheModeofcontrol
CNTLevelforTOGTerminal Output Built-inFanMotor
ShortorL(0−0.8V) ON Rotate
OpenorH(2.4−12V) OFF Stop
1) TTLcompatible.Themaximuminputvoltageto CNT
terminalis12V,and themaximum allowablereverse
voltageis-1V.The sinkcurrent ofCNTterminalis
3.5mA.
2)OutputON/OFFcontrolcanbeenable bya switch,
relayoratransistor ON/OFF.When CNTterminal−
TOGterminalisshortedpowersupplyisturnON,and
whenCNTterminal−TOGterminal isopened power
supplyisturnOFF.
3) RemoteON/OFFcontrolcircuitisisolatedfrom the
inputandoutputcircuitofpowersupply.
Itispossibleto useit regardlessofthepositiveand
negativeofthepowersupplyoutput.
2.FunctionsandPrecautions
TOG