Product data sheet Characteristics XPSMC16Z safety controller XPS-MC - 24 V DC - 16 input 30 LEDs signalling Commercial Status Commercialised Range of product Preventa Safety automation Product or component type Configurable safety controller Safety module name XPSMC Safety use category SIL 3 maximum conforming to IEC 61508 PLE maximum conforming to EN/ISO 13849-1 Category 4 maximum conforming to EN 954-1/EN/ ISO 13849-1 Type of start Configurable Standards EN 1760-1/ISO 13856-1 EN 574/ISO 13851 EN 954-1/EN/ISO 13849-1 EN/IEC 60204-1 EN/IEC 60947-5-1 EN/IEC 61496-1 IEC 61508 Product certifications CSA TUV UL [Us] rated supply voltage 24 V DC - 20...20 % Number of inputs 16 Communication port protocol Modbus with 1 RJ45 port(s), serial link, transmission rate: 1200 bps, 2400 bps, 4800 bps, 9600 bps or 19200 bps Safety level Can reach SIL 3 conforming to IEC 61508 Can reach PL e/category 4 conforming to EN 954-1/ EN/ISO 13849-1 Complementary Function of module Two-hand control (category 3) conforming to EN 574/ISO 13851 Light curtain monitoring (category 4) conforming to EN/IEC 61496 Zero speed detection Shaft/Chain breaking monitor Safety time delays Safety mat monitoring Position selector Muting function of light curtains Monitoring safety stop at top dead centre on eccentric press Magnetic switch monitoring Hydraulic press Guard monitoring with 1 or 2 limit switches Guard monitoring for injection presses and blowing machines Foot switch monitoring Enabling switch monitoring, 2 or 3 contacts Emergency stop monitoring, with or without time delay, 1 or 2-channel wiring Eccentric press Dynamic monitoring of hydraulic valves on linear presses Synchronisation time between inputs Depending on configuration selected Power consumption 12 W Input protection type External fuse 16 A [Uc] control circuit voltage 28.8 V Line resistance 100 Ohm, cable length: <= 2000 m Output type Solid state, 6 circuit(s), volt-free 2 relays, 2 NO contacts (4 NO total) circuit(s) Breaking capacity C300: inrush 1800 VA AC-15 for relay output C300: holding 180 VA AC-15 for relay output Jan 23, 2014 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Main Breaking capacity 1.5 A/24 V - L/R = 50 ms, DC-13 for relay output 2 A/24 V for static output circuit Output thermal current 6 A for 1 output and 2 A for the other for relay output 4 A for both outputs simultaneously [Ith] conventional free air thermal current <= 6.5 A for static output circuit <= 16 A for relay output Associated fuse rating 6 A fast blow for relay output 4 A gL for relay output 16 A gL for power supply Minimum output current 10 mA for relay output Minimum output voltage 17 V for relay output Response time Configurable : 20 ms or 30 ms with software XPSMCWIN [Ui] rated insulation voltage 300 V, degree of pollution 2 conforming to IEC 60647-5-1, DIN VDE 0110 part 1 [Uimp] rated impulse withstand voltage 4 kV overvoltage category III conforming to IEC 60647-5-1, DIN VDE 0110 part 1 Method of access Slave Exchange size 14 words Number of addresses 1...247 for Modbus Parity Odd for Modbus No for Modbus Even for Modbus Data format RTU (Remote Terminal Unit) mode 2 stop bits without parity 1 stop bit even or odd 1 start bit/8 data bits Supported modbus function 03: information and errors 02: 32-bit input data/8-bit output data 01: 8-bit output data/32-bit input data Local signalling 30 LEDs Mounting support Mounting plate Depth 153 mm Height 151.5 mm Width 74 mm Product weight 0.82 kg Environment IP degree of protection IP20 conforming to EN/IEC 60529 Ambient air temperature for operation -10...55 C Ambient air temperature for storage -25...85 C Contractual warranty Period 2 18 months Product data sheet Dimensions Drawings XPSMC16Z Dimensions 1 When using XPSMCTS* connectors this dimension is 153 mm (6.02 in) When using XPSMCTC* connectors this dimension is 151,5 mm (5.96 in) 3 Product data sheet Mounting and Clearance Installation Metal adaptor for fixing on metal: DIN rail 35 mm/1.38 in. 4 XPSMC16Z Product data sheet Connections and Schema XPSMC16Z Wiring Diagrams Refer to the Instruction Sheet To download the instruction sheet, follow below procedure: 1 2 Click on Download & Documents. Click on Instruction sheet. 5 Product data sheet Technical Description XPSMC16Z Safety Functions Emergency stop monitoring with time delay: 1 channel wiring, with automatic start. 2 channel wiring, with start button. Emergency stop monitoring without time delay: 1 channel wiring, with automatic start. 2 channel wiring, with start button. Two-hand control. Guard monitoring: with 1 limit switch. with 2 limit switches. with 2 limit switches, with guard locking. Guard monitoring for injection presses and blowing machines. Magnetic switch monitoring. Sensing mat monitoring. Light curtains monitoring: Relay output type. Solid-state output type. "Muting" function for light curtains. Zero speed detection. Dynamic monitoring of hydraulic valves on linear presses. 6 Safety time delays. Monitoring safety stop at top dead centre on eccentric press. Hydraulic press. Eccentric press. Enabling switching monitoring: 2 contact type. 3 contact type. Other functions: Foot switch monitoring Chain shaft breakage monitoring Position selector 7