Important Note
This supplement contains important information. The statements made take precedence over those in
the operating instructions and online help.
Please read this supplement carefully, it contains helpful information.
SIMATIC HMI
Panel PC Ex
Thin Client Ex
Notes
Supplement to operating instructions
Edition 02/2013
This supplement is valid for products with following order numbers:
SIMATIC HMI Panel PC Ex 6AV7200-1
SIMATIC HMI Thin Client Ex 6AV7200-0…
Supplement to operating instructions Edition 02/2013
2/52 A5E02338654-01
Please follow the guidelines mentioned in the manual!
Safety Guidelines Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to
prevent damage to property.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning
and operation of a device/system may only be performed by qualified personnel. Within the context of the
safety notes in this documentation qualified persons are defined as persons who are authorized to
commission, ground and label devices, systems and circuits in accordance with established safety
practices and standards.
Prescribed Usage
Note the following:
WARNING
This device may only be used for the applications described in the catalog or the technical description
and only in connection with devices or components from other manufacturers which have been approved
or recommended by Siemens. Correct, reliable operation of the product requires proper transport,
storage, positioning and assembly as well as careful operation and maintenance.
Trademarks
The trademarks in this publication may be trademarks whose use by third parties for their own purposes
could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However,
the information in this publication is reviewed regularly and any necessary corrections are included in
subsequent editions.
Supplement to operating instructions Edition 02/2013
3/52 A5E02338654-01
Service and support
Local information
If you have questions about the products described in this document, you can find help
at: http://www.siemens.com/automation/partner
Technical documentation for SIMATIC products
Further documentation for SIMATIC products and systems can be found at:
http://www.siemens.com/simatic-tech-doku-portal
Easy Shopping at the Mall
Catalog & online ordering system http://www.siemens.com/automation/mall
Training
All the training options are listed at: http://www.siemens.com/sitrain
Find a contact at: Phone: +49(911) 895-3200
Technical support
Tel +49 (0)911 895 7222
Fax +49 (0)911 895 7223
http://www.siemens.com/automation/csi/service
A Web form for Support Request can be found at:
http://www.siemens.com/automation/support-request
When you contact the customer support, please have the following information for the
technician on hand:
● BIOS version
● Order No. (MLFB) of the device
● Installed additional software
● Installed additional hardware
Online support
Information about the product, Support and Service, right through to the Technical
Forum,
can be found at: http://www.siemens.com/automation/service&support
After-sales information system for SIMATIC PC / PG
Information about contacts, drivers, and BIOS updates, FAQs and Customer Support
can be found at: http://www.siemens.com/asis
Supplement to operating instructions Edition 02/2013
4/52 A5E02338654-01
Notice to device designation
Panel PC Ex devices
The table below lists the Panel PC Ex devices together with their marking on the type plate and
the Operating Instructions.
MLFB
Designation Siemens
Device designation
(includes)
6AV720 0-1abcdx
a = A Panel PC Ex, Zone 2, 15“
MT-436-A-xx-TFT-xx
a = B Panel PC Ex, Zone 2, 19“
MT-456-A-xx-TFT-xx
a = D Panel PC Ex, Zone 1, 15“
ET-436-A-xx-TFT-xx
a = E Panel PC Ex, Zone 1, 19“
ET-456-A-xx-TFT-xx
a = J Panel PC Ex, Zone 2, 15“, SR
MT-436-A-xx-SR-xx
a = K Panel PC Ex, Zone 1, 15, SR
ET-436-A-xx-SR-xx
6AV720 0-1abcdx
b = A 10/100Base-TX
xx-4x6-A-TX-xx
b = B 100Base-FX
xx-4x6-A-FX-xx
6AV720 0-1abcdx
c = 1 CF 4GB, 1GB RAM
c = 2 CF 16GB, 1GB RAM
c = 3 HDD 100GB, 1GB RAM
c = 4 CF 4GB, 2GB RAM
c = 5 CF 16GB, 2GB RAM
c = 6 HDD 100GB, 2GB RAM
xx-4x6-A-xx-R1-4GB-xx
xx-4x6-A-xx-R1-16GB-xx
xx-4x6-A-xx-R1-100GB-xx
xx-4x6-A-xx-R2-4GB-xx
xx-4x6-A-xx-R2-16GB-xx
xx-4x6-A-xx-R2-100GB-xx
6AV720 0-1abcdx
d = 1 Windows XPe
d = 3 Windows XP Pro
d = 4 Windows 7 Ultimate
xx-4x6-A-xx-XPe
xx-4x6-A-xx-XPp
xx-4x6-A-xx-7U
6AV7675-0PX00-0AA0
Ethernet Switch
SK-KJ1740
The language sets of Windows XP Embedded contains the following languages:
Windows XPe set 1
English
German
French
Italian
Spanish
Portugese / Portugal
Portugese / Brazil
Dutch
Danish
Swedish
Norwegian
Finnish
Greek
Hungarian
Czech
Polish
Russian
Turkish
Hebrew (right-to-left layout)
Arabic (right-to-left layout)
Chinese (Traditional)
Chinese (Simplified)
Japanese
Korean
Notice to device designation
Thin Client Ex devices
The table below lists the Thin Client Ex devices together with their marking on the type plate
and the Operating Instructions.
MLFB
Designation Siemens
6AV720 0-0ab00xx
a = A Thin Client Ex, Zone 2, 15“
a = B Thin Client Ex, Zone 2, 19
a = D Thin Client Ex, Zone 1, 15“
a = E Thin Client Ex, Zone 1, 19“
a = G Thin Client Ex, Zone 2, 15“, SR
a = H Thin Client Ex, Zone 1, 15“, SR
6AV720 0-0ab00xx
b = A 10/100Base-TX
b = B 100Base-FX
6AV7675-0EX00-0AA0
Digital KVM-Box
6AV7675-0PX00-0AA0
Ethernet Switch
Supplement to operating instructions Edition 02/2013
6/52 A5E02338654-01
Note on device combinations
If a Panel PC Ex / Thin Client Ex device is installed inside a control cabinet or an enclosure
together with an additional heater, please note the special conditions that apply with regard to
the minimum temperature.
In general, the entire combination of devices is certified for a temperature range of
-30°C to +40°C.
If the temperature of the entire unit falls BELOW 20°C the Panel PC Ex / Thin Client Ex device
may only be switched on once the temperature has been raised back to -20°C or above.
This must be ensured by means of monitoring the temperature inside the control cabinet or
enclosure.
Alternatively, this can be ensured by pre-heating the unit with a type TEF 9201 100 W heater for
one and a half hours.
For the correct operation of all associated components please note, in addition to these
operating instructions, all other operating instructions enclosed in this delivery as well as
the operating instructions of the additional equipment to be connected.
Panel PC Ex
Thin Client Ex
heater
(z.B. TEF 9201)
-20°C … +40°C
-30°C … +40°C
-30°C … +40°C
Operating Instructions
MT-xx6-A
Series 400 Panel PC
Series 500 Thin Clients
(valid for HW Revision 3)
HW-Rev. MT-xx6-A-Fx: 03.00.11
HW-Rev. MT-xx6-A-Tx: 03.00.21
Operating Instructions Version: 03.00.01
Issue date: 12.02.2013
Operating Instructions MT-xx6-A Table of contents
Page 8 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
Table of contents
Description Page
Table of contents 8
1 Preface 10
2 Device function 10
2.1 MT-4x6-A (Series 400 Panel PC) 10
2.2 MT-5x6-A (Series 500 Thin Clients) 10
3 Technical Data 11
3.1 Additionally for MT-4x6-A (Panel PC) 12
4 Conformity to standards 13
5 Certificates 13
5.1 ATEX 13
5.2 IECEx 13
5.3 DNV 14
5.4 LR 14
5.5 GOST-R 14
5.6 CSA 14
5.7 UL-BR 14
6 Marking 15
7 Power supply 16
7.1 Operator interfaces 16
7.1.1 All circuits in zone 2 and 22 16
7.1.2 With circuits in zone 1 and 21 16
7.1.3 Operator interface terminals 16
7.1.3.1 Tightening torque 16
8 Permitted maximum values 17
8.1 External, non-intrinsically safe circuits 17
8.2 External inherently safe optical interface 17
8.3 External intrinsically safe circuits 18
9 Type code 20
9.1 MT-4x6-A (Panel PC) 20
9.2 MT-5x6-A (Thin Client) 21
10 Safety Advice 22
10.1 Installation and operation 22
10.2 Cautionary note 22
10.3 Special conditions 22
11 Installation 23
11.1 General information 23
11.2 MT-xx6-A 23
11.3 Installation via USB-interfaces 24
11.3.1 Software installation using a USB Flash-Drive 24
11.3.2 Software installation with external USB devices 24
11.4 USB interfaces 25
11.4.1 I.S. USB interfaces USB0, USB2 25
11.4.2 Ex-nA USB interfaces USB1, USB3 25
11.4.2.1 Connection variations for Ex-nA USB interfaces 25
Operating Instructions MT-xx6-A Table of contents
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 9 of 52
11.4.2.2 Connection terminal 26
12 Assembly and disassembly 27
12.1 General information 27
12.2 Cut-out MT-xx6-A 27
13 Operation 27
13.1 General information 27
13.2 Connections 28
13.2.1 Dip switch settings S3 and S4 29
13.2.2 Status LEDs 30
13.2.2.1 LEDs 30
14 Exicom-SHD-xxx hard disk 32
14.1 Installation of hard disk 32
14.1.1 Mechanical dimensions 32
14.2 Connections 33
14.2.1 Safety advice 33
14.3 Hard disk replacement 33
15 Maintenance, service 34
15.1 Servicing 34
15.2 Time function 34
16 Troubleshooting 35
17 Disposal 35
17.1.1 ROHS directive 2002/95/EC 35
17.1.2 China ROHS labelling 35
18 Front panel resistance 36
18.1 Design 36
18.2 Materials 36
18.3 Material properties 36
18.3.1 Entire device 37
18.3.2 Membrane top (Polyester) 37
18.3.3 Touch screen 39
18.3.4 Front panel seal 40
19 General Information 41
19.1 Keyboard features 41
19.2 MT-4x6-A (Panel PC) 42
19.2.1 Licensing issues 42
19.2.2 Recovery Stick 42
19.2.3 Back-up 42
19.2.4 Initial start-up 42
19.2.4.1 Initial start-up XP Pro/WIN 7 42
19.2.4.2 Initial start-up XP Embedded 42
19.2.5 Switching off/closing down 43
19.2.5.1 Note on XP Embedded 43
19.2.6 Installation Windows XP Professional 44
20 CSA Control Drawing 45
21 Declaration of EC conformity 48
22 Release notes 49
Operating Instructions MT-xx6-A Preface
Page 10 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
1 Preface
These Operating Instructions contain all aspects relevant to explosion protection for the
MT-xx6-A operator interfaces (series 400 Panel PC and series 500 Thin Clients). They also
contain information on the connection and installation of these devices. Please also refer to
additional documentation included in the delivery, such as the examination certificate and the
hardware manual, which contain further important information.
These operating instructions contain a joint description of the product lines Panel PC and Thin
Clients. Any differences between the three product lines will be explicitly mentioned and dealt
with. As a rule, though, the information contained in these operating instructions applies to all
models of the MT-xx6-A series.
The MT-xx6-A operator interfaces with display sizes of 26 cm/10.4", 38 cm/15" and 48 cm/19"
will be available in Hardware Revision 3.
For the correct operation of all associated components please note, in addition to these
operating instructions, all other operating instructions enclosed in this delivery as well as
the operating instructions of the additional equipment to be connected.
Please also note that all certificates of the operator interfaces can be found in a separate
document !
2 Device function
The MT-xx6-A operator interfaces are explosion-proof equipment for installation in hazardous
areas and can be installed in zones 2 and 22 with outputs for zones 1 and 21.
All devices have a modular structure, which makes changes and maintenance easy.
2.1 MT-4x6-A (Series 400 Panel PC)
The MT-4x6-A Panel PC devices are robust Panel PCs for hazardous areas. With their pre-
installed Windows operating systems they are ready to run straight away.
As a standard, all Panel PCs are equipped with a touch screen and several interfaces and are
based on the powerful ATOM technology (1.6 GHz clock frequency), making them the most
powerful devices on the market.
2.2 MT-5x6-A (Series 500 Thin Clients)
The MT-5x6-A Remote HMIs of the 500 series can be integrated into modern networks as Thin
Clients or with a KVM box via KVM-over-IP, thus providing ideal and flexible access options with
central data administration.
The MT-5x6 operator interfaces, which are used for operation and visualization, are located in
the hazardous area, whereas the PC that is operated is located in the safe area. Each
ERP/MES network can be accessed from each Thin Client via the IP address.
The Thin Client system supports both modern technologies such as DVI and USB and older
technologies such as VGA and PS/2.
Operating Instructions MT-xx6-A Technical Data
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 11 of 52
3 Technical Data
Function / Equipment
MT-406-A
MT-416-A
MT-436-A-(SR)
MT-536-A-(SR)
MT-456-A
MT-556-A
Display type
TFT Color,
16,777,216 Colors
Display size
26 cm (10.4")
38 cm (15")
48 cm (19")
Resolution in pixels
SVGA 800 x 600
XGA 1024 x 768
SXGA 1280 x 1024
Display
Touch screen on glass
Touch Screen
8-wire analogue resistive
normal
Sunlight readable
-
5-wire analogue
resistive
-
Backlight
LED background lighting
Service life of backlight
at +10°C
130,000 h
500,000 h
50,000 h
at +35°C
55,000 h
70,000 h
-
at +55°C
40,000 h
50,000 h
-
Brightness
normal
400 cd/m²
350 cd/m²
350 cd/m²
Sunlight readable
-
1000 cd/m²
-
Contrast
normal
min. 500:1, typ. 700:1
min. 400:1, typ. 700:1
1000:1
Sunlight readable
-
typ. 600:1
-
Keyboard
Polyester membrane on aluminium plate (> 1 million actions)
Functional keys
Soft keys
Cursor keys
Alphanumeric keys
System keys
12
10
Yes
12
14
12
no
no
no
no
8
no
no
no
no
8
no
no
no
no
Additional keyboard
optional 100 mA max. power consumption
105 Keys
or
107 keys with integrated trackball / joystick
Trackball/Joystick
optional
Power supply
Directly in the integrated connection box
Connections
via screw terminals, 2.5 mm² green (Ex-nA)
Power supply
24 VDC (20.4 to 28.8 VDC)
Power consumption [A]
1.2 A
max. operating voltage Um
30 VDC
MT-xx6-A
Real-time clock
Yes
Lithium battery and capacitor buffered, maintenance-free
> 5 years
at least 4 days
Data buffer
Battery
Capacitor
Status display LEDs
for activity on
- Solid state flash drive or HD
- Ethernet link
- COM 1 and COM 2
below the back cover
Interfaces
Ethernet
Either Tx or Fx
Copper (Tx)
10/100BaseTx, 10/100 Mbit (Ex-nA)
Optical fibre (Fx)
100BaseFx, 100 Mbit, inherently safe (Ex op is)
USB
2x Ex-nA; 2x Ex-ib/ic
PS/2
For external keyboard, mouse, trackball, joystick (all Ex-ib/ic)
Serial COM1
RS-232, RS-422, RS-485 (Ex-nA)
Fieldbus
not for Thin Client
Panel PC
MPI with MPI Box SSW7-HMI-RS-422
Audio
Line Out output (Ex-nA)
Data cable/-lenght
Copper (Tx)
up to 100 m via CAT5 installation cable AWG22
Optical fibre (Fx)
up to 2000 m via 62,5/125 μm (core-/external cross section) multi-mode optical fibre cable
Operating Instructions MT-xx6-A Technical Data
Page 12 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
Function / Equipment
MT-406-A
MT-416-A
MT-436-A-(SR)
MT-536-A-(SR)
MT-456-A
MT-556-A
Front plate
Polyester on seawater-proof aluminium with touch technology and safety glass
Housing
Stainless steel
Housing protection type
IP 66
Operating temperature range
Operation
- 20°C … + 55°C*
Operation with heater *
- 30°C … + 55°C*
Operation with heater **,
housing insulation and
protective screen
- 40°C … + 55°C*
Storage temperature range
- 30°C … + 60°C
* Comment
in the case of MT-4x6-A and MT-5x6-A:
at +55°C for a maximum of 5 hours, at +50°C for continuous operation (24/7)
** Comment
** The heater used must be of such a design that the temperature inside the operator
interface's housing does not fall below -20°C (-30°C only at the front) !
Heat dissipation
approx. 50 % via front plate, approx. 50 % via housing
Relative humidity
90% at + 40 °C, without condensation
Vibration
Operation
3 to 22 Hz: 1 mm
22 to 500 Hz: 9.8 m/s² = 1 g
Transport:
3 to 9 Hz: 3.5 mm
9 to 500 Hz: 9.8 m/s² = 1 g
Shock loading
Operation
150 m/s² = about 15 g / 11 ms
Transport:
250 m/s² = about 25 g / 6 ms
Dimensions [mm]
Front (w x h)
400 x 270
372 x 270
440 x 340
535 x 425
Cut-out
w x h [mm] (+/- 0.5)
385.5 x 257.5
359.5 x 257.5
427.5 x 327.5
522.5 x 412.5
Depth of cut-out
150
165
Wall thickness
8
Mounting position
vertical or horizontal
Weight [kg]
Device
13.00
12.60
17.30
23.5
Fixing frame
0.6
0.6
0.7
0.9
3.1 Additionally for MT-4x6-A (Panel PC)
Processor
ATOM 1.6 GHz
Working memory [GB]
Data memory [GB]
1 or 2
4 or 16
Type of data memory
Standard
Solid state flash drive
Optional
expansion to Exicom-SHD-xxx hard disk
100 GB
instead of flash drive
Operating system
Windows XP Embedded
Windows XP Professional
Windows 7 Ultimate
Standard Software
WIN CC flexible
Global language support
Via Multi-Language interface of Windows XP embedded (25 languages)
Operating Instructions MT-xx6-A Conformity to standards
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 13 of 52
4 Conformity to standards
The MT-xx6-A operator interfaces comply with the following standards and directives:
Standard
Classification
Directive 94/9/EC
1st supplement
IEC 60079-0 : 2011
General requirements
IEC 60079-1 : 2007
Flameproof enclosure "d"
IEC 60079-7 : 2006
Increased safety "e"
IEC 60079-11 : 2011
Intrinsic safety "i"
IEC 60079-15 : 2010
Type of protection "n"
IEC 60079-18 : 2009
Encapsulation "m"
IEC 60079-28 : 2006
Optical radiation "op is"
IEC 60079-31 : 2008
Protected by enclosures "t" (dust)
Electromagnetic compatibility
Directive 2004/108/EC
EN 61326-1 : 2008
General requirements
IEC 61000-6-2 : 2005
Immunity
IEC 61000-6-4 : 2011
Emission
5 Certificates
The MT-xx6-A operator interfaces are certified for installation in the following areas:
according to ATEX Directive 94/9/EC
for installation in zones 2 and 22
IECEx (International Electrotechnical Commision System for Certification to
Standards for Electrical Equipment for Explosive Atmospheres)
DNV (Det Norske Veritas)
LR (Lloyd´s Register)
GOST-R (Russion certification)
CSA (Canadian Standard Association)
UL-BR (UL do Brasil Certificações INMETRO)
5.1 ATEX
The ATEX certificates are listed under the following certification numbers:
Certificate number for MT-xx6-A: TÜV 11 ATEX 7103 X
5.2 IECEx
The IECEx certificates are listed under the following certification numbers:
Certificate number for MT-xx6-A: IECEx TUR 11.0015X
You can access all IECEx certificates on the official website of the IEC under their certificate
number. http://iecex.iec.ch/iecex/iecexweb.nsf/welcome?openform.
Operating Instructions MT-xx6-A Certificates
Page 14 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
5.3 DNV
The DNV certification is listed below the following numbers:
Certificate number: A-12989
File number: 899.60
Job Id: 262.1-001689-6
5.4 LR
The LR (Lloyd´s Register) certificate is listed under the following certification number:
Certificate number: 11/20032
5.5 GOST-R
The GOST-R certification is listed below the following number:
Certificate number: РОСС DE.ГБ04.B01741
5.6 CSA
The CSA certificate is listed under the following certification number:
Certificate number: 2512677
5.7 UL-BR
The UL-BR certificate is listed under the following certification number:
Certificate number: UL-BR 12.0398X
Operating Instructions MT-xx6-A Marking
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 15 of 52
6 Marking
Manufacturer
R. STAHL HMI Systems GmbH
Type code
MT-4x6-A / MT-5x6-A
CE classification:
c 0158
Testing authority and
certificate number:
TÜV 11 ATEX 7103 X
IECEx TUR 11.0015X
Ex classification:
e
ATEX guideline 94/9/EC
MT-xx6-A-Tx
II 3 (2/3) G Ex d e ia ib mb nA [ib Gb] [ic] IIC T4 Gc
II 3 (2/3) D Ex ia tc [ib Db] [ic] IIIC T80°C Dc IP66
MT-xx6-A-Fx
e
II 3 (2/3) G Ex d e ia ib mb nA [ib op is Gb] [ic] IIC T4 Gc
II 3 (2/3) D Ex ia tc [ib op is Db] [ic] IIIC T80°C Dc IP66
IECEx
MT-xx6-A-Tx
Ex d e ia ib mb nA [ib Gb] [ic] IIC T4 Gc
Ex ia tc [ib Db] [ic] IIIC T80°C Dc IP66
MT-xx6-A-Fx
Ex d e ia ib mb nA [ib op is Gb] [ic] IIC T4 Gc
Ex ia tc [ib op is Db] [ic] IIIC T80°C Dc IP66
GOST-R
MT-xx6-A-Tx
2ExdeiaibmbnA[ib][ic]IICT4
DIP A21 TA80°C, IP66
MT-xx6-A-Fx
2ExdeiaibmbnA[ibopis][ic]IICT4
DIP A21 TA80°C, IP66
CSA
Ex d e ia ib mb nA [ib Gb] [ic] IIC T4 Gc, Type 4X, IP66
Class II, Division 2, Groups E, F, G, T80°C
Ex ia tc [ib ic] IIIC T80°C Dc, IP66
UL-BR
MT-xx6-A-Tx
Ex d e ia ib mb nA [ib Gb] [ic] IIC T4 Gc
Ex ia tc [ib Db] [ic] IIIC T80°C Dc IP66
MT-xx6-A-Fx
Ex d e ia ib mb nA [ib op is Gb] IIC T4
Ex ia tc [ib op is Db] [ic] IIIC T80°C Dc IP66
Operating Instructions MT-xx6-A Power supply
Page 16 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
7 Power supply
7.1 Operator interfaces
Power supply: 24.0 VDC (min. 20.4 VDC , max. 28.8 VDC)
Um = 30 VDC
(for connected circuits in zone 1)
Power consumption: MT-xx6-A 1.2 A
7.1.1 All circuits in zone 2 and 22
If the operator interface and all connected circuits are solely used in zone 2 or 22, the operator
interface can be supplied with the required rated voltage of
Urated = 24 VDC (+20% / -15%)
7.1.2 With circuits in zone 1 and 21
If the operator interface is run in zone 2 and connected to intrinsically safe circuits / devices in
zone 1, the following applies:
Um = 30 VDC
(see EN 60079-11 : 2007, section 3.16).
7.1.3 Operator interface terminals
Copper wires with cross sections of betwee 0.2 mm² (AWG 24) and 1.5 mm² (AWG 14) may be
connected to any of the terminals of the operator interfaces.
When connecting cables to the terminals please make sure that the insulation of the
cables goes right up to the terminal contacts.
7.1.3.1 Tightening torque
For the terminals X1 and X11 a tightening torque of:
0,4 Nm up to 0,5 Nm is valid
and for the terminals X2, X3, X4, X5, X6, X7, X8 and X9 a tightening torque of:
0,5 Nm bis 0,6 Nm is valid.
Operating Instructions MT-xx6-A Permitted maximum values
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 17 of 52
8 Permitted maximum values
8.1 External, non-intrinsically safe circuits
Input voltage (X1):
Rated voltage 24 VDC (+20% / -15%)
(for exclusive operation in zone 2)
Power consumption for Urated 1.2 A max
Max. operating voltage Um 30 VDC
(applies for connected circuits in zone 1)
RS-422/-232 COM 1 (X2):
Rated voltage RS-422: 5 VDC RS-232: ±12 VDC
Max. operating voltage Um 253 VAC
USB-1 (X5):
Rated voltage 5 VDC
Max. operating voltage Um 253 VAC
USB-3 (X7):
Rated voltage 5 VDC
Max. operating voltage Um 253 VAC
Copper Ethernet (X11):
Rated voltage 5 VDC
Rated power 100 mW
Max. operating voltage Um 30 VDC
Audio (X3)
Rated voltage 5 VDC
Max. operating voltage Um 253 VAC
8.2 External inherently safe optical interface
Ethernet optical fiber (X10):
Wavelength 1350 nm
Radiant power 35 mW
Operating Instructions MT-xx6-A Permitted maximum values
Page 18 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
8.3 External intrinsically safe circuits
USB-0 (X4) and USB-2 (X6):
Uo
=
5.9
V
Io
=
2.18
A
Po
=
1.24
W
a) The maximum values for zone 1 group IIC are:
Ci
=
0
µF
Co
=
5.1
11
28
43
µF
Li
=
0
mH
Lo
=
10
5
2
1
µH
Co and Lo pairs directly above/underneath each other may be used.
The maximum values for zone 1 group IIB are:
Ci
=
0
µF
Co
=
14
40
79
200
µF
Li
=
0
mH
Lo
=
50
20
10
5
µH
Co and Lo pairs directly above/underneath each other may be used.
b) The maximum values for zone 2 group IIC are:
Ci
=
0
µF
Co
=
12
24
74
670
µF
Li
=
0
mH
Lo
=
10
5
2
1
µH
Co and Lo pairs directly above/underneath each other may be used.
The maximum values for zone 2 group IIB are:
Ci
=
0
µF
Co
=
37
92
200
790
µF
Li
=
0
mH
Lo
=
50
20
10
5
µH
Co and Lo pairs directly above/underneath each other may be used.
Reader RSi1 and RSi2 (X8) +Uint 1 (power supply circuit, X8.0, bridge to X8.2):
Uo
=
10.4
V
lo
=
220
mA
Po
=
2.29
W
a) The maximum values for zone 1 group IIC are:
Ci
=
1.72
µF
Co
=
0.8
µF
Li
=
0
mH
Lo
=
10
µH
Co and Lo pairs directly above/underneath each other may be used.
b) The maximum values for zone 2 group IIC are:
Ci
=
1.72
µF
Co
=
4.68
µF
Li
=
0
mH
Lo
=
10
µH
Co and Lo pairs directly above/underneath each other may be used.
Reader RSi1 (X8) +U_ex1 (power supply circuit, X8.2, bridge from X8.0):
Ui
=
12.4
V
Ii
=
220
mA
Pi
=
2.29
mW
Ci
=
25
nF
Li
=
0
mH
Operating Instructions MT-xx6-A Permitted maximum values
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 19 of 52
PS2 interface (X9):
Connection for keyboard, mouse, trackball, joystick
Uo
=
5.88
V
Io
=
200
mA
Po
=
1.18
W
a) The maximum values for zone 1 group IIC are:
Ci
=
17.6
µF
Co
=
15.4
25.4
µF
Li
=
0
mH
Lo
=
2
1
µH
Co and Lo pairs directly above/underneath each other may be used.
The maximum values for zone 1 group IIB are:
Ci
=
17.6
µF
Co
=
10.4
20.4
43.4
82.4
µF
Li
=
0
mH
Lo
=
100
50
20
10
µH
Co and Lo pairs directly above/underneath each other may be used.
b) The maximum values for zone 2 group IIC are:
Ci
=
17.6
µF
Co
=
68.4
652.4
µF
Li
=
0
mH
Lo
=
2
1
µH
Co and Lo pairs directly above/underneath each other may be used.
The maximum values for zone 2 group IIB are:
Ci
=
17.6
µF
Co
=
33.4
53.4
102.4
222.4
µF
Li
=
0
mH
Lo
=
100
50
20
10
µH
Co and Lo pairs directly above/underneath each other may be used.
Do NOT connect the optional external keyboard to live equipment !
Operating Instructions MT-xx6-A Type code
Page 20 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
9 Type code
9.1 MT-4x6-A (Panel PC)
MT-xx6-A-aa-Rx-bb-cc-dd-SIE
Front plate Siemens
Operating system
Data memory
Display version
Working memory
Ethernet interface
Family code (fixed to 6)
Size code (display)
0 = 10.4" display
1 = 10.4" display
3 = 15" display
5 = 19" display
4 = Panel PC Ex
Device for zones 2 and 22
Order variant:
Classification product key
Description
Type with
MT-4x6-A-Fx-Rx-bb-cc-dd-SIE
Optical fiber Ethernet interface100BaseFx (Ex op is)
MT-4x6-A-Tx-Rx-bb-cc-dd-SIE
Copper Ethernet interface 10/100BaseTx (Ex-nA)
MT-4x6-A-aa-R1-bb-cc-dd-SIE
Working memory 1 GB
MT-4x6-A-aa-R2-bb-cc-dd-SIE
Working memory 2 GB
MT-4x6-A-aa-Rx-TFT-bb-cc-dd-SIE
TFT display (standard)
MT-4x6-A-aa-Rx-SR-bb-cc-dd-SIE
Sunlight readable display 1000 cd/m² (MT-436-A only)
MT-4x6-A-aa-Rx-bb-4GB-dd-SIE
4 GB Solid State Drive
MT-4x6-A-aa-Rx-bb-16GB-dd-SIE
16 GB Solid State Drive
MT-4x6-A-aa-Rx-bb-100GB-dd-SIE
100 GB hard disk (externaly- Exicom-SHD-xxx) *
MT-4x6-A-aa-Rx-bb-cc-XPe-SIE
Windows XP embedded
MT-4x6-A-aa-Rx-bb-cc-XPp-SIE
Windows XP professional MUI
MT-4x6-A-aa-Rx-bb-cc-7U-SIE
Windows 7 ultimate
* The Exicom-SHD-xxx hard disk can only be used instead of a flash memory card (SSD),
not in addition to it !
Operating Instructions MT-xx6-A Type code
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 21 of 52
9.2 MT-5x6-A (Thin Client)
MT-xx6-A-aa-bb-SIE
Front plate Siemens
Display version
Ethernet interface
Family code (fixed to 6)
Size code (display)
3 = 15" display
5 = 19" display
5 = Thin Client Ex
Device for zones 2 and 22
Order variant:
Classification product key
Description
Type with
MT-5x6-A-Fx-bb-SIE
Optical fiber Ethernet interface 100BaseFx (Ex op is)
MT-5x6-A-Tx-bb-SIE
Copper Ethernet interface 10/100BaseTx (Ex-nA)
MT-5x6-A-aa-TFT-SIE
TFT display (standard)
MT-5x6-A-aa-SR-SIE
Sunlight readable display 1000 cd/m² (MT-536-A only)
Operating Instructions MT-xx6-A Safety Advice
Page 22 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
10 Safety Advice
This chapter is a summary of the key safety measures. The summary is supplementary to
existing rules which staff also have to study.
The safety of persons and equipment in hazardous areas depends on compliance with all
relevant safety regulations. Thus, the installation and maintenance staff carry a particular
responsibility, requiring precise knowledge of the applicable regulations and conditions.
10.1 Installation and operation
Please note the following when installing and operating the device:
The national regulations for installation and assembly apply (e.g. EN/IEC 60079-14).
The operator interface must only be switched on when it is closed.
The installation must be compliant with any applicable regulations.
After switching the operator interface off, wait for at least 1 minute before opening it.
The safe maximum values of the connected field device(s) must correspond to the values
listed on the data sheet or the EC type examination certificate.
The operator interfaces may be installed in zones 2 or 22.
When used in zone 2 and zone 22, intrinsically safe category 2 devices or energy-limited
category 3 associated equipment may be connected to the intrinsically safe circuits.
If category 2 equipment is connected to the intrinsically safe circuits in zone 1, Um must
adhere to EN 60079-11 : 2007, section 3.16 when connecting the power supply and the
non-energy-limited circuites of the MT-xx6-A.
For the maximum connectable L and C values of the intrinsically safe circuits, the
associated (above/underneath each other) pairs of values must be applied.
National safety and accident prevention rules.
Generally accepted technical rules.
Safety instructions contained in these operating instructions.
Any damage may compromise the explosion protection !
Use the device for its intended purpose only (see "Device Function").
Incorrect or unauthorized use and non-compliance with the instructions in this manual will void
any warranty on our part.
No changes to the device that compromise its explosion protection are permitted !
The device may only be installed and operated in an undamaged, dry and clean condition !
10.2 Cautionary note
10.3 Special conditions
The fronts of the operator interfaces with a sunlight readable display (type code includes “SR”)
may be cleaned with a damp cloth only.
Caution:
This is an EN 55022 Class A product. In a domestic environment this product may cause
radio interference in which case the user may be required to take adequate measures.
Operating Instructions MT-xx6-A Installation
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 23 of 52
11 Installation
11.1 General information
Electrical plants are subject to certain regulations concerning installation and operation
(e.g. RL 1999/92/EC, RL 94/9/EC and IEC/EN 60079-14).
It is the responsibility of the operators of electrical installations in hazardous environments to
ensure that the equipment is kept in proper condition, is operated according to instructions and
that maintenance and repairs are carried out.
11.2 MT-xx6-A
The operator interfaces may be installed in zones 2 or 22. The circuits must be installed
according to applicable regulations.
The PE connection part of the operator interface located at the back of the housing is
internally connected with the GND supply cable (X1 pins 3 and 4).
The operator interfaces can be mounted and operated in any position. Sufficient air
circulation must be ensured, however, so that the maximum operating temperature is not
exceeded.
The operator interface's front should be protected by a canopy against permanent
exposure to UV light. This increases the front membrane's lifespan. The canopy MUST
NOT be too close to the front plate and sufficient air circulation must be ensured.
The MT-4x6-A and MT-5x6-A devices may be operated at +55°C ONLY FOR SHORT
PERIODS (maximum 5 h) at a time.
Operating Instructions MT-xx6-A Installation
Page 24 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
11.3 Installation via USB-interfaces
Installation of software on the operator interfaces via the USB-interfaces:
11.3.1 Software installation using a USB Flash-Drive
You may only use USB Flash-Drives permitted for use by the manufacturer. These USB Flash-
Drives are below and in general referred to by the manufacturer as "USB(i) Drives". Data may
only be copied onto the operator interfaces and software may only be installed with these USB
Drives.
In hazardous areas you may only use I.S. certified USB Drives supplied by the
manufacturer.
In an industrial area, a permitted, non-explosion proof Flash-Drive may be connected to
the I.S. USB interface of the operator interface after having been connected to any PC.
The manufacturers USB(i) drives may also be connected to non-intrinsically safe
interfaces, from where they may be used with operator interfaces of the MT-xx6-A series.
If devices are connected to the I.S. USB interface that have not been approved the
manufacturer, protective elements may become damaged, thus compromising the intrinsic
safety of the interfaces.
In this case the manufacturer can no longer guarantee the intrinsic safety of the device !
11.3.2 Software installation with external USB devices
Not applicable to MT-5x6-A
Software may be installed with the aid of any external USB devices subject to the following
conditions:
The software is installed in the safe area.
The USB devices are connected to the USB interfaces USB1 or USB3 (X5 or X7) with the
VB-USB-INST1 connection cable.
Connection diagram with VB-USB-INST1 (hard disk, CD/DVD with power supply)
Direct connections to the operator interfaces must be via VB-USB-INST1!
Otherwise, the internal circuits may become damaged and the explosion-protection of the
operator interface may become compromised !
Operating Instructions MT-xx6-A Installation
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 25 of 52
11.4 USB interfaces
The MT-xx6-A device series have 4 USB interface channels.
USB0 at X4 for the internal connection of a USB Drive.
USB1 at X5 for the connection of external USB devices.
USB2 at X6 for the connection of an external USB Drive.
USB3 at X7 for the connection of external USB devices.
The connection diagram for the MT-xx6-A interfaces can be found in chapter 13.2
connections.
11.4.1 I.S. USB interfaces USB0, USB2
The USB0 and USB2 interfaces (X4 and X6) are intended for the internal or external connection
of USBi Drives.
The maximum value for the joint power supply of USB0 and USB2 is 500 mA.
11.4.2 Ex-nA USB interfaces USB1, USB3
The USB1 and USB3 interfaces (X5 and X7) are intended for the connection of external USB
devices.
The maximum value for the joint power supply of USB1 and USB3 is 500 mA.
11.4.2.1 Connection variations for Ex-nA USB interfaces
The two Ex-nA USB interfaces have an identical structure.
If intrinsically safe devices are connected to the Ex-nA USB interfaces of the MT-xx6-A
operator interfaces, the manufacturer cannot guarantee that the intrinsic safety of these
devices will continue to apply.
The following versions are possible:
1. If a USB device that is not connected to the mains is connected, voltage can be supplied
from the internal power supply (terminal 1).
2. If a USB device that is connected to the mains is connected, the internal power supply
(terminal 1) must not be connected. The power must be supplied from an external device.
Operating Instructions MT-xx6-A Installation
Page 26 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
11.4.2.2 Connection terminal
Flexible cables with a cross section of 0.2 2.5 mm² can be used.
The maximum cable length for the connection with the USB interfaces (X5 and X7) is 2.5 m.
The insulation of the wire must reach right up to the terminal body.
11.4.2.2.1 Type 1 connection version
The USB device does not require an external power supply as it uses less than 500 mA.
No connection to the mains via other interfaces, e.g. WLAN stick.
Type 1 connection diagram (e.g. WLAN stick)
11.4.2.2.2 Type 2 connection version
The USB device does require an external power supply to function because it uses over
500 mA (e.g. hard disks, CD/DVD drives).
The USB device is connected to the mains via other interfaces (e.g. USB/serial converter,
USB-Profibus interface).
Type 2 connection diagram (e.g. hard disk, CD/DVD with power supply)
Operating Instructions MT-xx6-A Assembly and disassembly
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 27 of 52
11.4.2.2.3 Type 3 connection version
The USB device does require an external power supply to function because it uses over
500 mA (e.g. hard disks, CD/DVD drives).
The USB device is connected to the mains via other interfaces (e.g. USB/serial converter,
USB-Profibus interface).
The USB device needs the VCC connection of the operator interface (internal supply
terminal 1) to function.
Type 3 connection diagram (any USB device with power supply)
12 Assembly and disassembly
12.1 General information
Assembly and disassembly are subject to general technical rules. Additional, specific safety
regulations apply to electronic and pneumatic installations.
12.2 Cut-out MT-xx6-A
Make a cut-out with the following dimensions:
Operator
interface
Width
Height
Depth of cut-out
Material thickness
MT-x06-A
385.5 ± 0.5 mm
257.5 ± 0.5 mm
150 mm
up to 8 mm
MT-x16-A
359.5 ± 0.5 mm
257.5 ± 0.5 mm
150 mm
up to 8 mm
MT-x36-A
427.5 ± 0.5 mm
327.5 ± 0.5 mm
165 mm
up to 8 mm
MT-x56-A
522,5 ± 0,5 mm
412,5 ± 0,5 mm
165 mm
up to 8 mm
13 Operation
13.1 General information
When operating the devices, particular care shall be taken that:
the operator interface has been properly installed according to instructions,
the device is undamaged,
the terminal compartment is clean,
all screws are tightened fast,
before switching the operator interface on, its external PE terminal is properly connected
to the equipotential bonding system at its place of use,
the cover of the terminal compartment is completely closed.
Operating Instructions MT-xx6-A Operation
Page 28 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
13.2 Connections
Terminal
Pin
Definition
Connection
X1
1
Power supply operator interface +24 VDC
Power supply
2
Power supply operator interface +24 VDC
of the
3
Power supply operator interface GND
operator interface
4
Power supply operator interface GND
X2
1
TxD-b
Serial
2
TxD-a
COM1 interface
3
RxD-b
RS-422/485
4
RxD-a
5
TxD-b'
6
TxD-a'
7
RxD-b'
8
RxD-a'
9
TxD
Serial
10
RxD
COM1 interface
11
RTS/
RS-232
12
CTS/
13
GND
X3
1
Line Out right
Audio
2
GND
3
Line Out left
X4
USB interface, connection type A
USB0
X5
1
VCC
USB1
2
USB -
3
USB +
4
GND
X6
1
VCC
USB2
2
USB -
3
USB +
4
GND
5
GND
X7
1
VCC
USB3
2
USB -
3
USB +
4
GND
X8
0
+U_INT1
Reader interface
1
0V
I.S.
2
+U_EX1
3
GND
4
+U_RD
5
Signal 1
6
Signal 2
7
Signal 3
8
Signal 4
9
+U_EX1 (out)
X9
1
VCC
PS2 interface *
2
KBDAT
for
3
KBCLK
external keyboard /
4
MSDAT
mouse
5
MSCLK
6
GND
Operating Instructions MT-xx6-A Operation
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 29 of 52
X10
1
Optical fiber connection type SC
Ethernet optical
fiber interface **
X11
1
TxD (+)
Ethernet copper
2
TxD (-)
Connection **
3
RxD (+)
4
RxD (-)
Please also note that the COM interface may only be physically connected once !
Power is supplied either with a physical RS-232 or an RS-422/485 connection.
* Do NOT connect the optional external keyboard to live equipment !
** Please note that the Ethernet connection is either for an optical fibre connection (X10) or
for a copper connection (X11), depending on the version ordered !
The optical fiber connection requires a multimode optical fiber cable with 62.5 µm core
diameter and 125 µm external diameter.
Copper wires with cross sections of between 0.2 mm² (AWG 24) and 1.5 mm² (AWG 14)
may be connected to any of the terminals of the operator interfaces.
Which cable cross sections are chosen should be decided on the basis of relevant
regulations, such as DIN VDE 0298. Factors that might require a larger cross section,
such as current, increased temperatures, cable bundling, etc. must also be taken into
account !
13.2.1 Dip switch settings S3 and S4
Switch
Position
Interface
Function
S3-1
OFF
COM1
RS-422/485
No bus terminator resistor set
ON
Bus terminator resistor TxD line
S3-2
OFF
No bus terminator resistor set
ON
Bus terminator resistor RxD line
S4-1
S4-2
S4-3
Interface
Keying
0
0
0
RS-422
Automatic keying
0
1
0
Keying always on
0
0
1
Keying enabled by SW
0
1
1
Driver in idle mode
1
0
0
RS-485
Automatic keying
1
1
0
Status not permitted !!!
1
0
1
Keying enabled by SW
1
1
1
Driver in idle mode
S4-4 *
OFF
Touch *
Touch switched off
ON
Touch switched on
* To switch off the touch via the dip switch S4-4 is at the moment not possible !
Operating Instructions MT-xx6-A Operation
Page 30 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
13.2.2 Status LEDs
The status of the respective LEDs at the operator interfaces indicates the activity of the
corresponding data lines.
In hazardous areas the operator interface must not be operated without the housing lid !
The status LEDs can therefore only be observed at the first start-up or in safe areas.
13.2.2.1 LEDs
Definition
Colour
Name
Description
LD5
green
COM1 TxD
Activity on COM1: sending, LED flashing
LD8
yellow
COM1 RxD
Activity on COM1: receiving, LED flashing
LD7
green
COM2 TxD
Activity on COM2: sending, LED flashing
LD6
yellow
COM2 RxD
Activity on COM2: receiving, LED flashing
LD14
yellow
LINK ACT
Ethernet link established, LED always on
Activity on Ethernet link, LED flashing
LD15
green
HD
Access to system disk (Solid State, HDD),
LED flashing
(only for MT-4xx-A devices)
Operating Instructions MT-xx6-A Operation
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 31 of 52
Back view of MT-xx6-A device:
LED section at MT-xx6-A device:
Operating Instructions MT-xx6-A Exicom-SHD-xxx hard disk
Page 32 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
14 Exicom-SHD-xxx hard disk
The optional Exicom-SHD-xxx hard disk can be fitted inside the MT-4x6-A operator interfaces.
* The Exicom-SHD-xxx hard disk can only be used instead of a flash memory card (SSD),
not in addition to it !
14.1 Installation of hard disk
The Exicom-SHD-xxx hard disk is mounted by the manufacturer during the production of its
operator interfaces. It is NOT possible to install the hard disks at a later date !
Installation of the Exicom-SHD-xxx hard disk into the MT-4x6-A operator interfaces
reduces the minimum operating temperature to -20°C !
The minimum temperature for the front remains -30°C.
The Exicom-SHD-xxx is incorporated into the operator interface's PA by means of two
fixing screws.
The fixing screws must be FIRMLY affixed to the housing of the operator interface to
ensure this.
The SAFE integration of the Exicom-SHD-xxx hard disk into the operator interface's PA is
guaranteed due to its factory-mounting by the manufacturer.
14.1.1 Mechanical dimensions
Hard disk housing (l x w x h, in mm) 113 x 92 x 31
Top view:
Operating Instructions MT-xx6-A Exicom-SHD-xxx hard disk
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 33 of 52
14.2 Connections
The Exicom-SHD-xxx hard disk is supplied with 24 VDC.
The two connection wires intended for the purpose can be connected to the free contacts of the
operator interface's X1 terminal (operator interface supply). The red cable (+ wire) is connected
to the + pin (pin 2) and the black cable (- wire) is connected to the (GND) pin (pin 3) of X1.
The data cable of the hard disk is connected with the S-ATA plug to the associated 11-pin
connector which protrudes from the encapsulation.
14.2.1 Safety advice
DO NOT operate the MT-4x6-A operator interfaces WITHOUT the HARD DISK or if the
SATA connection cable is DISCONNECTED !
A warning notice to this effect is attached to the SATA connection cable (see illustration).
While the operator interface is switched on, the SATA connector and the power supply of
the Exicom-SHD-xxx hard disk MUST NOT be disconnected.
A warning notice to this effect is attached to the Exicom-SHD-xxx hard disk (see
illustration).
14.3 Hard disk replacement
The Exicom-SHD-xxx hard disk may be replaced. However, only specially trained staff with
expertise in explosion-protection may carry out such a replacement.
For information on how to replace the hard disk, please refer to the Operating Instructions
"OI_Harddisk_SHD".
Operating Instructions MT-xx6-A Maintenance, service
Page 34 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
15 Maintenance, service
Associated equipment is subject to maintenance, service and testing according to guidelines
1999/92/EC, IEC 60079-19, EN 60079-17 and BetrSichVer (Betriebssicherheitsverordnung -
Occupational Safety and Health) !
Because the transmission of the devices remains reliable and stable over long periods of time,
regular adjustments are not required.
The following principles apply to repairs *, spare parts purchase* or exchange of parts * (where
this can be done by the user !):
Only original parts provided by the manufacturer must be used.
Fuses may only be replaced by equivalent fuse types.
* Please also note section Troubleshooting !
If the MT-xx6-A operator interfaces are stored for more than 6 months, they should be operated
every six months for at least one hour at room temperature (20°C ± 5°C).
The MT-xx6-A series operator interfaces are maintenance-free across their entire lifespan.
System maintenance should focus on the following:
a. Seal wear
b. Display damage
c. All screws are tightened fast
d. All cables and lines are properly connected and undamaged
15.1 Servicing
In accordance with IEC 60079-19 and EN 60079-17, operators of electric plants in hazardous
areas are obliged to have them serviced by qualified electricians.
15.2 Time function
Does not apply to MT-5x6-A:
When the MT-4x6-A operator interfaces are switched off, their clock function is maintained by a
battery and a capacitor. As long as the battery is intact, the clock function is maintained. Once
the battery fails, the capacitor takes over and maintains the clock function for about four days. If
the operator interface is switched on after a longer interval than that, the time and date have to
be re-set manually or via a connected system.
Operating Instructions MT-xx6-A Troubleshooting
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 35 of 52
16 Troubleshooting
Devices operated in hazardous areas must not be modified. Repairs may only be carried out by
qualified, authorized staff specially trained for this purpose.
Repairs may only be carried out by specially trained staff who are familiar with all basic
conditions of the applicable user regulations and if requested have been authorized by
the manufacturer.
17 Disposal
Disposal of packaging and used parts is subject to regulations valid in whichever country the
device has been installed.
The disposal of devices sold after August 13th, 2005, and installed in countries under the
jurisdiction of the EU is governed by directive 2002/96/EC on waste electrical and electronic
equipment (WEEE). Under this directive, operator interfaces are listed in category 9 (monitoring
and control instruments).
We shall take back our devices according to our General Terms and Conditions.
17.1.1 ROHS directive 2002/95/EC
The prohibition of hazardous substances as detailed in directive 2002/95/EC (ROHS) does not
apply to electronic equipment of categories 8 and 9, and is therefore not applicable to the
equipment described in these operating instructions.
17.1.2 China ROHS labelling
According to new Chinese legislation in force since 01.03.2007, all devices containing
hazardous substances must be labeled accordingly.
For our operator interfaces, the following conditions apply:
Names and contents of toxic or hazardous substances or elements:
Part
Toxic or hazardous substances and elements
Name
Lead
(Pb)
Mercury
(Hg)
Cadmium
(Cd)
Hexaval
ent
Chromi
um
(Cr (VI))
Polybrominat
ed Biphenyls
(PBB)
Polybrominate
d
diphenyl
ethers
(PBDE)
Housing
O
O
O
O
O
O
Display
O
O
O
O
O
O
all PCBs
X
O
O
O
O
O
Miscellaneous
O
O
O
O
O
O
O Indicates that this toxic or hazardous substance contained in all of the homogeneous
materials for this part is below the limit requirements in SJ/T11363-2006.
X Indicates that this toxic or hazardous substance contained in at least one of the
homogeneous materials for this part is below the limit requirements in SJ/T11363-2006.
Operating Instructions MT-xx6-A Front panel resistance
Page 36 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
18 Front panel resistance
This section contains information on the resistance of the operator interfaces to various
environmental factors. These have an impact on the mechanical, thermal and chemical stability
of the operator interfaces.
The resistance to chemicals was tested according to DIN 42115 Part 2, i.e. the stability over
24 hours without visible changes to the operator interfaces.
18.1 Design
Structure:
18.2 Materials
Application
Material
Membrane top
Polyester or stainless steel
Touch screen
Polyester
Display window
Safety glas
Front plate
Aluminum
Housing
Stainless steel
Front panel seal
Polyurethane
Back cover seal
(not visible)
Silicone
18.3 Material properties
The selection of chemicals listed here is not exhaustive.
More comprehensive lists can be obtained for further information from the manufacturer.
Because of the numerous chemical substances available on the market, these lists can
only represent a selection.
Further information can also be found on the following homepage:
http://macdermidautotype.com/
Operating Instructions MT-xx6-A Front panel resistance
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 37 of 52
18.3.1 Entire device
The chemical substances and resistances are the lowest common denominator of all
materials used in the operator interface.
Thus, the entire device has a somewhat lower chemical resistance than the individual
materials.
Property
Chemical material
class / group
Chemical
substances
Test method
Chemical
Chemical resistance
Alcohols
Glycerin
DIN 42115
DIN 53461
Aldehydes
Formaldehyde
37--42%
Household chemicals
Detergents
Oils
Petrol
Property
Resistance
Test method
Mechanical
Service life after imprint
Operating force
MIT folding resistance
5 million touches
max. 50 N
>20000 folding operations
Autotype
method
ASTM D2176
Thermal
Dimensional
Dimension stability
Max. 0.2% at 120° longitudinal
Typically 0.1%
Autotype
method
18.3.2 Membrane top (Polyester)
Property
Chemical material
class / group
Chemical substances
Test method
Chemical
Chemical
resistance
Alcohols
1,3 Butanediol
1,4 Butanediol
Cyclohexanol
Diacetone alcohol
Ethanol
Glycol
Glycerol
Isopropyl alcohol
Methanol
Neopentyl glycol
Octanol
1,2 Propylene glycol
Triacetin
Dowandol DRM/PM
DIN 42115
DIN 53 461
Oder
ASTM-F-1598-
95
Aldehydes
Acetaldehyde
Formaldehyde 37--42%
Amines
Ammonia < 2%
Esters
Amyl acetate
Ethylacetate
N-Butyl acetate
Operating Instructions MT-xx6-A Front panel resistance
Page 38 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
Ethers
1.1.1. Trichloroethane
Ether
Dioxane
Diethyl ether
2-Methyltetrahydrofuran
(2-ME-THF)
Aromatic hydrocarbons
Benzene
Toluene
Xylene
Paint thinner (white spirit)
Ketones
Acetone
Methyl ethyl ketone
Cyclohexanone
Methyl isobutyl ketone
(MIBK)
Isophorone
Diluted acids
Formic acid <50%
Acetic acid < 5%
Phosphoric acid <30%
Hydrochloric acid <10%
Nitric acid <10%
Trichloroacetic acid <50%
Sulfuric acid <30%
Diluted alkaloids
(bases)
Caustic soda <40%
Household chemicals
Ajax
Ariel
Domestos
Downey
Fantastic
Formula 409
Gumption
Jet Dry
Lenor
Persil
Tenside
Top Jop
Vim
Vortex
Washing powder
Fabric conditioner
Whis
Windex
Oils
Petrol
Drilling muds
Braking fluid
Decon foam
Diesel oil
Varnish
Keroflux
Paraffin oil
Castor oil
Silicone oil
Solvent naphta
Mineral turpentine
Kerosene
Operating Instructions MT-xx6-A Front panel resistance
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 39 of 52
No specific material
class
Acetonitrile
Alkali carbonate
Dichromates
Potassium dichromate
Caustic soda <20%
Dibutyl phthalate
Dioctyl phthalate
Iron II chloride (FeCl2)
Iron II chloride (FeCl3)
Haloalkanes
Potassium soap
Potassium hydroxide <30%
Sodium bisulfate
Tetrachloroethylene
Salt water
Trichloroethylene
Water
Hydrogen peroxide >25%
Property
Resistance
Test method
Mechanic (keyboard)
Service life after imprint
Operating force
MIT folding resistance
5 million touches
max. 50 N
>20000 folding operations
Autotype
method
ASTM D2176
Mechanic (touch screen)
point activation
1 million activations at any single point
3M method
Thermal
Dimensional
Dimension stability
Max. 0.2% at 120° longitudinal
Typically 0.1%
Autotype
method
18.3.3 Touch screen
Property
Chemical material
class / group
Chemical
substances
Test method
Chemical
Chemical resistance
(see front membrane)
(see front membrane)
(see front
membrane)
Property
Resistance
Test method
Mechanical
Service life after imprint
MIT folding resistance
(see front membrane)
(see front
membrane)
Thermal
Dimensional
Dimension stability
(see front membrane)
(see front
membrane)
Operating Instructions MT-xx6-A Front panel resistance
Page 40 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
18.3.4 Front panel seal
Property
Chemical material
class / group
Chemical
substances
Test method
Chemical
Chemical resistance
Alcohols
Glycerol
DIN 53461
Aldehydes
Formaldehyde
Ketones
Acetone
Household chemicals
Detergents
Soap suds
Oils
Petrol
Diesel oil
Heizöl
Hydrauliköl
Leinöl
Property
Resistance
Test method
Mechanical
(No information available at present)
Thermal
Installation area
-30 to 80°C
DIN 53461
18.3.5 Rückdeckeldichtung
Property
Chemical material
class / group
Chemical
substances
Test method
Chemical
Chemical resistance
Alcohols
Methanol
Glycerol
DIN 53461
Aldehydes
Formaldehyde
Amines
Ammonia
Diluted acids
Sulfuric acid 25%
Household chemicals
Detergents
Soap suds
Oils
Petrol
Braking fluid
Mineral oils
Engine oils
Axle grease / lube oil
Property
Resistance
Test method
Mechanical
(No information available at present)
Thermal
Installation area
-60 to 200°C
DIN 53461
Operating Instructions MT-xx6-A General Information
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 41 of 52
19 General Information
The General Information below ONLY applies to the Panel PC Ex series of operator interfaces,
and NOT to the Thin Client Ex series.
19.1 Keyboard features
Pressing two keys at once (e.g. F1 + F7) is not supported by the operator interfaces !
In such a case, the system considers the key that was pressed first as "active" and implements
the associated functions and / or key bit functions !
The key pressed second is ignored.
Pressing any three of the following keys at the same time has the same effect as pressing
Ctrl + Alt + Del !
The keys are: F1, F2, F7 and F8.
MT-406-A only:
Pressing the S1 S10 softkeys on the MT-406-A has the same effect as pressing the
numerical keys 0 9.
As an alternative, you may also allocate the Shift + F1 Shift + F10 functions to the
S1 S10 keys.
If this is required, it must be stated when ordering, as it can only be done by the manufacturer
before delivery.
Operating Instructions MT-xx6-A General Information
Page 42 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
19.2 MT-4x6-A (Panel PC)
19.2.1 Licensing issues
The Panel PC Ex series operator interfaces are fully pre-installed with the Windows XP
Embedded, Windows XP Professional or Windows 7 Ultimate operating systems.
The license sticker is affixed on the back of the operator interface, next to the type plate.
Please note that according to the license issued for Windows XP Embedded the application of
this system as an Office PC is not permitted.
19.2.2 Recovery Stick
To restore your Panel PC device to its original state you will need a Recovery Stick, which
is available as an optional extra. This recovery stick (USB-drive, also available intrinsically
safe) contains the factory image, with which the system can be restored to delivery status
within a very short time.
Please note that you can restore the operator interfaces to their original state only with the
aid of the Recovery Stick.
As an option, the recovery stick can also contain a backup software, with which you can
back up your own device configuration.
19.2.3 Back-up
Please note that it is the sole responsibility of the operator to generate a back-up of the
operator interfaces and their overall function.
We strongly recommend such a back-up to be stored on an external storage medium
(USB stick / recovery stick, CD, DVD or similar) or on the company network.
19.2.4 Initial start-up
19.2.4.1 Initial start-up XP Pro/WIN 7
When the Panel PC operator interfaces are run for the first time with the Windows XP
Professional or Windows 7 operating systems, this requires a keyboard that must be
connected via the VB-USB-ISNT1 cable included in the delivery !
See also: Software installation with external USB devices
19.2.4.2 Initial start-up XP Embedded
When the device is started for the first time, a Wizard starts where users have to select certain
settings.
Please follow the instructions of the Wizard carefully.
Operating Instructions MT-xx6-A General Information
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 43 of 52
19.2.5 Switching off/closing down
The Microsoft Windows operating system stores key data in the main memory, regardless
of the application, and has to store this data on the hard disk before the PC / operator
interface is switched off.
It is therefore important for the safe and correct operation that the operator interface is
closed down properly (see illustration below) and NOT simply switched off.
Otherwise the existing image of the device may be damaged, rendering the operator
interface non-functioning.
After the data has been stored, Windows informs the user that the device can now be switched
off.
Only switch off the device once you have received this message.
19.2.5.1 Note on XP Embedded
When using the Windows XP Embedded operating system on the Panel PC series operator
interfaces, the C:\ system drive can be protected from unauthorised writing.
This is NOT the case with Windows XP Professional or Windows 7 Ultimate !
Recommendation:
In the case of applications that require constant writing into memory, the manufacturer
recommends you use external storage media (USB sticks, network servers) for these write
processes.
Operating Instructions MT-xx6-A General Information
Page 44 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
19.2.6 Installation Windows XP Professional
After installing the Windows XP Professional Image, the following message will pop up when
starting up the device again:
The following services are dependent on the distributed transaction coordinator service.
Stopping the distributed transaction coordinator service will also stop these services.
Message Queuing
Do you want to continue this operation ?
The MSDTC service is necessary for the SQL server, which in turn is necessary for
Siemens WinCC. For this reason, the message MUST be confirmed with YES, otherwise the
start-up of this service will fail.
Operating Instructions MT-xx6-A CSA Control Drawing
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 45 of 52
20 CSA Control Drawing
Operating Instructions MT-xx6-A CSA Control Drawing
Page 46 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
Operating Instructions MT-xx6-A CSA Control Drawing
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 47 of 52
Operating Instructions MT-xx6-A Declaration of EC conformity
Page 48 of 52 OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013
21 Declaration of EC conformity
Operating Instructions MT-xx6-A Release notes
OI_MT_xx6_A_SIE_en_V_03_00_01.docx / 12.02.2013 Page 49 of 52
22 Release notes
The chapter entitled "Release Notes" contains all the changes made in every version of the
Operating Instructions.
Version 03.00.00
First edition with HW-Rev. 3 SIE
Including of data cable length in" technical data"
Including of Windows 7 Ultimate in "note on XP Embedded"
Version 03.00.01
Text and layout changes
Changing of "technical data"
Text of type code adapted
Correction of CSA marking
Inclusion of note to hard disk "usage instead of a flash memory"
Siemens AG
Industry Sector
Postfach 48 48
90327 NÜRNBERG
DEUTSCHLAND