Fuji Electric FA components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
08/35
08
■Specifications
Rated Rated Peak Max. Watt Fuse-link
current
voltage
arc interrupting I2t loss
voltage
(Amp
2
×sec.)
× 103Type
(A) (V) (W)
12 550V 1550 0.09 5.1 BLC012-1
20 AC 1550 0.27 8.5 BLC020-1
23 1550 0.39 10 BLC023-1
45 1380 1.8 19 BLC045-1
75 1250 5 32 BLC075-1
90 1250 11.5 38 BLC090-1
120 1200 33 51 BLC120-1
140 1200 100 59 BLC140-1
30 250V Max. 0.35 4.0 CR2L-30
50 AC 500 0.85 6.0 CR2L-50
75 2.3 9.0 CR2L-75
100 4.0 12.0 CR2L-100
125 6.5 14.0 CR2L-125
140 7.0 16.0 CR2L-140
150 9.5 18.0 CR2L-150
175 13 21.0 CR2L-175
200 17 23.0 CR2L-200
225 22 26.0 CR2L-225
260 27 30.0 CR2L-260
300 38 35.0 CR2L-300
325 49 37.0 CR2L-325
350 60 37.0 CR2L-350
400 103 39.0 CR2L-400
450 140 46.0 CR2L-450
500 160 48.0 CR2L-500
550 200 51.0 CR2L-550
600 215 56.0 CR2L-600
Interrupting capacity
BLC ...... 100kA at 550V AC
CR2L .... 100kA at 250V AC
BLC, CR and CS types
Super Rapid Fuses
150–1500 Volts AC
10–4700 Amps
■Description
The FUJI BLC, CR and CS types are
extremely reliable fuses which have
been specially developed to provide
protection for silicon diodes and
thyristors and are suitable for inverters
using semiconductors or transformers-
rectifiers. FUJI Super Rapid Fuses are
designed with a very small total I2t
value which gives them a high speed
interrupting action in the face of
abnormal currents.
In addition the arc voltage generated at
the time of interruption has a low value
so that faults will not influence related
electric machinery and equipment.
These fuses can carry out the
protection of many types of circuits
rating from the semiconductor
overcurrents to destructive short-
circuiting faults-i.e. when the
SD-36 SM-388 SI-431 SI-429
BLC CR2L CS5F CS10F
semiconductors short or circuits fail the
sound elements will be quickly isolated
from the fault circuits.
■Features
•The total clearing I2t is small and the
semiconductor circuit is completely
protected.
•Since the peak arc voltage at the
time of interruption is low damage to
other equipment does not occur.
Low Voltage Fuses
BLC, CR and CS types
Super Rapid Fuses
Rated Rated Peak Max. Watt Fuse-link
current
voltage
arc interrupting I2t loss
voltage
(Amp
2
×sec.)
× 103Type
(A) (V) (W)
10 250V Max. 0.04 1.2 CR2LS-10
20 AC 500 0.17 3.0 CR2LS-20
30 0.35 4.0 CR2LS-30
50 0.85 6.0 CR2LS-50
75 2.3 9.0 CR2LS-75
100 4.0 12.0 CR2LS-100
20 600V Max. 0.14 4.0 CR6L-20
30 AC 1200 0.35 7.0 CR6L-30
50 1.8 9.0 CR6L-50
75 3.0 12.5 CR6L-75
100 7.0 15 CR6L-100
150 18 22.0 CR6L-150
200 30 34.0 CR6L-200
250 70 37.0 CR6L-250
300 95 40.0 CR6L-300
350 150 45.0 CR6L-350
400 200 55 CR6L-400
500 390 60 CR6L-500
600 700 70 CR6L-600
Interrupting capacity
CR2LS . 100kA at 250V AC
CR6L .... 100kA at 600V AC
•High interrupting capacity of 200kA
at 1000V AC
•The CS type is provided with a blown
fuse indicator. An alarm contact
block (1NO or 1NC) can also be
attached.
■UL recognized: CR2L/UL,CR2LS/UL,
CR6L/UL
(File No. E92312)
CSA certificated: CR2LS/UL
(File No. LO4000-4090)
TÜV: CR2LS/UL (10-100A),
CR2L/UL (150-350A)
(Rep. No. E9450643E02)
CR6L/UL (50-300A)
(Rep. No. E9560543E02)