Preface, Contents
Document Guide 1
Product Overview 2
Installing and Wiring the C7-635 3
Special Features of the C7-635 4
Maintenance 5
Appendices
Technical Specifications A
Index
Edition 03/2004
A5E00155581-04
C7-635 Control System
Manual
SIMATIC
This manual is part of the documentation
package with the order number:
6ES7635-1EA00-8BA0
This manual has the order number:
6ES7635-1AA00-8BA0
The following supplement is part of this documentation:
No. Designation Drawing number Edition
1 Product information A5E00861679-01 07/2006
!Danger
indicates that death, severe personal injury or substantial property damage will result if proper precautions
are not taken.
!Warning
indicates that death, severe personal injury or substantial property damage can result if proper
precautions are not taken.
!Caution
indicates that minor personal injury can result if proper precautions are not taken.
Caution
indicates that property damage can result if proper precautions are not taken.
Notice
draws your attention to particularly important information on the product, handling the product, or to a
particular part of the documentation.
Qualified Personnel
Only qualified personnel should be allowed to install and work on this equipment. Qualified persons are
defined as persons who are authorized to commission, to ground and to tag circuits, equipment, and
systems in accordance with established safety practices and standards.
Correct Usage
Note the following:
!Warning
This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers which
have been approved or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installed
correctly, and operated and maintained as recommended.
Trademarks
SIMATIC®, SIMATIC HMI® and SIMATIC NET® are registered trademarks of SIEMENS AG.
Third parties using for their own purposes any other names in this document which refer to trademarks
might infringe upon the rights of the trademark owners.
Safety Guidelines
This manual contains notices intended to ensure personal safety, as well as to protect the products and
connected equipment against damage. These notices are highlighted by the symbols shown below and
graded according to severity by the following texts:
We have checked the contents of this manual for agreement
with the hardware and software described. Since deviations
cannot be precluded entirely, we cannot guarantee full
agreement. However, the data in this manual are reviewed
regularly and any necessary corrections included in
subsequent editions. Suggestions for improvement are
welcomed.
Disclaim of LiabilityCopyright Siemens AG 2002-2004 All rights reserved
The reproduction, transmission or use of this document or its
contents is not permitted without express written authority.
Offenders will be liable for damages. All rights, including rights
created by patent grant or registration of a utility model or
design, are reserved.
Siemens AG
Bereich Automation and Drives
Geschaeftsgebiet Industrial Automation Systems
Postfach 4848, D- 90327 Nuernberg
© Siemens AG 2002-2004
Technical data subject to change.
Siemens Aktiengesellschaft A5E00155581-04
iii
C7-635 Control System
A5E00155581-04
Preface
Purpose of this Manual
This manual provides a complete overview of the C7-635 Control System and
assistance with its installation and commissioning. Options for connecting
additional devices are explained, and the required components are presented.
Scope of Manual
This manual is applicable to the following:
C7 Order Number As of Version
Firmware/Hardware
C7-635 Touch 6ES7 635-2EB01-0AE3 CPU V2.0.7 / 01
HMI V 6.0.2.23 (Win CE)
C7-635 Key 6ES7 635-2EC01-0AE3 CPU V2.0.7 / 01
HMI V 6.0.2.23 (Win CE)
Audience and Knowledge Requirements
This manual is intended for persons having the required qualifications to
commission, operate, and program the hardware product described.
You should be familiar with the use of computers or similar tools (such as
programming devices) under the Windows 98/2000/NT 4.0/XP operating system
and be knowledgeable regarding the basic STEP 7 software and ProTool
configuration software and their documentation.
C7-635 Documentation Package
The C7-635 consists of the following individual components:
SIMATIC S7-CPU 314C-2 DP
SIMATIC Touch Panel TP170 B (C7-635 Touch) and Operator Panel OP170 B
(C7-635 Key)
Manuals providing detailed information on these individual components are
included in this documentation package. These manuals are essential when
working with the C7-635.
Preface
iv C7-635 Control System
A5E00155581-04
The documentation package consists of seven manuals and an instruction list:
Manual
Operating Instructions
Reference Manual
S7-300 Instruction List
Touch Panel “TP170 A”, “TP170 B”,
Operator Panel “OP170 B”
Description of operator input, the functions,
and the technical specifications of the CPU.
Description of the Individual Technological
Functions
Positioning, Counting, and Control
The CD contains examples of the
technological functions.
Description of how to configure, install, wire,
network, and commission the S7-300.
Function description and technical
specifications of the signal modules, power supply
modules, and interface modules.
List of CPU instruction sets
and their execution times.
List of executable blocks
(OBs/SFCs/SFBs) and their execution times.
Provides information about:
Functionality
Device description
Operating modes and operation of the OP/TP
Manual
C7-635 Control System
Manual
Description of:
Installation and wiring
Operator input
Technical Specifications of the C7-635
You are reading this manual.
Communication for
Windows-Based Systems
Manual
Includes:
Connection to S7-200, S7-300, and S7-400
by means of MPI and PROFIBUS
User data areas for communication between
CPU and Touch Panel/Operator Panel
Manual
CPU 31xC Technological Functions
Examples
S7-300, CPU 31xC and CPU 31x:
Hardware and Installation
S7-300 Module Data
CPU 31xC, CPU 31x,
IM 151-7 CPU, BM 147-1 CPU,
BM 147-2 CPU
CPU 31xC and CPU 31x, Technical data
Preface
v
C7-635 Control System
A5E00155581-04
Additional Documentation
To assist you in programming and configuring a C7, there is a wide range of user
documentation for specific applications. The following information will help you
when consulting the user documentation.
Reference manual
Programming with STEP 7
Manual
Manual for programming in STL, LAD,
or FBD
Basics for programming in STEP 7
Instruction list (IL) for S7-300/400
PLCs
or
Ladder diagram (LAD) for S7-300/400
PLCs
or
Function block diagram (FBD) for
S7-300/400 PLCs
Manual for creating configurations with
ProTool
Operation of ProTool
Configuration
Screens and messages
Downloading configuration to the C7
ProTool
Configuring Windows-based systems
Manual
Approbation
For detailed information on approvals and standards, refer to Appendix A,
Technical data.
Standards
The C7-635 meets the requirements and criteria of IEC 61131-2.
Preface
vi C7-635 Control System
A5E00155581-04
Guide
This manual contains the following elements to help you access particular
information quickly and easily:
Complete table of contents at the front of the manual
Information located in the left-justified headings of each chapter page providing
an overview of section contents.
Detailed keyword index at the back of the manual
Recycling and disposal
The C7-635 system can be recycled due to its low-contaminant equipment.
Contact a certified company for the environment-friendly recycling disposal of your
electronic waste.
Additional Support
If you have questions regarding the use of the products described in the manual
and are unable to find an answer here, please contact your nearest Siemens
representative.
http://www.ad.siemens.com/automation/partner
You will find a guide to the technical documentation offered for the individual
SIMATIC Products and Systems here at:
http://www.siemens.com/simatic–tech–doku–portal
Training Center
To facilitate getting started with the SIMATIC C7 automation system, we offer
suitable courses. Please contact your regional Training Center or the main Training
Center in D90327 Nuremberg, Germany.
Telephone: +49 (911) 895-3200
Internet: http://www.sitrain.com
Preface
vii
C7-635 Control System
A5E00155581-04
A&D Technical Support
Worldwide, available 24 hours a day:
Johnson City
Nuernberg
Beijing
Technical Support
Worldwide (Nuernberg)
Technical Support
24 hours a day, 365 days a year
Phone: +49 (180) 5050-222
Fax: +49 (180) 5050-223
mailto:adsupport@siemens.com
GMT: +1:00
Europe / Africa (Nuernberg)
Authorization
Local time: Mon.-Fri.
8:00 AM to 5:00 PM
Phone: +49 (180) 5050–222
Fax: +49 (180) 5050-223
mailto:adsupport@siemens.com
GMT: +1:00
United States (Johnson City)
Technical Support and
Authorization
Local time: Mon.-Fri.
8:00 AM to 500 PM
Phone: +1 (423) 262 2522
Fax: +1 (423) 262 2289
mailto:simatic.hotline@sea.siemens.com
GMT: –5:00
Asia / Australia (Beijing)
Technical Support and
Authorization
Local time: Mon.-Fri.
8:00 AM to 5:00 PM
Phone: +86 10 64 75 75 75
Fax: +86 10 64 74 74 74
mailto:adsupport.asia@siemens.com
GMT: +8:00
The languages of the SIMATIC Hotlines and the authorization hotline are generally German and English.
Preface
viii C7-635 Control System
A5E00155581-04
Service & Support on the Internet
In addition to our documentation, we offer our Know-how online on the internet at:
http://www.siemens.com/automation/service&support
where you will find the following:
The newsletter, which constantly provides you with up-to-date information on
your products.
The right documents via our Search function in Service & Support.
A forum, where users and experts from all over the world exchange their
experiences.
Your local representative for Automation & Drives.
Information on field service, repairs, spare parts and more under “Services”.
ix
C7-635 Control System
A5E00155581-04
Contents
1 Document Guide 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Product Overview 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Configuration and Structure 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 C7-635 Components and Accessories 2-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Installing and Wiring the C7-635 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Labeling Strips (C7-635 Key only) Labeling Strips 3-1. . . . . . . . . . . . . . . . . . . .
3.2 Mechanical Installation 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Locating the C7-635 in a Mechanical Environment 3-10. . . . . . . . . . . . . . . . . . .
3.4 Setting Up the Electrical Configuration and Connector Pin Assignment 3-11.
3.5 Guidelines for Fail-Safe Construction 3-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6 Connecting Shielded Cables 3-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7 Coding Connector Parts to Prevent Incorrect Usage 3-25. . . . . . . . . . . . . . . . .
4 Special Features of the C7-635 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Operating Mode Selection 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Status and Error Displays of the C7-635 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Arrangement of additional S7-300 modules 4-5. . . . . . . . . . . . . . . . . . . . . . . . .
4.4 Status Display of the Digital Onboard I/O 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Maintenance 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Cleaning the Monitor 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Replacing the C7-635 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A Technical Specifications A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1 Technical Specifications for Complete Apparatus A-1. . . . . . . . . . . . . . . . . . . .
A.2 Technical Specifications for TP/OP A-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.3 Technical Specifications for CPU A-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.4 Technical Specifications for Integrated I/O A-14. . . . . . . . . . . . . . . . . . . . . . . . . .
A.5 Notes on Power Supply A-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.6 Approvals A-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.7 Notes on CE Marking A-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.8 Notes for Machine Manufacturers A-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index Index-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
xC7-635 Control System
A5E00155581-04
Figure
2-1 C7-635 Touch 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 C7-635 Key 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Components and interfaces of the C7-635 2-4. . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 Inserting labeling strips for C7-635 Key 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Mechanically Fastening the C7-635 Touch 3-4. . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Dimension Drawings for the C7-635 Touch (Measurements in mm) 3-4. . . . .
3-4 Dimension Drawings for the C7-635 Key (Measurements in mm) 3-5. . . . . .
3-5 Dimension Drawings for the C7-635 Touch (Measurements in mm) 3-6. . . . .
3-6 Dimension Drawings for the C7-635 Touch (Measurements in mm) 3-7. . . . .
3-7 Dimension Drawings for the C7-635 Key (Measurements in mm) 3-8. . . . . .
3-8 Dimension Drawings for the C7-635 Key (Measurements in mm) 3-9. . . . . .
3-9 Installation Clearances When Mounting the C7-635 Touch 3-10. . . . . . . . . . . .
3-10 Installation Clearances when Mounting the C7-635 Key 3-10. . . . . . . . . . . . . . .
3-11 C7-635 Touch with Connectors and Sockets, Front View 3-11. . . . . . . . . . . . . .
3-12 C7-635 with Connectors and Sockets, Back View 3-12. . . . . . . . . . . . . . . . . . . .
3-13 C7-635 Layout of Connector Pin Assignment 3-13. . . . . . . . . . . . . . . . . . . . . . . .
3-14 C7-635 with Connectors and Sockets, Side View 3-13. . . . . . . . . . . . . . . . . . . .
3-15 C7-635 with Connectors and Sockets, Bottom View 3-15. . . . . . . . . . . . . . . . . .
3-16 C7-635 with Connectors and Sockets, Side View 3-19. . . . . . . . . . . . . . . . . . . .
3-17 C7-635 with grounding busbar, shielding terminals,
and terminal for functional ground 3-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-18 Preventing Incorrect Usage of Connectors 3-25. . . . . . . . . . . . . . . . . . . . . . . . . .
4-1 C7-635 Touch 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Connecting Additional S7-300 Modules Directly on the Device Using
the 2-Module I/O Set 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Connecting Additional S7-300 Modules Directly on the Device Using
the 2-Module I/O Set 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 Connecting Additional S7-300 Modules at a Distance of Up to 1.5 m 4-8. . .
4-5 DI/DO Status Display 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table
3-1 Mechanical Installation 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Supply Connector X1 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Programming Device Connection (MPI) 2 3-14. . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 DP Connection X3 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 RS232 Connection X4 3-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6 Connector Pin Assignment I/O Connector X10 3-16. . . . . . . . . . . . . . . . . . . . . .
3-7 Connector Pin Assignments I/O Connector X11 3-17. . . . . . . . . . . . . . . . . . . . .
3-8 Connector Pin Assignments I/O Connector X12 3-18. . . . . . . . . . . . . . . . . . . . .
3-9 Connector Pin Assignment I/O Connector X13 3-19. . . . . . . . . . . . . . . . . . . . . .
3-10 Connector Pin Assignments Analog Output X 14 3-20. . . . . . . . . . . . . . . . . . .
3-11 Cables for Connection to C7-635 3-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1 Operating Mode Keys 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Description of the DI/DO Status Display in Figure 4-5 4-9. . . . . . . . . . . . . . . .
A-1 Technical Specifications for C7-635 A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-2 Functional Scope of TP/OP A-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
C7-635 Control System
A5E00155581-04
Document Guide
This guide lists the most important topics and indicates which manuals in the
documentation package contain relevant information for each topic.
Information Location
(This Manual)
Reference
Product Overview Chapter 2
Mounting and Wiring Chapter 3
Special Features of the C7-635 Chapter 4
Control and Display Elements CPU 31xC and CPU 31x,
Technical data
Memory
SIMATIC Micro Memory Card (MMC)
for the CPU
CPU 31xC and CPU 31x,
Technical data
CPU Memory Concept CPU 31xC and CPU 31x,
Technical data
Compact Flash Card (CF-Card)
for the TP/OP
Touch Panel TP170 A, TP170 B,
Operator Panel OP170 B,
Chapter 12
Commissioning the HMI Portion Touch Panel TP170 A, TP170 B,
Operator Panel OP170 B,
Chapter 3
Operating the Device Touch Panel TP170 A, TP170 B,
Operator Panel OP170 B,
Chapter 4
Data Areas for Communication
between C7-OP and C7-CPU
SIMATIC HMI, Communication for
Windows-Based Systems,
Chapter 7
Screen Objects Touch Panel TP170 A, TP170 B,
Operator Panel OP170 B,
Chapter 7
System Settings Touch Panel TP170 A, TP170 B,
Operator Panel OP170 B,
Chapter 9
Maintenance Chapter 5
Technological Functions S7-300 Automation System
CPU 31xC
Technological Functions
Technical Specifications Appendix A
Scope of Functions Appendix A
1
Document Guide
1-2 C7-635 Control System
A5E00155581-04
2-1
C7-635 Control System
A5E00155581-04
Product Overview
2.1 Configuration and Structure
Figure 2-1 C7-635 Touch
2
Product Overview
2-2 C7-635 Control System
A5E00155581-04
Figure 2-2 C7-635 Key
Product Overview
2-3
C7-635 Control System
A5E00155581-04
Components
The SIMATIC C7-635 consists of the following components:
SIMATIC S7 314C-2 DP CPU
SIMATIC touch panel TP170 B or operator panel OP170 B
Interfaces
SIMATIC C7-635 interfaces:
An interface for connecting up to four S7-300 modules via the S7-300 I/O bus
Integrated digital and analog I/O (CPU 314C-2DP I/O)
DP interface for the communication with nodes on a PROFIBUS DP network
MPI interface for the communication with a PG/PC and further S7 CPUs, C7
control systems and OPs
RS232 interface (e.g. as printer port)
Micro Memory Card (MMC)
Compact Flash Card (CF Card)
Product Overview
2-4 C7-635 Control System
A5E00155581-04
C7-635
Integrated
I/O
DP
interface
RS232
interface
C7-PLC C7-TP/OP
CPU memory
C7-CPU
TP/OP memory
STEP 7
ProTool
S7-300
I/O bus
expansion
MPI
interface
C7-TP/OP
MMC CF-
Card
Figure 2-3 Components and interfaces of the C7-635
Plug-In Modules on the S7-300 I/O Bus
Note
I/O expansions can be interconnected via the S7 300 I/O bus without IM interface
module using the following accessories:
2-module I/O set: Expansion with up to two S7 300 modules
4-module I/O set: Expansion with up to four S7 300 modules
You can add an IM-360 interface module in order to connect up to three expansion
rows for a maximum of 23 S7 300 modules.
Product Overview
2-5
C7-635 Control System
A5E00155581-04
Interplay of CPU and TP/OP
The individual components integrated in the SIMATIC C7-635 correspond to the
components that can also be used for modular configurations consisting of
CPU-314C-2DP, TP170 B, and OP170 B.
The basic mode of operation is also similar to operation of a configuration with
standard modules from the programmable controller and TP/OP family; the
individual components function independently, and each processor has its own
dedicated memory.
The C7-CPU and the C7-TP/OP communicate internally over the MPI interface.
The C7-CPU is independent of the C7-TP/OP. The C7-TP/OP continues to run, for
example, if the C7-CPU enters the STOP mode.
Programming and Configuration
Note
The C7-CPU and the C7-TP/OP each have their own MPI address. Therefore, you
program and configure these components in exactly the same way as independent
CPU and TP/OP components.
These items are addressed explicitly in the manual, as necessary.
You program the C7-635 Touch with STEP 7 as of V 5.2 + Service Pack 1 +
Hardware Update C7-635 Touch V2.0.
You program the C7-635 Key with STEP 7 as of V 5.2 + Service Pack 1 +
Hardware Update C7-635 Key V2.0.
The programming languages you can use are listed in the CPU 31xC and
CPU 31x, Technical data manual.
The C7-635 is configured with ProTool, ProTool/Lite, or ProTool/Pro starting with
V 6.0 + Service Pack 1.
The tools run on a programming device or PC under Windows.
Product Overview
2-6 C7-635 Control System
A5E00155581-04
CPU
The user program controlling the process runs on the C7-635.
The following functional units determine the mode of operation of the C7-635:
Loading memory
The loading memory is located on the Micro Memory Card (MMC) and contains
the user program.
Processor
The processor executes the program cyclically:
At the beginning of the cycle, the processor reads the signal states on all
inputs and generates a process image of the inputs (PII).
The program is executed step-by-step using internal counters, bit memory,
and timers.
The processor stores the calculated signal states in the process output
image (POI). At the end of the cycle, the process image is transmitted to the
outputs.
Touch Panel/Operator Panel
The touch panel and the operator panel of the C7-635 are based on the standard
Windows CE operating system. You can visually display operating modes, current
process values, and faults. You can also make entries on the C7-635. Simple
machine diagnostic functions are also possible.
You can also incorporate your own graphics, digital pictures, and scanned images
into your project. Moreover, you can represent elements such as temperature
variations graphically using bar graphs and diagrams.
Scope of Functions
CPU
64 Kbytes of CPU user memory
Various sizes of loading memory and retentive memory in the Micro Memory
Card
Integrated I/O
24 DI
16 DO
–4 AI
–2 AO
1 PT 100
Product Overview
2-7
C7-635 Control System
A5E00155581-04
Technological functions
Positioning with an analog output or digital outputs
Counting, frequency measurements, or pulse width modulation (only two
channels are available when the positioning function is used)
Closed loop control
PROFIBUS-DP interface
Touch Panel/Operator Panel
32 Kbytes of internal memory for recipes can be expanded with Compact Flash
Card (CF Card); 768 Kbytes of internal configuration memory.
Password Protection
Input/output fields for displaying and modifying process parameters
Configurable buttons and function keys (C7-635 Key) for controlling input/output
and data bits
Bar graphs for graphics-based display of dynamic values
Standard library for graphics and buttons that can be used in ProTool CS
Graphics that can be used to label buttons or configured as format-filling
background images
Permanent text for labelling buttons, process images, and process values in
any font size
Print functions
Message editing
Curves
Interrupt timer
Recipe management
Backup of recipe data and configurations on optional memory card (CF card)
You will find a complete overview of the scope of functions in Appendix A.
Product Overview
2-8 C7-635 Control System
A5E00155581-04
2.2 C7-635 Components and Accessories
Components
The following components are supplied with the C7-635:
1 C7-635 Touch (6ES7635-2EB01-0AE3) with sealing or
1 C7-635 Key (6ES7635-2EC01-0AE3) with sealing
1 grounding busbar, including two mounting screws and six shielding terminals
10 brackets
Additional Devices and Tools Required to Operate the C7-635
You need the following devices and tools:
A Micro Memory Card (MMC) to store the CPU user program that is
programmed with STEP 7. The C7-635 can only be operated with an MMC.
A Compact Flash Card (CF Card) for the TP/OP if you require more than
32 Kbytes of memory for recipes or if the C7-635 is to be replaceable without a
programming device/PC
24 V power supply
Connector set (screw terminals or spring-type terminals) for C7 I/O with coding
profiles and coding tabs
C7-635 accessory for I/O expansion (directly on the device, or at a distance of
1.5 m), in case you would like to expand the I/O.
A programming device or PC with:
An MPI interface and an MPI cable to generate the user program, or
alternatively, a programming device/PC with the capability of reading and
writing to a CF Card
An RS232 interface and RS232 cable (zero modem cable)
For C7-635 Touch, STEP 7 as of Version 5.2 + Service Pack 1 + Hardware
Update C7-635 Touch V2.0
For C7-635 Key, STEP 7 as of Version 5.2 + Service Pack 1 + Hardware
Update C7-635 Key V2.0
The configuration tool ProTool, ProTool/Lite or ProTool/Pro starting with
V 6.0 + Service Pack 1
Product Overview
2-9
C7-635 Control System
A5E00155581-04
Accessories
The following components can be ordered as C7-635 accessories:
I/O set with two modules for I/O expansion directly on the device
6ES7635-0AA00-6AA0
Consisting of:
A cable, approximately 0.25 m (for connecting the C7-635 to the S7 module)
A cable, approximately 0.08 m (for connecting the S7 module to the
S7 module)
Mounting plate with S7 DIN rails including four Kombitorx screws (screwed
to the back of the device)
I/O set with four modules for I/O expansion directly on the device
6ES7635-0AA00-6BA0
Consisting of:
A cable, approximately 0.20 m
S7 DIN rail, 190 mm including 4 countersunk screws (screwed to the back of
the device)
Cable, 1.5 m, for I/O expansion up to a maximum distance of 1.5 m
6ES7635-0AA00-6CA0
You must order a standard DIN rail for the S7-300 programmable controller in
addition.
Connector set with screw terminals for C7 I/O with coding profiles and
coding carriers 6ES7635-0AA00-4AA0 or
Connector set with spring-loaded terminals for C7 I/O with coding profiles
and coding carriers 6ES7635-0AA00-4BA0
Grounding bar with shielding terminals for analog I/O
6ES7635-0AA00-6EA0
Protective film for the C7-635 display
6AV6574-1AD00-4AX0
Paper documentation C7-635 control system
Consisting of:
C7-635 manual in the following languages:
German: 6ES7635-1AA00-8AA0
English: 6ES7635-1AA00-8BA0
French: 6ES7635-1AA00-8CA0
Spanish: 6ES7635-1AA00-8DA0
Italian: 6ES7635-1AA00-8EA0
Product Overview
2-10 C7-635 Control System
A5E00155581-04
Paper documentation C7-635 control systemdocumentation package
Consisting of:
C7-635 manual
Manuals for CPU 314C-2 DP
Touch Panel TP170 A TP170 B, Operator Panel OP170 Bmanual
Communication for Windows-Based Systems manual)
in the following languages:
German: 6ES7635-1EA00-8AA0
English: 6ES7635-1EA00-8BA0
French: 6ES7635-1EA00-8CA0
Spanish: 6ES7635-1EA00-8DA0
Italian: 6ES7635-1EA00-8EA0
The following components can be ordered as C7 accessories:
MPI cable 6ES7901-0BF00-0AA0 (for connecting the C7 to the programming
device)
PC adapter 6ES7972-0CA23-0XA0 (for connecting the C7 to the PC)
RS232 cable 6ES7901-1BF00-0XA0 (zero modem cable)
Spare Parts
Service pack (gasket and 10 mounting supports) 6ES7635-0AA00-3AA0.
The gasket has to be replaced every time the C7-635 is installed/uninstalled.
3-1
C7-635 Control System
A5E00155581-04
Installing and Wiring the C7-635
3.1 Labeling Strips (C7-635 Key only) Labeling Strips
The function keys can be labeled individually with labeling strips that are inserted in
the keyboard from below.
System-Specific Labeling
The template for the labeling strips is provided with ProTool (V6.0 + Service
Pack 2, directory Utilities) or can be obtained from the Internet. With it, you can
design and print out system-specific labeling strips easily.
Internet address: www.siemens.com/automation/service&support
The file “SLIDE635.DOC” with the labeling strips can be obtained by selecting
Product Support > Automation Systems > SIMATIC Industrial Automation Systems
> PLC > SIMATIC C7 > Control Systems > Downloads
To make your own labeling strips, use transparent film (0.1 to 0.15 mm thick) so
that the LEDs in the function keys remain visible. Label the film using either a
printer or a wipe-resistant foil pen.
!Caution
To prevent the keyboard from smudging on the inside, the labeling must be
covered with a transparent adhesive strip or a transparent adhesive film.
Otherwise, operating pressure causes the labeling color to rub off on the inside of
the key. A key that has been smudged from the inside cannot be cleaned and can
only be replaced at the factory.
The labeling strips have to be cut exactly along the indicated cutting edge. If the
labeling strip is cut too large, it cannot be inserted.
3
Installing and Wiring the C7-635
3-2 C7-635 Control System
A5E00155581-04
The strip is inserted as follows:
Step Action
1. Place the device with the front plate facing downward.
2. Remove any labeling strips that have been previously inserted.
3. With the labeling pointing downward, insert the new labeled strips into the slits
on the front panel (use tweezers, if necessary). The position of the eight labeling
strips is marked in Figure 3-1 with arrows.
Labeling strips
Figure 3-1 Inserting labeling strips for C7-635 Key
Installing and Wiring the C7-635
3-3
C7-635 Control System
A5E00155581-04
3.2 Mechanical Installation
Mounting
The C7-635 is intended for stationary and enclosed installation in a control cabinet
door.
Note
You can only achieve the degree of protection IP65/NEMA 4X if you follow steps 1
through 5 during installation.
!Caution
The inserted CF card protrudes from the C7-635 and could therefore be damaged.
Prior to the removal and installation of the device, remove the Micro Memory Card
(MMC) of the CPU and the Compact Flash Card (CF Card) of the OP.
!Caution
Condensation may develop on the device when you take it from a cold
environment to the operating area.
Before you start it, allow the device to become acclimatized to room temperature.
If condensation has developed, the device may not be switched on until it is
completely dry.
Mounting is performed as follows:
Table 3-1 Mechanical Installation
Step Action
1. C7-635 Touch:
Make a cutout in the control cabinet door
(dimensions 231+1.0 x 183+1.0 mm). See Figure 3-3.
C7-635 Key:
Make a cutout in the control cabinet door
(dimensions 231+1.0 x 257+1.0 mm). See Figure 3-4.
2. Ensure that no Compact Flash Card (CF Card) is inserted into the C7-635.
The CF Card protrudes from the C7-635 and could be damaged when the
device is installed.
3. Place the C7-635 in the prepared cutout in the control cabinet door. Ensure
that the gasket is applied evenly to the metal plate.
4. Guide the fastening hooks of the provided mounting supports À (for the
C7-635 Touch, 8 mounting supports; for the C7-635 Key, 10 mounting
supports) into the intended recesses in the C7-635 housing. Figure 3-2
provides an example of the mechanical fastening of the C7-635 Touch.
Installing and Wiring the C7-635
3-4 C7-635 Control System
A5E00155581-04
Table 3-1 Mechanical Installation, continued
Step Action
5. Using a screwdriver, tighten the C7-635 evenly and crosswise from behind
in the control cabinet door until the front panel of the C7-635 rests on the
control cabinet door Á. Situate the device so that there is even spacing on
all sides between the housing and the cutout section ®.
1
2
3
Control
cabinet
door
Figure 3-2 Mechanically Fastening the C7-635 Touch
199
260
79
231+1.0
183+1.0
Cutout in control
cabinet door
Figure 3-3 Dimension Drawings for the C7-635 Touch (Measurements in
mm)
Installing and Wiring the C7-635
3-5
C7-635 Control System
A5E00155581-04
273,8
260
80
231+1.0
Cutout in control
cabinet door
257+1.0
Figure 3-4 Dimension Drawings for the C7-635 Key (Measurements in mm)
Installing and Wiring the C7-635
3-6 C7-635 Control System
A5E00155581-04
124
88
152
117
Figure 3-5 Dimension Drawings for the C7-635 Touch (Measurements in mm)
Installing and Wiring the C7-635
3-7
C7-635 Control System
A5E00155581-04
Figure 3-6 Dimension Drawings for the C7-635 Touch (Measurements in mm)
Installing and Wiring the C7-635
3-8 C7-635 Control System
A5E00155581-04
Siemens
Figure 3-7 Dimension Drawings for the C7-635 Key (Measurements in mm)
Installing and Wiring the C7-635
3-9
C7-635 Control System
A5E00155581-04
Figure 3-8 Dimension Drawings for the C7-635 Key (Measurements in mm)
Installing and Wiring the C7-635
3-10 C7-635 Control System
A5E00155581-04
3.3 Locating the C7-635 in a Mechanical Environment
Locating the C7-635
When installing a C7-635, pay attention to the following:
The sheet thickness of a control cabinet door can be 2 to 4 mm. You must
ensure that the gasket seals tightly around the entire device.
A distance of at least 50 mm and 70 mm respectively must be maintained on
the sides of the C7-635 for outgoing cables and to allow for air circulation, as is
shown in Figure 3-9.
Make sure the gasket is correctly seated on the front panel.
The C7-635 must be protected from direct exposure to sunlight (the device
should not be operated outside of enclosed areas).
50
50
70 70
Figure 3-9 Installation Clearances When Mounting the C7-635 Touch
50
50
70 70
Figure 3-10 Installation Clearances when Mounting the C7-635 Key
Installing and Wiring the C7-635
3-11
C7-635 Control System
A5E00155581-04
3.4 Setting Up the Electrical Configuration and Connector Pin
Assignment
Connector Pin Assignment of the C7-635
Tables 3-2 to 3-10 indicate the connector pin assignment of the C7-635. The
figures show the C7-635 Touch as an example. Connector and socket positions
are identical for the C7-635 Key.
!Caution
For functional reasons, the connector pin assignment is not compatible with
predecessor products C7-621, C7-623, C7-626, C7-633, and C7-634.
Note
The C7-635 cannot be used in an ungrounded configuration.
I/O connector
DI 16 X 11 in front
DO 16 X 12 in back
Analog
output
AO2
X14
Supply
Connector
X 1
Micro
Memory
Card of
the CPU
X 7
Back-
plane bus
(I/O bus)
X 5 in
back
I/O connector
Supply I/O DI 8 X 10 in front
AI4 + 1 PT100 X 13 in back
Compact
Flash Card
of the TP
X 8
PROFIBU
S/DP
X 3 in front
Program-
ming device
connection
(MPI)
X 2 in back
RS 232
X 4 in front
1
11
1
Figure 3-11 C7-635 Touch with Connectors and Sockets, Front View
Installing and Wiring the C7-635
3-12 C7-635 Control System
A5E00155581-04
R
SIMATIC C7
S
M
I/O connector
DO 16 X 12 in front
DI 16 X 11 in back
Analog
output
AO2
X14
Supply
Connector
X 1
Micro
Memory Card
of the CPU
X 7
Backplane
bus (I/O
bus) X 5 in
front
FRCE
5 VDC
BF
RUN
STOP
SF
I/O connector
AI4 + 1 PT100 X 13 in front
Supply I/O DI 8 X 10 in back
Compact
Flash
Card of
the TP
X 8
PROFIBUS/
DP
X 3 in back
Programming
device
connection
(MPI)
X 2 in front
RS 232
X 4 in
back 1
11
1
Figure 3-12 C7-635 with Connectors and Sockets, Back View
Installing and Wiring the C7-635
3-13
C7-635 Control System
A5E00155581-04
Figure 3-13 C7-635 Layout of Connector Pin Assignment
Supply Connector
X 1
Micro Memory Card (MMC) of
the CPU X 7
PROFIBUS/DP
X 3
Programming device
connection (MPI)
X 2
1
Figure 3-14 C7-635 with Connectors and Sockets, Side View
Installing and Wiring the C7-635
3-14 C7-635 Control System
A5E00155581-04
Supply connector X1
Table 3-2 Supply Connector X1
Pin
Name
Signal Description
1AT2 Authorization input (for example, for external switch)
2AT1 Authorization input (for example, for external switch)
3 M Ground 24 V
4L+ Supply voltage 24 VDC
Programming Device Connection (MPI) 2
Table 3-3 Programming Device Connection (MPI) 2
Pin Name Signal Description
1NC Not connected
2M24V Ground 24 V
3 B RS 485 cable B
4RTS RTS
5M5V Ground 5 V
6P5V Supply voltage 5 V
7P24V MPI Supply voltage 24 V MPI
8 A RS 485 cable A
9NC Not connected
DP Connection X3
Table 3-4 DP Connection X3
Pin Name Signal Description
1NC Not connected
2M24V Ground 24 V
3 B RS 485 cable B
4RTS RTS
5M5V Ground 5 V
6P5V Supply voltage 5 V
7P24V DP Supply voltage 24 V DP
8 A RS 485 cable A
9NC Not connected
Installing and Wiring the C7-635
3-15
C7-635 Control System
A5E00155581-04
RS 232 X4
Table 3-5 RS232 Connection X4
Pin Name Signal Description
1DCD Received detector
2RXD Received data
3TXD Transmitted data
4 DTR Data terminal ready
5 GND Ground 5 V
6DSR Data set ready
7RTS Request to send
8 CTS Clear to send
9NC Not connected
Supply I/O DI 8 X 10
11
11
AI4 + 1 PT100 X 13 DO 16 X 12
DI 16 X 11
Figure 3-15 C7-635 with Connectors and Sockets, Bottom View
Installing and Wiring the C7-635
3-16 C7-635 Control System
A5E00155581-04
I/O connector X10
Table 3-6 Connector Pin Assignment I/O Connector X10
Pin Name Signal Description
1 DI+2.0 Digital input 16
2 DI+2.1 Digital input 17
3 DI+2.2 Digital input 18
4 DI+2.3 Digital input 19
5 DI+2.4 Digital input 20
6 DI+2.5 Digital input 21
7 DI+2.6 Digital input 22
8 DI+2.7 Digital input 23
92L+ 24 V supply voltage for DO 0.0 to 0.7
10 2L+ 24 V supply voltage for DO 0.0 to 0.7
11 2M Ground for DO 0.0 to 0.7
12 3L+ 24 V supply voltage for DO 1.0 to 1.7
13 3L+ 24 V supply voltage for DO 1.0 to 1.7
14 3M Ground for DO 1.0 to 1.7
15 1L+ 24 V supply voltage for DI 0.0 to 1.7
16 1M Ground for DI 0.0 to 2.7
Installing and Wiring the C7-635
3-17
C7-635 Control System
A5E00155581-04
I/O Connector X 11
For the technological functions, the meaning of the inputs is described in the
columns “Counting”, “Frequency Measuring”, “Pulse Width Modulation”, “Analog
Positioning”, and “Digital Positioning”.
Table 3-7 Connector Pin Assignments I/O Connector X11
Pin
Name
Signal Description Counting Frequency
Measuring
Pulse
Width
Modulation
Analog
Positioning
Digital
Positioning
1 DI+0.0 Digital input 0 Channel 0: Trace
A/Pulse
Sensor Signal A
2 DI+0.1 Digital input 1 Channel 0: Trace
B/Direction
Sensor Signal B
3 DI+0.2 Digital input 2 Channel 0: Hardware Gate Sensor Signal N
4 DI+0.3 Digital input 3 Channel 1: Trace
A/Pulse
Length Measurement
5 DI+0.4 Digital input 4 Channel 1: Trace
B/Direction
Home position switch
6 DI+0.5 Digital input 5 Channel 1: Hardware Gate
7 DI+0.6 Digital input 6 Channel 2: Trace
A/Pulse
8 DI+0.7 Digital input 7 Channel 2: Trace
B/Direction
9 DI+1.0 Digital input 8 Channel 2: Hardware Gate
10 DI+1.1 Digital input 9 Channel 3: Trace
A/Pulse
11 DI+1.2 Digital input 10 Channel 3: Trace
B/Direction
12 DI+1.3 Digital input 11 Channel 3: Hardware Gate
13 DI+1.4 Digital input 12 Channel
0: Latch
14 DI+1.5 Digital input 13 Channel
1: Latch
15 DI+1.6 Digital input 14 Channel
2: Latch
16 DI+1.7 Digital input 15 Channel
3: Latch
Installing and Wiring the C7-635
3-18 C7-635 Control System
A5E00155581-04
I/O Connector X 12
For the technological functions, the meaning of the outputs is described in the
columns “Counting”, “Frequency Measuring”, “Pulse Width Modulation”, “Analog
Positioning”, and Digital Positioning”.
Table 3-8 Connector Pin Assignments I/O Connector X12
Pin
Name
Signal Description Counting Frequency
Measuring
Pulse Width
Modulation
Analog
Positioning
Digital
Positioning
1 DO+0.0 Digital
output 0
Channel 0: Output
2 DO+0.1 Digital
output 1
Channel 1: Output
3 DO+0.2 Digital
output 2
Channel 2: Output
4 DO+0.3 Digital
output 3
Channel 3: Output
5 DO+0.4 Digital
output 4
6 DO+0.5 Digital
output 5
7 DO+0.6 Digital
output 6
CONV_
EN
Enable
power
section
8 DO+0.7 Digital
output 7
9 DO+1.0 Digital
output 8
Q0
10 DO+1.1 Digital
output 9
Q1
11 DO+1.2 Digital
output 10
Q2
12 DO+1.3 Digital
output 11
Q3
13 DO+1.4 Digital
output 12
14 DO+1.5 Digital
output 13
15 DO+1.6 Digital
output 14
16 DO+1.7 Digital
output 15
Installing and Wiring the C7-635
3-19
C7-635 Control System
A5E00155581-04
I/O connector X13
Table 3-9 Connector Pin Assignment I/O Connector X13
Pin Name Signal Description
1AI0-U Analog voltage input channel 0
2AI0-IAnalog current input channel 0
3AI0-CAnalog reference potential channel 0
4AI1-U Analog voltage input channel 1
5AI1-IAnalog current input channel 1
6AI1-CAnalog reference potential channel 1
7AI2-U Analog voltage input channel 2
8AI2-IAnalog current input channel 2
9AI2-CAnalog reference potential channel 2
10 AI3-U Analog voltage input channel 3
11 AI3-IAnalog current input channel 3
12 AI3-CAnalog reference potential channel 3
13 MANA Analog ground
14 MANA Analog ground
15 AIR-PPT100_OUT
16 AIR-NPT100_IN
R
S
M
Analog output AO2
X14
Backplane bus (I/O bus) X 5
Compact Flash Card
of the TP
X 8
RS 232
X 4
1
Figure 3-16 C7-635 with Connectors and Sockets, Side View
Installing and Wiring the C7-635
3-20 C7-635 Control System
A5E00155581-04
Analog output X14
For the technological functions, the meaning of the outputs is described in the
column “Analog Positioning”.
Table 3-10 Connector Pin Assignments Analog Output X 14
Pin Name Signal Description Analog Positioning
1AO0_U Analog voltage output
channel 0
Voltage output
Power section
2AO0_I Analog current output
channel 0
Current output
Power section
3 MANA Analog ground Analog ground
4AO1_U Analog voltage output
channel 1
5AO1_I Analog current output
channel 1
6 MANA Analog ground Analog ground
Installing and Wiring the C7-635
3-21
C7-635 Control System
A5E00155581-04
C7-635 Device Connections
You can use the following cables to connect the C7-635 to other components:
Table 3-11 Cables for Connection to C7-635
Connecting Cable Length Special
Features
Illustration Connection
S7-300 I/O Bus
I/O expansion cable 0.25 m
1.5 m
-C7-635 S7-300
rack
MPI Interface
Programming device (PG) cable 5 m -For example:
C7-635 PG
C7-635 S7-300
C7-635 S7-400
PROFIBUS-DP interface
PROFIBUS bus cable
Indoor cable,
buried cable,
and bus connector,
without programming port,
with programming port
and PROFIBUS bus terminal RS 485,
with 1.5 m cable, with 3 m cable,
with programming port and
1.5 m cable
-Self-made
cable
C7 PG/PC
C7 C7
C7 S7-300
C7 S7-400
Serial interface (RS 232 (V.24))
Serial cable (printer cable) See cata-
log
ST80.1
C7 printer
IM361
IM361 cable -C7 Additional I/O
(S7-300)
C7-635 I/O connections
Connectors for C7-635 I/O
Cable cross section
16-pin
6-pin
4-pin
0.2 to 2.5
mm2
C7 External
sensing elements/
actuators
Installing and Wiring the C7-635
3-22 C7-635 Control System
A5E00155581-04
3.5 Guidelines for Fail-Safe Construction
Overview
Shielding measures must be implemented in an automation system to prevent
faults. This can only be ensured by use of an enclosed metal construction (cabinet
mounting, for example).
Low frequency (LF) or high frequency (HF) interference signals can reach the
internal bus of the controller if the system is not grounded or shielded properly,
causing a malfunction.
Interference signals can also be caused when relays or contactors switch (very
rapid changes in current or voltage; HF interference signals) or when two
components of system have different grounding potentials (LF interference
signals).
Note
You can find additional information about construction guidelines in the S7-300,
CPU 31xC and CPU 31x: Hardware and Installation manual.
Use/Installation of Fail-Safe Cables
Only shielded cables are permitted for all analog signals.
Cable shielding must be grounded on both sides for:
Controller cables
Bus cables
I/O device cables
Standard cables from Siemens comply with these requirements.
All plug connections must be screwed or clamped into place.
Signal lines must not be laid parallel to heavy current lines. A separate cable
channel must be used that is separated from heavy current lines by at least
50 cm.
Installing and Wiring the C7-635
3-23
C7-635 Control System
A5E00155581-04
Cabinet Design
Devices that could introduce interference signals from outside into the cabinet
must be placed far below the cabinet. The grounding terminal must be placed
immediately at the cabinet entrance to directly ground cables capable of carrying
interference signals. All shielded cables must be laid here with the shield. For
double-shielded signal lines, only the outer shield is to be laid here.
Long signal lines must be installed along the cabinet walls. It is important to use an
EMC-compliant cabinet construction to reduce disturbance variables. All chassis
ground connections in the cabinet are to be made with a large cable cross section
and laid over a large surface.
Analog devices located in the control cabinet must be isolated and grounded at a
point in the cabinet (use a copper strip).
The materials used should always contain the same type of metal (as a rule, do
not use aluminum due to the risk of oxidation).
All doors and plates (side walls, back wall, and ceiling) of the cabinet must be
connected at least three times with cabinet framework (short, unpainted
connections over a large surface).
Note
The following applies for systems that generate large amounts of
electrostaticenergy (such as textile machines and special construction machines):
The grounding conductors of the machine parts exposed to interference signals
are to be connected to a special functional ground separated from the central
grounding point of the cabinet (surface grounding with building construction,
sheathing).
Functional Ground
Connect the functional ground (see Figure 3-17) to the cabinet ground with a
cable lug and a cable with a minimum cross section of 4 mm2.
Installing and Wiring the C7-635
3-24 C7-635 Control System
A5E00155581-04
3.6 Connecting Shielded Cables
Overview
This section describes how to connect the shield of shielded signal lines to the
ground. A grounding terminal is used to connect the shield directly to the ground of
the C7-635.
Procedure
Proceed as follows to install the grounding terminal supplied with the C7-635 and
the shield terminals:
1. Mount the grounding busbar at the position shown in Fig. 3-17, using the
included screws 1 or, as an alternative, at this position 2.
2. Install the shielding terminals on the grounding busbar as shown in Fig. 3-17.
3. Push the stripped ends of the cable shielding into the shielding terminals.
Shielding
terminal
Functional
ground
2
2
1
Figure 3-17 C7-635 with grounding busbar, shielding terminals, and terminal for functional ground
Installing and Wiring the C7-635
3-25
C7-635 Control System
A5E00155581-04
3.7 Coding Connector Parts to Prevent Incorrect Usage
You can order a connector set with coding profiles and coding tabs as an
accessory for the C7-635 (see accessories in Section 2.2).
!Caution
It is highly recommended that you code the connectors, as unintentionally using
the wrong connector may damage the device.
Coding the Connectors
The coding profiles and coding tabs (see Figure 3-18) enable you to code
connectors without loss of pole to prevent incorrect usage. Use the following
procedure:
1. Insert coding profile on connector part into the slots provided.
2. Insert coding carrier on the main housing into the corresponding recesses.
A coding profile and a coding tab facing one another prevent the connector part
from being inserted.
If a coding profile and coding carrier do not face one another, the connector part
can be inserted without difficulty.
1
2
3
4
5
6
7
8
9
10
Figure 3-18 Preventing Incorrect Usage of Connectors
Installing and Wiring the C7-635
3-26 C7-635 Control System
A5E00155581-04
4-1
C7-635 Control System
A5E00155581-04
Special Features of the C7-635
Deviations from the CPU314C-2 DP
Operating mode selection
Arrangement of additional S7-300 modules
Status display of the digital onboard I/O
User memory expanded from 48 Kbytes to 64 Kbytes
All integrated I/O inputs have a common reference ground
Deviations from TP170 /OP170 B
RS 485 interface (MPI) can not be switched to RS 422 interface
No second RS 232 interface
No DP interface to TP/OP
4
Special Features of the C7-635
4-2 C7-635 Control System
A5E00155581-04
4.1 Operating Mode Selection
Status and error LEDs Operating mode keys with touch LEDs
Figure 4-1 C7-635 Touch
Changing the C7-CPU Operating Mode
The figure above uses the C7-635 Touch as an example. The function and position
of the operating mode keys and the status and error LEDs are the same for the
C7-635 Key.
Select the CPU operating modes RUN, STOP, and MRES as follows using the
operating mode keys:
Each time you press a key, the CPU mode changes. The key must be pressed for
at least 500 ms for the change to take place and the corresponding key LED (R, S,
M) to illuminate. The key LEDs do not reflect the CPU operating mode, rather,
they indicate the setting of the operating mode keys.
The key function can be activated and deactivated by means of the external
authorization inputs AT1 and AT2 to prevent the C7-CPU operating modes from
being changed in an uncontrolled manner (for example, by unauthorized operating
staff).
Special Features of the C7-635
4-3
C7-635 Control System
A5E00155581-04
The following applies for activated operating mode selection:
You must have bridged the authorization inputs AT1/AT2
The key LEDs alongside the operating mode keys indicate the mode selector
setting
The current CPU operating status is indicated by the status LEDs
The following applies to deactivated operating mode selection:
You must leave the authorization inputs AT1 and AT2 open
The key LEDs alongside the operating mode keys are switched off
The current CPU operating status is indicated by the status LEDs
The authorization inputs are located on supply connector X1 of the C7-635
(see also Table 3-2).
Authorization activated:
AT2
AT1
M
L+
1234
X1
AT1 - AT2 bridged
Authorization deactivated:
AT2
AT1
M
L+
1234
X1
AT1 - AT2 open
Table 4-1 Operating Mode Keys
Operating
Mode
Key Description/Procedure
RUN
(R)
The C7-CPU executes the user program.
Programs and data:
Can be read out from the C7-CPU with the programming
device/PC (C7 programming device).
Can be transmitted to the S7-CPU or changed there
(programming device/PC C7).
STOP
(S)
The C7-CPU does not execute user programs.
Programs:
Can be read out from the C7-CPU with the programming
device/PC (C7 programming device/PC)
Can be transmitted to the C7-CPU and changed there
(programming device/PC C7).
Note:
STOP mode is only valid for the C7-CPU. It does not apply to the
C7-TP/OP. It is always possible to continue working with the
C7-TP/OP.
Special Features of the C7-635
4-4 C7-635 Control System
A5E00155581-04
Table 4-1 Operating Mode Keys, continued
Operating
Mode
Description/ProcedureKey
MRES
(M)
General reset
Performing a general reset of the C7-CPU (clearing the memory and
reloading the user program from the MMC) requires a special
operating mode key procedure:
1. Select STOP mode by pressing the DOWN key.
The key LED “S” illuminates, and
the CPU status LED “STOP” illuminates.
2. Select MRES mode by pressing the UP key and the DOWN key
at the same time. The “M” key LED illuminates.
3. Hold the keys down until the status LED “STOP” illuminates for
the second time and remains lit (this occurs after 3 seconds).
4. Now release the keys.
5. You must repeat pressing both keys within 3 seconds.
6. Release the keys when the ”STOP” status LED flashes rapidly
(at 2 Hz).
When the CPU has finished the general reset operation, the
“STOP” status LED stops flashing and remains lit. The CPU is
now reset and in STOP mode.
The operator actions described in the table above are only required if:
The user wants to perform a general reset of the C7-635 without the C7-635
itself giving a general reset prompt (indicated by slow flashing of the “STOP”
status LED).
The C7-635 requests a general reset itself, pressing both keys briefly is
sufficient to start the general reset process.
If the C7-635 requests a new general reset after a general reset operation has
been performed, the MMC may require formatting in certain cases. You will find
information on this subject in the S7-300, CPU 31xC and CPU 31x: Hardware and
Installation manual.
If the group error (SF) display is illuminated on the C7-635, its diagnostic buffer
has to be evaluated with the programming device/PC. More information about the
entries in the diagnostic buffer is provided in the STEP 7 Online Help.
Special Features of the C7-635
4-5
C7-635 Control System
A5E00155581-04
4.2 Status and Error Displays of the C7-635
Meaning of the Status and Error Displays
The status and error displays are explained in the sequence in which they are
arranged on the C7-635.
Display Meaning Description
SF (red) C7-635 group error
(SF)
Illuminates if there are:
Hardware errors
Firmware errors
Programming errors
Parameter assignment errors
Calculation errors
Time errors
I/O errors during internal I/O functions
For exact error determination, a programming device/PC has
to be used, and the diagnostic buffer has to be read out.
BF (red) Bus error
indication
Illuminates when there are
bus errors (physical errors)
DP interface errors
5 VDC (green) 5 VDC supply for
the C7-635
Illuminates if internal 5 VDC supply is okay.
FRCE (yellow) Reserved Illuminates when a force request is active.
RUN (green) RUN mode of the
C7-635
Illuminates when the C7-635 is processing the user program.
Flashes (2 Hz) during the C7-635 startup (in addition, the STOP
display illuminates; after the STOP display goes out, the outputs
are enabled).
STOP (yellow) STOP mode of the
C7-635
Illuminates when the C7-635 is not executing a user program
Flashes slowly when the C7-635 requests a general reset
Flashes rapidly when the C7-635 is performing a general reset.
4.3 Arrangement of additional S7-300 modules
Additional S7-300 Modules
You have the option of connecting up to four additional S7-300 modules to the
C7-635 by means of the S7-300 I/O bus. These modules can be connected either
directly on the device or at a distance of up to 1.5 m.
If you insertan IM-360 interface module, you can use it to connect additional
modules.
You will find a description of how to install S7-300 modules in the S7-300,
CPU 31xC and CPU 31x: Hardware and Installation manual.
Special Features of the C7-635
4-6 C7-635 Control System
A5E00155581-04
Connecting Additional S7-300 Modules Directly on the Device
In the figures below, the C7-635 Touch is used as an example. The installation
steps are the same for the C7-635 Key.
2-Module I/O set
As a prerequisite, you must have the “2-module I/O set” accessory specifically for
the C7-635.
Use the following procedure to connect the additional S7-300 modules:
1. Screw the mounting plate to the back wall of the C7-635 housing.
2. Install the C7-635 in the control cabinet door. Refer to the notes in Chapter 3.2
for this.
3. Connect the C7-635 to the module (inserted on the left in the figure) using the
connecting cable (0.25 m).
4. Connect the two modules using the connecting cable (0.08m).
5. Mount the modules on the S7 DIN rail.
S7-300 modules
C7-635
Mounting plate
Figure 4-2 Connecting Additional S7-300 Modules Directly on the Device Using the
2-Module I/O Set
Special Features of the C7-635
4-7
C7-635 Control System
A5E00155581-04
4-Module I/O Set
As a prerequisite, you must have the “4-module I/O set” accessory specifically for
the C7-635.
Use the following procedure to connect the additional S7-300 modules:
1. Bolt the S7 DIN rail (190 mm) to the back wall of the C7-635.
2. Install the C7-635 in the cabinet door. Follow the instructions in chapter 3.2
3. Connect the C7-635 to the outermost modules on the left-hand side using the
connecting cable.
4. Mount the modules on the S7 DIN rail (190 mm).
S7-300 modules
S7 DIN rail
C7-635
Figure 4-3 Connecting Additional S7-300 Modules Directly on the Device Using the
2-Module I/O Set
Special Features of the C7-635
4-8 C7-635 Control System
A5E00155581-04
Connecting Additional S7-300 Modules at a Distance of Up to 1.5 m
As a prerequisite, you must have the “1.5 m cable” accessory specifically for the
C7-635 and a standard DIN rail.
Use the following procedure to connect the additional modules:
1. Connect the C7-635 to the outermost modules on the left-hand side by means
of the connecting cable.
2. Mount the modules on an S7 standard DIN rail of the S7-300 programmable
controller.
3. Using the cable clamp, connect the shield support of the I/O bus cable to the
S7 DIN rail.
S7 DIN rail
S7-300 module
Cable clamp for shield support
Figure 4-4 Connecting Additional S7-300 Modules at a Distance of Up to 1.5 m
Special Features of the C7-635
4-9
C7-635 Control System
A5E00155581-04
4.4 Status Display of the Digital Onboard I/O
I/O Status Display
There are no LEDs for displaying the status of the C7-635 I/O. You can configure a
screen to display the I/O status (see Figure 4-5).
The represented values must be read as a direct process image of the DI and an
internal process image of the DO of the digital C7-635 I/O, and displayed in the
BIN format.
Note that when the C7-CPU is in STOP mode, the real process status DO is 0.
However, the last process status set by the program is displayed.
The following data are displayed:
= Selection of
10100010 +1.7 - +1.0
DO:10101000 +0.7 - +0.0
ÀÁ
DI:11100010 +0.7 - +0.0
11101010 +1.7 - +1.0
10101010 +2.7 - +2.0
Figure 4-5 DI/DO Status Display
Table 4-2 Description of the DI/DO Status Display in Figure 4-5
Item Description
ÀSignal status of the DI/DO
1 DI/DO set
0 DI/DO reset
ÁPin Name DI/DO
Note
The values of the DI/DO are read in and displayed in the time configured with
ProTool. Changes made between these two occurrences are not displayed.
Special Features of the C7-635
4-10 C7-635 Control System
A5E00155581-04
5-1
C7-635 Control System
A5E00155581-04
Maintenance
The operator panel is designed for low-maintenance operation. Maintenance is
limited to the following:
Regular cleaning of the monitor
Replacement in case of a defect
5.1 Cleaning the Monitor
Preparation
Clean the monitor of your device at regular intervals using a damp cloth. Switch the
device off or select the configured cleaning screen. This ensures that you do not
unintentionally delete functions.
Cleaning Screen
If the cleaning screen function is configured in your project, you can clean the
monitor of the C7-635 Touch while it is switched on during the time displayed (in
the progress bar) without unintentionally deleting functions. All inputs are disabled
during this time.
Protective Film
A protective film is available for the C7-635 Touch. This film protects the monitor
from scratches and smudges.
Cleaning Solution
Use only water and cleaning solution or a foaming screen cleaner to dampen the
cloth. Spray the cleaning solution onto the cloth, rather than directly onto the
monitor.
Note
If you use a harsh solvent or scouring solution, the keyboard can rub off or the
touch screen can be damaged.
5
Maintenance
5-2 C7-635 Control System
A5E00155581-04
5.2 Replacing the C7-635
Introduction
A C7-635 is not designed for onsite repair. Therefore, a defective C7-635 must be
replaced.
To save the configuration of the TP/OP, you should have a Compact Flash Card
(CF Card). You should make a backup of the configuration on the CF card as soon
as you have finished commissioning the device, so that you can restore the
configuration if the device becomes defective.
!Caution
Prior to installing and uninstalling the device, remove the Micro Memory Card
(MMC) of the CPU and the Compact Flash Card (CF Card) of the TP/OP.
The inserted CF card protrudes from the C7-635 and could therefore be damaged.
How you proceed depends on whether you have backed up the TP/OP
configuration on a CF Card.
With CF Card
Requirements
You have inserted a CF Card.
You have a new gasket. The gasket must be replaced each time the C7-635 is
installed or uninstalled. The gasket is part of the service pack (see
Section 2.2).
Assembly
Step Action
1. Create a backup of the TP/OP configuration on the CF card. You should create
the backup immediately prior to uninstalling the device so that current data
(such as recipes) are included. Refer to the “Touch Panel TP170 A, TP 170 B,
Operator Panel OP170 B“ manual for information about how to make a backup
copy.
2. You do not need to take special action to back up the user program on the CPU.
It is saved as a non-volatile program on the MMC.
3. Switch off the power supply.
4. Loosen the cables from the shielding terminals and remove all connectors.
5. Remove the MMC and the CF Card.
6. Loosen the mounting supports with a screwdriver and remove the device from
the control cabinet.
Maintenance
5-3
C7-635 Control System
A5E00155581-04
Installation
Step Action
1. Complete the mechanical installation as described in Section 3.2. Be sure to
observe the relevant notes.
2. Insert the MMC and the CF Card.
3. Insert the cables and press the bare cables into the shielding terminals, as
described in Section 3.6.
4. Switch on the power supply.
5. Reload the saved data of the TP/OP configuration to the internal memory
(Restore). You will find a description of this procedure in the “Touch Panel
TP170 A, TP170B, Operator Panel OP170 B” manual.
6. Perform a general reset of the C7-CPU.
7. Switch the CPU to RUN mode.
Without CF Card
Requirements
You have a new gasket. The gasket must be replaced each time the C7-635 is
installed or uninstalled. The gasket is part of the service pack (see Section 2.2).
Programming device/PC with MPI interface
Corresponding connecting cable (MPI)
ProTool
Assembly
Step Action
1. Connect a programming device/PC to the MPI interface.
2. Save the TP/OP configuration in the C7-635 with ProTool. If the C7-635 is
defective and the configuration cannot be read, uninstall the C7-635 without any
additional safety precautions.
3. You do not need to take special action to back up the user program on the CPU.
It is saved as a non-volatile program on the MMC.
4. Switch off the power supply.
5. Loosen the cables from the shielding terminals and remove all connectors.
6. Remove the MMC.
7. Loosen the mounting supports with a screwdriver and remove the device from
the control cabinet.
Maintenance
5-4 C7-635 Control System
A5E00155581-04
Installation
Step Action
1. Complete the mechanical installation as described in Section 3.2. Be sure to
observe the relevant notes.
2. Insert the MMC.
3. Insert the cables and press the bare cables into the shielding terminals, as
described in Section 3.6.
4. Switch on the power supply.
5. Connect the C7-635 to the MPI interface of the programming device/PC.
6. Make sure that in the “Control Panel” in the menu “Transfer > Transfer Settings”
the MPI interface is activated.
7. Activate the transfer mode and download the backed-up TP/OP configuration
with ProTool.
8. Clear and reset the C7-CPU.
9. Switch the CPU to RUN mode.
A-1
C7-635 Control System
A5E00155581-04
Technical Specifications
A.1 Technical Specifications for Complete Apparatus
In this table, you will find the technical specifications for the complete apparatus.
Table A-1 Technical Specifications for C7-635
General Specifications C7-635 Touch C7-635 Key
Order No. 6ES7635-2EB01-0AE3 6ES7635-2EC01-0AE3
Dimensions
Mounting dimensions
260 x 199 x 79 mm (WxHxD)
231 x 183 mm
(tolerance: +1 mm)
260 x 274 x 80 mm (WxHxD)
231 x 257 mm
(tolerance: +1 mm)
Mounting depth for 2-module I/O
set:
144 mm (measured from the outer metal edge of the cutout)
Mounting depth for 4-module I/O
set:
195 mm (measured from the outer metal edge of the cutout)
Weight 1,380 g 1,500 g
Display
Active screen surface
Resolution
Colors
116 x 87 mm
320 x 240
Blue mode in 4 shades
Keyboard Resistive touch
Two-key membrane keyboard
Matrix keyboard
61-key membrane keyboard
Power Supply C7-635 Touch C7-635 Key
Supply voltage (UN)
Polarized input voltage
Voltage interruption
(can be jumpered)
24 VDC; (20.4 VDC to 28.8 VDC, Safety Extra Low Voltage, SELV)
The C7-635 has no integrated protection against high-energy
interfering pulses in the μs-range (surge pulse). Consult the S7-300,
CPU 31xC and CPU 31x: Hardware and Installation manual for the
required protective specifications.
Yes
20 ms
Current consumption Typically 350 mA in no-load
operation
1 A maximum
Typically 350 mA in no-load
operation
1 A maximum
Inrush current 2 A for 70 ms 2 A for 70 ms
Power losses 14 W 14 W
Ungrounded configuration Not possible
Software C7-635 Touch C7-635 Key
TP/OP operating system platform MS Windows CE MS Windows CE
A
Technical Specifications
A-2 C7-635 Control System
A5E00155581-04
Safety C7-635 Touch C7-635 Key
Standard references DIN EN 61131-2 corresponds to IEC 61131-2
Protection against ingress of
solid foreign bodies and water
Front panel
Housing
IP 65 in accordance with IEC
60529, NEMA 4X
IP 20 in accordance with IEC
60529
IP 65 in accordance with IEC
60529, NEMA 4X
IP 20 in accordance with IEC
60529
Electromagnetic
Compatibility (EMC)
C7-635 Touch C7-635 Key
Emitted interference
Limit class
A in accordance with EN55011
Cable-fed disturbances on DC
supply cables
±2 kV (in accordance with IEC 61000-4-4; burst)
Surge measurements with additional protective elements:
±1 kV (in accordance with IEC 61000-4-5; μs-pulse/cable to cable)
±2 kV (in accordance with IEC 61000-4-5; μs-pulse/cable to ground)
Interference immunity on signal
cables
±2 kV (in accordance with IEC 61000-4-4; burst)
Interference immunity from static
discharges
±6 kV, contact discharge (in accordance with IEC 61000-4-2; ESD)
±8 kV, air discharge (in accordance with IEC 61000-4-2; ESD)
Immunity to high-frequency
radiation
10 V/m, with 80% amplitude modulation at 1 kHz,
10 kHz to 80 MHz (in accordance with IEC 61000-4-6)
10 V/m, with 80% amplitude modulation at 1 kHz,
80 MHz to 1 GHz (in accordance with IEC 61000-4-3)
10 V/m, pulse-modulated 50% ED at 900 MHz and
1.89 GHz (in accordance with IEC61000-4-3)
Climatic Conditions C7-635 Touch C7-635 Key
Temperature
Operation
Storage/transport
Tested in accordance with IEC 60068-2-1 and IEC 60068-2-2:
0 °C to +40 °C in horizontal mountingposition
0 °C to +45 °C in 45°mounting position
0 °C to +50 °C in vertical mounting position
Note:
When the device is in a horizontal mounting position, display
readability is limited.
At temperatures < 10°C, rapidly changing displays do not appear
correctly.
–20 °C to +70 °C
Relative humidity
Operation
Storage/transport
Tested in accordance with IEC 60068-2-3
5% to 95% at 25 °C (no condensation)
5% to 95% at 25 °C (no condensation)
Air pressure
Operation
Storage/transport
1080-795 hPa (corresponds to –1000 m to +2000 m)
1080-660 hPa (corresponds to –1000 m to +3500 m)
Mechanical
Environmental Conditions
C7-635 Touch C7-635 Key
Technical Specifications
A-3
C7-635 Control System
A5E00155581-04
Mechanical
Environmental Conditions
C7-635 KeyC7-635 Touch
Vibration
Operation
Storage/transport in packaging
Tested in accordance with IEC 60068-2-6
10 to 58 Hz, amplitude 0.075
58 to 150 Hz, acceleration 9.8 m/s2
5 to 9 Hz, amplitude 3.5 mm
9 to 500 Hz, acceleration 9.8 m/s
Shock test
Operation
Storage/transport
Tested in accordance with IEC 60068-2-29
Half-sine: 150 m/s2(15 g), 11 ms, 18 shocks
250 m/s2 (25 g), 6 ms, 1,000 shocks
Resistance to fire:
Terminal strips
Master strips in housing
FV2 (tested in accordance with IEC 60707)
FV0
A.2 Technical Specifications for TP/OP
The table below summarizes the TP/OP scope of functions for the C7-635. The
values provided for HMI functions are maximum values that can be managed by
the C7-635. These values are limited by the size of the internal configuration
memory and the size of the Compact Flash Card (CF Card) of the TP.
Table A-2 Functional Scope of TP/OP
Function C7-635 Touch (TP) C7-635 Key (OP)
Memory Configuration of the TP
Recipes
768 Kbytes internal
32 Kbytes internal, expandable by means of
Compact Flash Card (CF card)
Operational Number 400 1)
messages Display Message line, message window/
message page, message display
View all pending messages Message page/message display
Length of message text per
line
70 characters
Process values in message
text
8
Edit message 4
Technical Specifications
A-4 C7-635 Control System
A5E00155581-04
Table A-2 Functional Scope of TP/OP, continued
Function C7-635 Key (OP)C7-635 Touch (TP)
Error messages Number 400 1)
Display
Message
window/message
page/
message display
Message line/
Message window/
Message page/
Message display
Display type First/last, selectable
Display all pending messages inmessage page/message display
Length of message text per
line
70 characters
Process values in message
text
8
Acknowledge individual error
messages
4
Acknowledge multiple error
messages simultaneously
(group acknowledgement)
16 acknowledgement groups
Edit message 4
Alarm_S Display S7 messages 4
Message printout Printer output 4
Volatile message
bff
Capacity 128 message events
buffer View status/error messages 4
Delete 4
Print 4
Simultaneously pending
message events (maximum)
64
Message recording Time of occurrence Date/time
Message event Incoming, outgoing, acknowledged
Technical Specifications
A-5
C7-635 Control System
A5E00155581-04
Table A-2 Functional Scope of TP/OP, continued
Function C7-635 Key (OP)C7-635 Touch (TP)
Screens Number 100
Fields per screen 50
Variables per screen 50
Complex elements per
screen
5
Displays 4 4
Print (hard copy) 4 4
Screen objects
Graphics
Text
Output field
Input field
Symbolic output field
Select field
Date/time
Graphic list
Vector graphic
Button
Status button
Switch
Invisible switch
Curve display
Bar graph
Message display
Simple message display
Password list
Recipe display
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
Operator prompting
Dynamic attributes
Show/hide objects
Help text
TAB sequence
Pictograms for softkeys
LEDs in
function keys
4
4
4
-
-
-
4
4
4
4
4
4
Permanent window 4 4
Limit-value
monitoring
Inputs/outputs 4 4
Conversion
functions
Inputs/outputs 4 4
Variables Number 250
Technical Specifications
A-6 C7-635 Control System
A5E00155581-04
Table A-2 Functional Scope of TP/OP, continued
Function C7-635 Key (OP)C7-635 Touch (TP)
Help text Lines/characters 7/35
For messages 4 4
For screens 4 4
For screen objects
Input field
Select field
Button
Status button
Switch
Invisible button
4
4
-
-
-
-
4
4
4
4
4
4
Curves Number 50
Graphic objects Number 50
Text elements Number 1000
Print functions Screen capture 4 4
Direct message listing 4 4
Password protection Number of passwords 50
Password level 10 (0 to 9)
Recipes Number 20
Data records per recipe 50 2)
Entries per recipe 60
Online language
selection
Number of languages 3
Screen settings Contrast 4 4
Timer Triggers functions cyclically
or one time
4 4
1) Total number for operational and fault messages
2) Limited by memory medium
Technical Specifications
A-7
C7-635 Control System
A5E00155581-04
A.3 Technical Specifications for CPU
Memory
User memory
Integrated 64 KB
Expandable No
Loading memory Plug-in (MMC)
Backup Ensured with MMC (maintenance-free)
Processing Times
Bit operation Minimum 0.1 μs
Word instructions Minimum 0.2 μs
Fixed-point arithmetic Minimum 2 μs
Floating-point maths Minimum 6 μs
Timers/Counters and their Retentivity
S7 counters 256
Retentivity Adjustable
Default From C 0 to C 7
Counting range 0 to 999
IEC Counters Yes
Type SFB
Number Unlimited (limited only by user memory)
S7 timers 256
Retentivity Adjustable
Default No retentivity
Timing range 10 ms to 9,990 s
IEC timers Yes
Type SFB
Number Unlimited (limited only by user memory)
Technical Specifications
A-8 C7-635 Control System
A5E00155581-04
Data Areas and their Retentive Characteristics
Total retentive data area
(including memory bits; timers;
counters)
All
Bit memories 256 bytes
Retentivity Adjustable
Retentivity preset MB 0 to MB 15
Clock memories 8 (1 memory byte)
Data blocks Maximum 511
Size Maximum 16 Kbytes
Local data per priority class Maximum 510 bytes
Blocks
Total 1024 (DBs, FCs, FBs, OBs, SDBs)
The maximum number of blocks that can be loaded is depending on
the MMC used.
OBs See instruction list
Size Maximum 16 Kbytes
Nesting depth
Per priority class 8
Additional nesting depths
within an error OB
4
FBs Maximum 512 (FB 0 to FB 511)
Size Maximum 16 Kbytes
FCs Maximum 512 (FC 0 to FC 511)
Size Maximum 16 Kbytes
Address Areas (I/O)
I/O address area overall Maximum 1024 bytes/1024 bytes (can be addressed by user)
Distributed Maximum 1,000 bytes
I/O process image 128 bytes/128 bytes
Digital channels Maximum 8,192
Of total, number of local
channels
Maximum 992
Integrated channels 24 DI / 16 DO
Analog channels Maximum 512
Of total, number of local
channels
Maximum 248
Integrated channels 4 + 1 AI/2 AO
Technical Specifications
A-9
C7-635 Control System
A5E00155581-04
Configuration
Rack Maximum 4
Modules in
rack 0
Maximum 4
Modules in
racks 1 and 2
Maximum 8
Modules in
rack 3
Maximum 7
Number of DP masters
Integrated 1
By means of CP Maximum 1
Function modules and communication processors that can be operated
FM Maximum 8
CP (PtP) Maximum 8
CP (LAN) Maximum 10
Time
Realtime clock Yes (HW clock)
Buffered Yes
Backup period 6 weeks, typically (at an ambient temperature of 40°C)
Accuracy Deviation per day < 10 s
Operating hours counter 1
Number 0
Value range 0 to 231 hours (when using SFC 101)
Selectivity 1 hour
Retentive Yes; requires restarting at every restart
Clock synchronization Yes
In PLC Master
On MPI Master/slave
S7 Message Functions
Number of stations that can log in
for message functions
(for example, OS)
Maximum 12
(depends on the number of connections configured for PG/OP and
S7 basic communication)
Process diagnostic messages Yes
Simultaneously active alarm
S-blocks
Maximum 40
Technical Specifications
A-10 C7-635 Control System
A5E00155581-04
Testing and Commissioning Functions
Status/control variable Yes
Variable Inputs, outputs, flags, DBs, timers, counters
Number of variables Maximum 30
Of total, number of status
variables
Maximum 30
Of total, number of control
variables
Maximum 14
Force Yes
Variables Inputs, outputs
Number of variables Maximum 10
Status block Yes
Single sequence Yes
Breakpoint 2
Diagnostic buffer Yes
Number of entries (cannot be
set)
Maximum 100
Communication Functions
Programming device/OP
communication
Yes
Global data communication Yes
Number of global data
packets
Maximum 4
Sending station Maximum 4
Receiving station Maximum 4
Size of global data packets Maximum 22 bytes
Of total, number of consistent
bytes
22 bytes
S7 standard communication Yes
Useful data per job Maximum 76 bytes
Of total, number of consistent
bytes
76 bytes (with X_SEND or X_RCV)
64 bytes (with X_PUT or X_GET as server)
S7 communication
As Server Yes
As Client Yes (with CP and loadable FB)
Useful data per job Maximum 180 bytes (with PUT/GET)
Of total, number of consistent
bytes
64 bytes
S5-compatible communication Yes (via CP and loadable FCs)
Number of connections Maximum 12
Usable for
Programming device
communication
Maximum 11
Reserved (default) 1
Adjustable From 1 to 11
OP communication Maximum 11
Reserved (default) 1
Technical Specifications
A-11
C7-635 Control System
A5E00155581-04
Communication Functions
Adjustable From 1 to 11
S7 basic communication Maximum 8
Reserved (default) 8
Adjustable From 0 to 8
Routing Maximum 4
MPI
Type of interface Integrated RS 485 interface
Physics RS 485
Galvanically isolated No
Interface current supply
(15 VDC to 30 VDC)
Maximum 200 mA
Number of connections 12
Services
Programming device/OP
communication
Yes
Routing Yes
Global data communication Yes
S7 standard communication Yes
S7 communication
As server Yes
As client Yes (with CP and loadable FB)
Transmission rates Maximum 187.5 kbaud
PROFIBUS-DP
Type of interface Integrated RS 485 interface
Physics RS 485
Galvanically isolated Yes
Interface current supply (15 VDC
to 30 VDC)
Maximum 200 mA
Number of connections 12
DP master
Number of connections 12
Services
Programming device/OP
communication
Yes
Routing Yes
Global data communication No
S7 standard communication No
S7 communication No
Equidistance Yes
SYNC/FREEZE Yes
Activate/deactivate DP slaves Yes
Transmission rates Up to 12 Mbaud
Technical Specifications
A-12 C7-635 Control System
A5E00155581-04
PROFIBUS-DP
Number of DP slaves per
station
Maximum 32;
Address area Maximum 1 Kbyte I / 1 Kbyte O
Useful data per DP slave Maximum 244 bytes I / 244 bytes O
DP slave
Number of connections 12
Services
Programming device/OP
communication
Yes
Routing Yes (only with active interface)
Global data communication No
S7 standard communication No
S7 communication No
Direct data exchange Yes
Transmission rates Up to 12 Mbaud
Transfer memory 244 bytes I / 244 bytes O
Automatic baud rate search Yes (only if interface is passive)
Address areas Maximum 32 with a maximum of 32 bytes each
DPV 1 No
Programming
Programming language LAD/FBD/STL
Stored instructions See instruction list
Nesting levels 8
System functions (SFCs) See instruction list
System function blocks (SFBs) See instruction list
User program security Yes
Technical Specifications
A-13
C7-635 Control System
A5E00155581-04
Integrated I/O
Default addresses of the integrated
Digital inputs 124.0 to 126.7
Digital outputs 124.0 to 125.7
Analog inputs 752 to 761
Analog outputs 752 to 755
Integrated Functions (see the CPU 31xC Technological Functions manual)
Counters,
Frequency meters,
Pulse outputs (pulse width
modulation)
4 channels in total,
Frequency meter up to 60 kHz, maximum,
Pulse outputs up to 2.5 kHz, maximum
Controlled positioning 1 channel
Integrated SFB ”controlling” PID controller
Technical Specifications
A-14 C7-635 Control System
A5E00155581-04
A.4 Technical Specifications for Integrated I/O
Digital inputs
Number
Number of inputs 24
inputs usable for
technological functions
16
Cable Length (for Standard DI /Technological Functions)
Unshielded Maximum 600 m / No
Shielded Maximum 1000 m / Maximum 50 m
Voltage, Currents, Potentials
Rated load current L+ 24V DC
Polarity reversal protection Yes
Number of inputs that can be triggered simultaneously
Vertical mounting position
Up to 40°C18
Up to 50°C12
45° mounting position
Up to 45°C12
Horizontal mounting position
Up to 40°C12
Galvanic isolation
Between channels and I/O
bus
Yes
Between channels No
Permissible potential difference
Between different circuits 75 VDC/60 VAC
Insulation tested at 500 VDC
Current consumption
From power voltage L+
(no-load)
Maximum 70 mA
Technical Specifications
A-15
C7-635 Control System
A5E00155581-04
Status, Interrupts, Diagnostics
Interrupts Yes, if the corresponding channel is configured as an interrupt
input
When using the technological functions,
see CPU 31xC Technological Functions manual
Diagnostic functions No diagnostics when operated as standard I/O
When using the technological functions,
see CPU 31xC Technological Functions manual
Data for Selecting an Encoder for Standard DI
Input voltage
Rated value 24 VDC
for signal “1” 15 V to 30 V
for signal “0” –3 V to 5 V
Input current
for signal ”1” 7 mA, typically
Delay of the standard inputs
Configurable Yes (0.1 / 0.5 / 3 / 15 ms)
You may change the delay time of standard inputs while the program
is being executed. Please note that your new filter time may not be
effective until the next filter cycle.
Rated value 3 ms
Input delay when using
technological functions
Minimum pulse width /
minimum pulse interval at
maximum count frequency
8μs
Input characteristic According to IEC 1131, Type 1
Connection of 2-wire BEROs Possible
Permissible quiescent current Maximum 1.5 mA
Technical Specifications
A-16 C7-635 Control System
A5E00155581-04
Digital outputs
Note
Technological functions utilize fast digital outputs. These outputs must only be
connected to resistive loads.
Number
Number of outputs 16
Of total, number of fast
outputs
4
Cable length
Unshielded Maximum 600 m
Shielded Maximum 1,000 m (109 yd.)
Voltage, Currents, Potentials
Rated load current L+ 24 VDC
Polarity reversal protection Yes
Total current of outputs (per group)
Vertical mounting position
Up to 40°CMaximum 3.0 A
Up to 50°CMaximum 2.0 A
45°C mounting position
Up to 45°CMaximum 2.0 A
Horizontal mounting position
Up to 40°CMaximum 2.0 A
Galvanic isolation
Between channels and I/O
bus
Yes
Between channels Yes
In groups of 8
Permissible potential difference
Between different circuits 75 VDC/60 VAC
Insulation tested at 500V DC
Current consumption
From load voltage L+ Maximum 20 mA per group
Technical Specifications
A-17
C7-635 Control System
A5E00155581-04
Status, Interrupts, Diagnostics
Interrupts No interrupts when operated as standard I/O
When using the technological functions,
see CPU 31xC Technological Functions manual
Diagnostic functions No diagnostics when operated as standard I/O
When using the technological functions,
see CPU 31xC Technological Functions manual
Data for Selecting an Actuator for Standard DO
Output voltage
for signal ”1” Minimum L+ (–0.8 V)
Output current
for signal “1”
Rated value 0.5 A
Permissible range 5 mA to 0.6 A
for signal “0” (residual
current)
Maximum 0.5 mA
Load impedance range 48 Ω to 4 kΩ
Lamp load Maximum 5 W
Parallel connection of 2 outputs
For redundant load control Possible
For performance increase Not possible
Triggering of a digital input Possible
Switching frequency
For resistive load Maximum 100 Hz
For inductive load according
to IEC 947-5, DC13
Maximum 0.5 Hz
For lamp load Maximum 100 Hz
Fast outputs with resistive
load
Maximum 2.5 kHz
Inductive breaking voltage limited
internally to
(L+) – 48 V, typically
Short-circuit protected output Yes, electronic
Response threshold 1 A, typically
Technical Specifications
A-18 C7-635 Control System
A5E00155581-04
Analog inputs
Number
Number of inputs
Current / voltage input
Resistance input
4 channels
1 channel
Cable length
Shielded Maximum 100 m (109 yd.)
Voltage, Currents, Potentials
Resistance input
No-load voltage 2.5 V, typically
Measured current 1.8 mA to 3.3 mA, typically
Galvanic isolation
Between channels and I/O
bus
Yes
Between channels No
Permissible potential difference
Between inputs and MANA
(VCM)
8.0 VDC
Between MANA and Minternal
(VISO)
75 VDC/60 VAC
Insulation tested at 500 VDC
Analog Value Generation
Measuring principle Momentary value encoding
(successive approximation)
Integration time/conversion time/tesolution (per channel)
Configurable Yes
Integration time in ms 2.5 / 16.6 / 20
Permissible input frequency Maximum 400 Hz
Resolution (including
overdrive)
11 bits + sign bit
Suppression of interference
frequency f1
400 / 60 / 50 Hz
Time constant of the input filter 0.38 ms
Basic execution time 1 ms
Technical Specifications
A-19
C7-635 Control System
A5E00155581-04
Interference Suppression, Error Limits
Interference voltage suppression for f = n x (f1+/– 1 %),
(f1 = interference frequency), n = 1, 2
Common mode interference
(VCM < 8.0 V)
> 40 dB
Feedback interference (peak
value of the interference <
rated value of the input range)
> 30 dB
Crosstalk between the inputs > 50 dB
Operational error limits (throughout temperature range, relative to input range)
Voltage/current < 1 %
Resistance < 5%
Basic error limits (operational limit at 25°C, relative to input range)
Voltage/current < 0.7%
Resistance < 3%
Temperature error (related to input
range)
+/– 0.006 %/K
Linearity error (related to input
range)
+/– 0.06%
Accuracy of reproducibility (in
steady state at 25 ° C, relative to
input range)
+/–0.06%
Status, Interrupts, Diagnostics
Interrupts No interrupts when operated as standard I/O
When using the technological functions,
see CPU 31xC Technological Functions manual
Diagnostic functions No diagnostics when operated as standard I/O
When using the technological functions,
see CPU 31x Technological Functions manual
Technical Specifications
A-20 C7-635 Control System
A5E00155581-04
Encoder Selection Data
Input ranges (rated value)/input resistance
Voltage +/– 10 V/100 k Ω
0 V to 10 V/100 kΩ
Current +/– 20 mA/50 Ω
0 mA to 20 mA/50 Ω
4 mA to 20 mA/50 Ω
Resistance 0Ω to 600 Ω/10 MΩ
Resistive thermometer Pt 100/10 MΩ
Permissible input voltage (destruction limit)
For voltage input Maximum 30 V continuous;
For current input Maximum 2.5 V continuous, maximum 24 V transient
Permissible input current (destruction limit)
for voltage input Maximum 0.5 mA continuous;
For current input Maximum 50 mA continuous;
Connection of signal encoders
For voltage measurement Possible
For current measurement
As 2-wire measuring
transducer
Possible, with external power supply
As 4-wire measuring
transducer
Possible
For measuring resistance
With 2-wire connection Possible, without cable resistance compensation
With 3-wire connection Not possible
With 4-wire connection Not possible
Linearization of characteristic
curve
By software
For resistive thermometer Pt 100
Temperature compensation No
Technical unit for temperature
measurement
Degrees Centigrade/Fahrenheit/Kelvin
Technical Specifications
A-21
C7-635 Control System
A5E00155581-04
Analog outputs
Number
Number of outputs 2
Cable length
Shielded Maximum 200 m
Voltage, Currents, Potentials
Rated load current L+ 24 VDC
Polarity reversal protection Yes
Galvanic isolation
Between channels and I/O
bus
Yes
Between channels No
Permissible potential difference
between MANA and Minternal
(VISO)
75 VDC/60 VAC
Insulation tested at 500 VDC
Analog Value Generation
Resolution (including
overdrive)
11 bits + sign bit
Conversion time (per channel) 1 ms
Settling time
For resistive load 0.6 ms
For capacitive load 1.0 ms
For inductive load 0.5 ms
Interference Suppression, Error Limits
Crosstalk between the outputs > 60 dB
Operational error limits (throughout temperature range, relative to output range)
Voltage/current +/– 1%
Basic error limits (operational limit at 25°C, relative to output range )
Voltage/current +/– 0.7%
Temperature error (relative to
output range)
+/–0.01 %/K
Linearity error (relative to output
range)
+/–0.15%
Technical Specifications
A-22 C7-635 Control System
A5E00155581-04
Status, Interrupts, Diagnostics
Interrupts No interrupts when operated as standard I/O
When using the technological functions,
see CPU 31xC Technological Functions manual
Diagnostic functions No diagnostics when operated as standard I/O
When using the technological functions,
see CPU 31xC Technological Functions manual
Actuator Selection Data
Output range (rated values)
Voltage +/– 10 V
0 V to 10 V
Current +/– 20 mA
0 mA to 20 mA
4 mA to 20 mA
Load resistance
(in the rated range of the output)
Voltage outputs
ohmic load Minimum 1 kΩ
capacitive load Maximum 0.1 μF
Current outputs
ohmic load Maximum 300 Ω
inductive load Max. 0.1 mH
Voltage output
Short-circuit protection Yes
Short-circuit current 55 mA, typically
Current output
No-load voltage 17 V, typically
Destruction limit for externally applied voltages/currents
Output voltage to MANA Maximum 16 V continuous;
Current Maximum 50 mA continuous;
Connection of actuators
For voltage output
2-wire connection Possible, without cable resistance compensation
4-wire connection (measuring
line)
Not possible
For current output
2-wire connection Possible
Technical Specifications
A-23
C7-635 Control System
A5E00155581-04
A.5 Notes on Power Supply
24 VDC Supply
For the C7-635, the entire supply has to be generated with DC 24 V (operating
voltage, load voltage, relay supply, etc.) as Safety Extra-Low Voltage (SELV).
!Warning
Personal injury and property damage can occur.
If you do not configure the 24 VDC power supply of the C7-635 correctly, you can
incur damage to the components of your automation system and personal injury.
For the 24 VDC power supply of the C7-635, use only safety extra-low voltage
(SELV).
A.6 Approvals
Approvals for USA and Canada
Note
Which one of the approvals (UL/CSA or cULus) listed below is relevant for your
product is indicated on the rating plate.
UL approval
Underwriters Laboratories Inc. to
UL 508 (Industrial Control Equipment)
CSA approval
Canadian Standards Association to
C22.2 No. 142 (Process Control Equipment)
or
Underwriters Laboratories Inc. to
SUL 508 (Industrial Control Equipment)
SCSA C22.2 No. 142 (Process Control Equipment)
Technical Specifications
A-24 C7-635 Control System
A5E00155581-04
or
Underwriters Laboratories Inc. to
SUL 508 (Industrial Control Equipment)
SCSA C22.2 No. 142 (Process Control Equipment)
SUL 1604 (Hazardous Location)
SCSA-213 (Hazardous Location)
APPROVED for use in
Class I, Division 2, Group A, B, C, D Tx;
Class I, Zone 2, Group IIC Tx
FM Approval
FM
APPROVED
FM standards 3611, 3600, and 3810 APPROVED for use in Class I,
Division 2, Group A, B, C, D indoor hazardous locations.
!Warning
Personal injury and material damage may be incurred.
In hazardous areas, personal injury or property damage can result if you discon-
nect any plug-it connections while the system is in operation.
Always deenergize the C7-635 in hazardous areas before removing plug-it con-
nectors.
!Warning
WARNING - DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS
LOCATION IS KNOWN TO BE NONHAZARDOUS
Marine approval
Approvals by the following classification authorities are pending:
ABS (American Bureau of Shipping)
BV (Bureau Veritas)
DNV (Det Norske Veritas)
GL (Germanischer Lloyd)
LRS (Lloyds Register of Shipping)
Class NK (Nippon Kaiji Kyokai)
HAZ. LOC.
Technical Specifications
A-25
C7-635 Control System
A5E00155581-04
A.7 Notes on CE Marking
EC Guideline 89/336/EEC EMC Guidelines
This product complies with the requirements of the EC guideline 89/336/EEC
“Electromagnetic Compatibility”.
The EC declarations of conformity and their associated documentation are available
to the proper authorities in accordance with the above-mentioned EC Guideline,
Article 10 (1) at the following address:
Siemens AG
Automation and Drives Division
A&D AS RD 42
P.O. Box 1963
D-92209 Amberg, Federal Republic of Germany
Range of Application
The following range of application applies for the C7-635 control system, in
accordance with this CE marking:
Range of Application Requirements
Emitted Interference Immunity to Interference
Industrial applications EN 50081-2: 1993 EN 61000-6-2: 1999
Installation Guidelines
The installation guidelines and safety notes provided in the documentation are to
be adhered to during commissioning and operation.
Technical Specifications
A-26 C7-635 Control System
A5E00155581-04
A.8 Notes for Machine Manufacturers
Introduction
The SIMATIC automation system is not a machine in the sense of the EC guideline
“Machinery”. Consequently, no declaration of conformity exists with regard to the
EC guideline 89/392/EEC “Machinery”.
EC Guideline 89/392/EEC ”Machinery”
EC guideline 89/392/EEC “Machinery” regulates the requirements of machinery. In
this guideline, machinery is considered to include all associated parts or
mechanisms (see also EN 292-1, Section 3.1).
SIMATIC is a part of the electrical equipment of machinery and must therefore be
included by the machine manufacturer in the declaration of conformity process.
Electrical Equipment of Machinery in Accordance with EN 60204
The standard EN 60204-1 (Safety of Machinery, General Requirements of the
Electrical Equipment of Machinery) is applicable for the electrical equipment of
machinery.
The following table is provided to help you with the declaration of conformity; it
indicates which criteria are applicable for SIMATIC in accordance with EN 60204-1
(June 1993 edition).
EN 60204-1 Subject/Criterion Comments
Section 4 General Requirements The requirements are satisfied if the devices are
assembled/installed in accordance with the mounting
guidelines. You must also take into account the explanations
provided on previous pages.
Section 11.2 Digital Input/Output
Interfaces
The requirements are satisfied.
Section 12.3 Programmable Equipment The requirements are satisfied if devicesfor protection
against changes to memory by unauthorized persons are
installed in lockable cabinets.
Section 20.4 Dielectric Tests The requirements are satisfied.
Index-1
C7-635 Control System
A5E00155581-04
Index
A
Accessories, 2-9
Additional devices and tools required to
operate the C7-635, 2-8
Additional S7-300 modules, 4-5
Approval
CSA, A-23
Marine, A-24
UL, A-23
Approvals, A-23
Authorization inputs AT1/AT2, 4-3
B
Backup, 5-2
Backup battery, replacing, 5-1
BF, 4-5
Bus connector, 3-21
C
C7, installing, 3-3
C7 accessories, 2-9
C7 minimum distance, 3-10
C7 operation, requirements, 2-8
C7-635 components, 2-8
C7-CPU, selecting operating mode, 4-2
Cabinet design, 3-23
CE Marking, A-23, A-25
Cleaning solution, 5-1
Cleaning the monitor, 5-1
Coding connectors, 3-25
Coding profile, 3-25
Components, 2-3, 2-8
Connecting Cables, 3-21
Connector pin assignment, 3-11
Construction, fail-safe, 3-22
Construction guidelines, 3-22
CSA, approval, A-23
D
Degree of protection IP65, 3-3
Deviations from CPU314C-2 DP, 4-1
Deviations from TP 170 B, 4-1
Dewing, 3-3
DI/DO-status display
description, 4-9
explanation, 3-3
Digital input, 3-16, 3-19
Digital output, 3-17, 3-18
E
EC-guideline, Machinery, A-26
F
Fail-safe construction, 3-22
FM-approval, A-24
FRCE, 4-5
Function keys, labeling, 3-1
Functional ground, 3-23
G
General reset, MRES, 4-4
Grounding, 3-22, 3-23
Grounding terminal, 3-23, 3-24
installing, 3-24
Group error, CPU, 4-5
I
I/O expansion directly on the device, 4-6, 4-7
I/O status display, 4-9
IM361-cable, 3-21
Installation of fail-safe cables, 3-22
Integrated I/O, 2-6
Interfaces, 2-3
Interference signals, 3-22
IP65, 3-3
K
Key-LEDs, 4-2
Keyboard, C7-635, 3-11, 3-12, 3-13, 3-15, 3-19
L
Labeling strips, 3-1
Index
Index-2 C7-635 Control System
A5E00155581-04
M
Machinery, with SIMATIC, A-26
Maintenance, 5-1
Manufacturers of machines, A-26
Marine, approval, A-24
Mechanical installation, 3-3
Minimum distance, C7, 3-10
Mounting depth, A-1
2-module I/O set, A-1
4-module I/O set, A-1
Mounting the C7, 3-3
MPI-address, 2-5
MRES, 4-4
N
Notes on power supply, A-23
O
Operating mode selection, 4-2
Operating modes, 4-2
Operation of C7, requirements, 2-8
P
Plug-In S7-300 modules, 2-4
PROFIBUS-Bus cable, 3-21
PROFIBUS-Bus terminal, 3-21
PROFIBUS-DP interface, 2-7
Programming device (PG)-cable, 3-21
Protective film, 5-1
R
Replacing the C7-635, 5-2
Restore, 5-3
RUN, 4-3, 4-5
S
S7-300 modules, 4-5
SF, 4-5
Shielded cables, 3-24
Shielding, 3-22
Shielding terminal, 3-24
Spare parts, 2-10
Special features of the C7-635, 4-1
Status-LEDs, 4-3
STOP, 4-3, 4-5
T
Technical specifications for complete
apparatus, A-1
Technical specifications for CPU, A-7
Technical specifications for integrated I/O, A-14
Technical specifications TP, A-3
Technological functions, 2-7
U
UL, Approval, A-23
User memory, 2-6
Copyright ESiemens AG 2006
Siemens Aktiengesellschaft A5E00861679-01
Product Information
07.2006
Device Manual C7-613 Control System
Device Manual C7-635 Control System
Device Manual C7-636 Control System
This product information contains important information about the documentation mentioned
above. It is to be regarded as a separate component. Its specifications and information have a
higher binding nature than those of other manuals, instruction lists and Getting Starteds.
New C7 devices with larger working memory
The working memory of the following C7 devices was extended. The CPUs can now ex-
ecute larger user programs.
Due to these improvements, the order number of the CPUs were changed.
The new C7 devices are:
contained in STEP7 V5.4 Service Pack 1
configurable with the older STEP7 versions:
The C7 devices with the new order number can be downloaded from the Internet as
a hardware update (0109).
Requirement is STEP7 V5.2, Service Pack1.
configurable with the corresponding previous C7 devices
compatible with the previous C7 devices
Non--retentive data blocks
In opposition to the data in the S7--300, CPU 31xC and CPU 31x manual, Technical
data”, chapter 4.1.2, the C7 devices with frimware V2.0.12 are no longer supported by
retentive data blocks. Non--retentive data blocks and code blocks can be loaded to the
maximum limit of the working memory. Retentive data blocks can be loaded to the
maximum retentive limit of the working memory (see the following table).
2
Product Information
A5E00861679-01
Product
description
Previous order nr. Firmware
<
Previous
Working
memory
Previous
Working
memory
retentive **
New order nr. Firmware
Working
memory
new
Working
memory
retentive **
new
Hard-
ware
update
C7-613 6ES7613-1CA01-0AE3 V2.0.12 48 KB 48 KB 6ES7613-1CA02-0AE3 V2.0.12 80 KB 64 KB 0109
C7-635 Touch 6ES7635-2EB01-0AE3 V2.0.12 64 KB 64 KB 6ES7635-2EB02-0AE3 V2.0.12 96 KB 64 KB 0109
C7-635 Key 6ES7635-2EC01-0AE3 V2.0.12 64 KB 64 KB 6ES7635-2EC02-0AE3 V2.0.12 96 KB 64 KB 0109
C7-636 Touch* 6ES7636-2EB00-0AE3 V2.0.12 128 KB 128 KB 6ES7636-2EB00-0AE3 V2.0.12 128 KB 128 KB --
C7-636 Key* 6ES7636-2EC00-0AE3 V2.0.12 128 KB 128 KB 6ES7636-2EC00-0AE3 V2.0.12 128 KB 128 KB --
* not affected by the extension of the memory
** Maximum size for retentive working memory for retentive data blocks