D4B-N
16
JCORRECT USE
Operating Environment
The D4B-jN is for indoor use. The D4B-jN may malfunction if
the D4B-jN is used outdoors. Be sure to use a model with a
lever-type actuator for outdoor use instead.
Do not use the D4B-jN in the following places:
•Places with radical temperature changes.
•Places with excessive humidity that may cause condensa-
tion.
•Places with excessive vibration.
•Places where metal dust, oil, or chemical may be sprayed to
the D4B-jN.
Mounting
Use four M5 screws with washers to mount the standard model. Be
sure to apply the propertorque to tighten each screw. The D4B-jN
can be mounted more securely by using the four screws plus two
5--0.05/--0.15-mm protruding parts, each of which has a maximum
height of 4.8 mm as shown below.
Mounting Dimensions (M5)
30
60 59.3±0.1 30
40
42
27±0.1
5 dia. holes, max. 5 height
--0.15
--0.05
Standard Model 3-Conduit Model
Protruding portions
Changes in Actuator Mounting Position
To change the angle of the lever, loosen the Allen-head bolts on the
side of the lever.
The operating position indicator plate has protruding parts which
engage with the lever, thus allowing changes to the lever position
by 90°.
The back of the operating position indicator plate has no
protruding parts. The lever can be set at any angle by attaching
the operating position indicator plate to the Switch so that this
side will face the lever. In this case, however, the D4B-jN will
not be approved by SUVA or BIA. Make sure that the lever
engages with the operating position indicator plate securely so
that the lever will not slip.
Changes in Head Mounting Position
By removing the screws on the four corners of the head, the
head can be reset in any of four directions. Make sure that no
foreign materials will penetrate through the head.
Wiring
Do not connect the bare lead wires directly to the terminals but
be sure to connect each of them by using an insulation tube and
M3.5 round solderless terminals and tighten each terminal screw
within the specified torque range.
The proper lead wire is 20 to 14 AWG (0.5 to 2.5 mm2)insize.
dz dia.: 3.7
Ddia.: 4.5
B: 7.0
L: 20.2
F: 7.7
I: 9.0 (mm) Ddia.
dz dia.
Make sure that all solderless terminals come into contact with the
casing or cover as shown below, or the cover may not be
mounted properly or the D4B-jN may malfunction.
Crimp-style
terminal
Case
Cover
Terminal screw
Crimp-style terminal
Terminal screw
Case
Terminal screw
Cover
Crimp-style terminal
Correct
Correct
Incorrect
Incorrect
Crimp-style terminal
Crimp-style terminal
Correct
Incorrect