QUINT-PS/24DC/24DC/10 Order No.: 2320092
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2320092
PHOENIX CONTACT Ltd Page 2 / 6
http://www.phoenixcontact.co.uk 20-Jan-2012
Technical data
Input data
Nominal input voltage 24 V DC
DC input voltage range 18 V DC ... 32 V DC
14 V DC ... 18 V DC (Consider derating during operation)
DC frequency range 0 Hz
Current consumption Typ. 14 A (24 V DC)
Inrush surge current < 15 A (typical)
Power failure bypass > 12 ms (24 V DC)
Input fuse 25 A (internal (device protection))
Permissible backup fuse B16
B20
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 18 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current 10 A (-25 °C ... 60 °C)
12.5 A (with POWER BOOST, -25°C ... 40°C permanently, UOUT =
24 V DC)
60 A (SFB technology, 12 ms)
Magnetic fuse tripping B6
C4
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Max. capacitive load Unlimited
Current limitation Approx. 18 A
Control deviation < 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Residual ripple < 20 mVPP
Peak switching voltages nominal load < 10 mVPP (20 MHz)
Maximum power dissipation idling 1.6 W
Power loss nominal load max. 24 W