SDN™ Redundant Series Specifications for SDN2.5-20RED and SDN 30/40RED
Catalog Number
Description SDN 2.5-20RED SDN 30/40RED
Concept
By means of a separate redundancy module, you can interconnect several identical SDN power supply units in a N+1 redundant mode. These external
modules decouple the power supply outputs from each other so that, in case of failure, one power supply unit cannot overload the other units. The
modules incorporate DC OK relay contacts. The switch on front of the SDN power supply should be placed in parallel mode (not single mode) when
power supplies are used with redundant module.
Electrical Characteristics
Voltage
-Nominal Value 24 Vdc
-Max. Rated 35 V
Voltage Drop
-Vin -> Vout Typ. 0.6 V
Current Handling Capacity
-Maximum Value 20 A 40 A
Inverse Battery Protection Yes
Connection Via captive screw terminals
-Connector size range
Solid: 16-10 AWG (1.5 - 6 mm2)
Stranded: 16-12 AWG (1.5 - 4 mm2)
Solid: 16-5 AWG (1.5 - 16 mm2)
Stranded: 16-8 AWG (1.5 - 10 mm2)
Note: GND must be connected to module for voltage monitor to operate properly.
See Connectors and Wiring diagrams on next page.
Relay Contacts
DC Okay Contacts (qty) description (1) Vout “OK” - N.O. & N.C. Contact (1) Vout “OK” - N.O. Contact
(2) Vin “OK” - N.O. Contact
-Voltage Set Point > 18 Vdc ±5%
-Contact Rating 30 Vdc @ 2A / 250 V @ 2A
DC OK LED Vout “OK” Green LED
-Voltage Set Point > 18 Vdc ±5%
Dimensions
H x W x D - inches (mm) 4.88 in x 1.97 in x 4.55 in
(124.0 mm x 50.0 mm x 116.0 mm)
4.88 in x 2.56 in x 4.55 in
(124.0 mm x 65.0 mm x 116.0 mm)
Free Space for Ventilation -
inches (mm)
Above/Below: 0.39 in. (10 mm) recommended
Left/Right: 0.39 in. (10 mm) recommended
Weight lbs (kg) 1.4 (625.00) 1.4 (646.00)
General
Ambient Temperature
Storage: -25°C to +85°C Operation: -10°C to +60°C full power with operation to 70°C possible with a
linear derating to half power from 60°C to 70°C (Convection cooling, no forced air required). Operation up
to 50% load permissible with sideways or front side up mounting orientation.
The relative humidity is < 90% RH, noncondensing.