Alpha400 Alpha600 Alpha800
185
System Power Supply
䡵Alpha 400/600/800 Common specification
1 NUMBER of SLOTS 5 Slots (7 channels max.) 5 Slots (7 channels max.) 7 Slots (14 channels max.)
2 INPUT VOLTAGE RANGE 85-265VAC(47-63Hz) 85-90VAC (required the output derating)
3
MAXIMUM TOTAL OUTPUT WATTAGE
400W 600W 800W(1000W peak)
4 INPUT CURRENT typ.
7A: 100VAC/3.5A: 200VAC at full load 10A: 100VAC/ 5A: 200VAC at full load 13A: 100VAC/ 6.5A: 200VAC at full load
5 INRUSH CURRENT 20A max. 30A max. 40A max.
6
HARMONICS CURRENT CONTROL
meet EN61000-3-2 (Harmonics current correction range: 85-255VAC)
7 POWER FACTOR typ. 0.99 (typ.): input 100VAC at full load / 0.95 (typ.): 230VAC at full load
8 EFFICIENCY (typ.) 75%: input 100/200VAC nominal outputs voltage at maximum total output power
9
MISSING CYCLE HOLD UP TIME (typ.)
minimum 16mS: input 100/200VAC nominal outputs voltage at maximum total output power
10 LEAKAGE CURRENT maximum 0.95mA at full load
11
OPERATING AMBIENT TEMPERATURE
0~+60°C (0-50°C : 100%, +60°C : 75%)
12 OPERATING AMBIENT HUMIDITY 30~90%RH (no condensation)
13
STORAGE AMBIENT TEMPERATURE
-30~+85ËšC
14
STORAGE AMBIENT
HUMIDITY 10~95%RH (no condensation)
15 COOLING Forced air cooling with internal fan
16 WITHSTAND VOLTAGE input - FG 1.5kVAC for one minute (20mA): input - output 3kVAC for one minute (20mA)
17 INSULATION RESISTOR minimum 100M ohm (output - FG 500VDC. 25ËšC. 70%RH)
18 VIBRATION
Vibration cycles at 10-55Hz, sweep time for one minute, 19.6
m/s
2
constant, X,Y,Z axis on each side for one hour with no input.
19 MECHANICAL SHOCK maximum 196.1m/s2
20 SAFETY STANDARDS Approved by UL1950, CSA950 (C-UL), EN60950(SEMKO), EN60601-1, UL2601-1, meet DENTORI
21 CONDUCTED E.M.I. meets EN55022-class A, meet VCCI-class A
22 RADIATED R.F.I. meets EN55022-class A, VCCI-classA
23 NOISE IMMUNITY meets EN61000-4-2 Level 4, EN61000-4-3 Level 3, EN61000-4-4 Level4 and EN61000-4-5 Level 3
24 WEIGHT (typ.) 2100g 2500g 3400g
25 SIZE (W x H x D) 126.5 x 63 x 274.5mm 126.5 x 63 x 318.5mm 175.5 x 63 x 279mm
Specifications(please read the instruction manual before design)
䡵Alpha 400/600/800 Specification for Output Modules
Output Module name A B C D E F G H M N P Q R T
(*1) 100MHz (measured by the Japanese Standard EIAJ RC-9131)
(*2) Input Voltage 85 - 265VAC at constant load
(*3) no-load to full-load, at constant input voltage (when use the remote sensing, the level will be the same as the line regulation.)
(*4) Constant Current Auto-Reset (pre-set before shipment: fixed the limitation)
(*5) Shut Down method with Manual Reset (restart the input to be reset)
1. NUMBER of SLOTS 2111 1 22 1 11 1 122
2. RATED OUTPUT VOLTAGE V 5 5 12 24 12 12 12 24 24 24 12 24 24 12 3.3 3.3 2
3.
MAXIMUM OUTPUT CURRENT
A6025168883325558558256060
4. OUTPUT VOLTAGE RANGE V 4.5 4.5 5.0 18.0 5.0 5.0 10.0 18.0 18.0 18.0 5.0 18.0 18.0 5.0 2.7 2.7 1.8
-5.5 -5.5 -15.0 -28.0 -15.0 -15.0 -15.0 -28.0 -28.0 -28.0 -15.0 -28.0 -28.0 -15.0 -3.9 -3.9 -2.4
5.
MAXIMUM OUTPUT RIPPLE
mV 100 100 240 480 240 240 240 480 480 480 240 480 480 240 100 100 100
AND NOISE VOLTAGE (*1) P-P
6.
MAXIMUM LINE REGULATION
(*2) mV 25 25 60 72 60 60 60 72 72 72 60 72 72 60 25 25 25
7.
MAXIMUM LOAD REGULATION
(*3) mV 100 100 240 480 240 240 240 480 480 480 240 480 480 240 100 100 100
8.
OVERLOAD CURRENT PROTECTION
(*4) A 63.0 26.3 16.8 8.4 8.4 8.4 34.6 26.2 5.2 5.2 8.4 5.2 5.2 8.4 26.3 63.0 63.0
-78.0 -32.5 -20.8 -10.4 -10.4 -10.4 -42.9 -32.5 -5.8 -5.8 -10.4 -5.8 -5.8 -10.4 -32.5 -78.0 -78.0
9.
OVER VOLTAGE PROTECTION
(*5) V 6.3 6.3 16.2 32.4 16.2 16.2 16.2 32.4 32.4 32.4 16.2 32.4 32.4 16.2 4.1 4.1 2.71
-7.0 -7.0 -18.6 -37.2 -18.6 -18.6 -18.6 -37.2 -37.2 -37.2 -18.6 -37.2 -37.2 -18.6 -4.7 -4.7 -3.0
10.
OPERATING AMBIENT TEMPERATURE
0~+60°C ( 0~+50°C : 100%, +60°C : 75% )
11. REMOTE SENSING Available (without dual outputs module: E, H, P Module)
12. REMOTE ON/OFF CONTROL Option I J: output inhibits on each output (TTL level)
OUTPUT INHIBIT CONTROL MJ: output inhibits on all the outputs (TTL level)
13. SERIES OPERATION Available (can be operated in series between each output of Output Module and dual Outputs Module)
14. PARALLEL OPERATION Available (Please contact to Densei-Lambda before use in parallel operation of the Modules)
15.
OUTPUT VOLTAGE MONITOR SIGNAL
Option for I J Module: monitoring the output voltage up or down (TTL open collector)
16.
INPUT VOLTAGE DETECTOR SIGNAL
Option for M J Module: detecting the output of the active filter (TTL open collector)