132 Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
P Series
P Series
CORCOM Product Guide
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications
The P series power entry module offers fuller flexibility of
design in a more compact package.
As the first 10 amp module to provide all five power entry
functions in one compact design, the CHAMELEON
module readily adapts to its environment and the needs of
international markets.
Snap-in or flange mounting
IEC power line connector
Both North American and European fusing capabilities
Two voltage selections
Optional DPST on/off switch
Filtering options for general purpose, medical and
high-performance applications.
The CHAMELEON modules compact design and modular
construction will allow you to select the power entry
features you require — without altering the panel cutout.
And the Chameleon module, with adapters, will fit any
standard panel cutout.
The CHAMELEON module has four filter options.
S models offer protection for general purpose applica-
tions where line-to-ground and line-to-line noise must be
controlled. The filters are designed to meet low leakage
requirements of VDE portable equipment. They are
available in current ratings of 3, 6 and 10 amps.
H models provide susceptibility protection without leak-
age current associated with line-to-ground capacitors and
are designed to allow equipment to meet UL 544 for patient
care and non-patient care equipment.
Also available is an interconnection block, B models.
The block connects the voltage selection terminals of an
unfiltered CHAMELEON module with a switch and an IEC
connector to reduce external wiring.
L Models – High performance medical filter versions that
are designed to help bring most digital equipment (includ-
ing switching power supplies) into compliance with
EN55022, Level B (as well as FCC part 15J, Class B)
conducted emissions limits while additionally allowing
equipment to meet UL544, UL2601and EN60601 for patient
care equipment and non-patient care equipment. They are
available with current ratings of 6 and 10 amps. High
performance versions are available with horizontal mount-
ing ears, single voltage, complete can shield with options
for switch, fuses and current ratings only. Extenders are
not available.
Z Models – High performance filter versions are designed
to help bring most digital equipment (including switching
power supplies) into compliance with EN55022, Level B
(as well as FCC Part 15J, Class B) conducted emissions
limits. They are available with current ratings of 6 and 10
amps. High performance versions are available with
horizontal mounting ears, no extenders, single voltage,
complete can shield with options for switch, fuses and
current ratings only.
PS000SS30
PS Unfiltered PS Filtered
PE Filter with "A" Shield
UL Recognized
CSA Certified
VDE Approved
133
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
Power Entry Modules
CORCOM Product Guide
P Series Part Number Schematic
Part numbers are constructed by selecting the alphanumeric character which represents the desired feature.
Additional extender which allows the P series to adapt to CORCOM's L
series product cutout, as well as the panel cutout of Schaffner and Delta
parts is available.
* Extenders cannot be added to units with B shields.
P Series
PSJ0XSS60
Mounting Style
E = Mounting ears
(Horizontal)
S = Snap-in
M = Mounting ears
(Vertical)
Extender
Option
0 = None
C = FN260
J = J Series
L = L Series
Switch Option
0 = Blank
S = Double pole
single throw
(DPST)
Input Voltage Select
0 = Single voltage
S = Dual voltage
select (SMPS)
X = Dual voltage
select (series/parallel)
Fuse Options
D = Dual fuse
S = Single fuse
Filter Type
0 = No filter
B = Interconnection
block
H = Medical Filter
L = High Performance
Medical
S = General purpose
Z = High Performance
Filter Current
0 = No filter
3 = 3 amps
6 = 6 amps
X = 10 amps
Shield Options
0 = No shield
A = Filter shield
B = Complete
Shield
C = Complete can
(for L & Z models)
Mounting
Style
Extender
Options*
Switch
Options
Voltage
Select
Fuse
Options
Filter
Type
Filter
Current
Shield
Options*
**
**
**
***
The part number PSJ0XSS60 would represent the equivalent of the Corcom
J Series 6J4:.
P Series (P)
with a snap-in mount (S)
with the J extender to fit the 6J4 cutout(J), and includes no switch (0)
dual voltage select (X)
single fusing (S),
general purpose filter (S)
for 6 amps (6)
with no shield (0).
Extender for
J-Series or others
Optional filter
Optional switch
Fuse holder
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
Notes:
An additional extender which allows the P series to adapt to Corcom's L
series product cutout as well as the panel cutout of Schaffner and Delta
parts is also available.
Extenders cannot be added to units with B shields
When using the interconnection block, the last 3 digits of the part number
are BX (0, A, or B)
For alternative switch orientation options, please contact technical sup
port or your Corcom sales representative
** Dual voltage options only available with filter types O, H or S
••• High performance versions are available with horizontal mounting ears
(PE style), no extenders, single voltage, complete can shield with options
for switch, fuses, filter type (L or Z) and 6 or 10 amp current ratings only.
Input Voltage Selection Schemes
X - Dual Primary Transformer Type
S - Jumper Type
134 Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
CORCOM Product Guide
115V 230V
Note 1 Note 1
Note 1
Note 1
A
B
C
D
Power on/off
Neutral
Provision for
single fusing
G
H
Power
input
Sel.
Jumpers
SMPS
Hot
Ground
Note 1: Jumpers are required if a filter or interconnection module is not
used.
Note 2: Location of optional filter. Jumpers are required if a filter or
interconnection block is not used.
The P series of power entry modules provides a dual volt-
age selector which is integrated with the fuseholder. To
simplify the wiring in each individual application, Tyco
Electronics provides dedicated voltage selectors for differ-
ent voltage selection schemes. The two most popular
schemes are the parallel and serial for dual primary trans-
formers and the “DPST switch” for switching mode power
supplies (jumper types.) P series products with an “S” as
the fifth digit are specifically designed for “jumper” type
applications associated with switching mode power sup-
plies. P series products with an “X” as the fifth digit are
specifically designed for dual primary transformer applica-
tions. The voltage selector installed will allow proper wiring
from these applications. No matter what voltage selection
scheme is used, wiring is always made to the same four
terminals.
P Series
Voltage Selection
A Shield BShield
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
115V 230V
Note 1 Note 2
Note 2
Note 1
A
B
C
D
Power on/off
115V
115V
Neutral
Provision for
single fusing
Transformer
primary
G
H
Hot
Ground
Shield
A new feature available on the P series is an RF shield. The
metal shield, available on filtered models, provides shield-
ing from radiated emissions and provides an additional RF
ground for the filter to the case. The shield is available in
two versions, a shield of the filter components (designated
by A as the ninth digit) and a complete shield (designated
by B as the ninth digit). The A shield covers the filter por-
tion of the module and increases performance of the filter
by protecting the components from magnetic coupling.
This shield improves RF ground connection to the case
while still allowing the use of the P Series extender. The B
shield covers the entire power entry module with metal,
protecting the equipment from all radiated noise. Used
with the filter, the shield provides the most secure protec-
tion from RFI noise problems. The B shield cannot be used
with any extender.
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
135
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
Power Entry Modules
P Series
CORCOM Product Guide
Fuseholder
Another feature of the P series power entry module is a ver-
satile fusing arrangement. Its fuseholder can hold two 1/4”
x 1-1/4” or 5 x 20mm fuses. It can also be converted to
accept one fuse with a conversion clip that bridges one of
the two fuse chambers. The conversion clip is installed on
the P Series power entry modules set for single fusing
(those with part numbers with an “S” as the sixth digit).
Units with a “D” as the sixth digit do not include a conver-
sion clip.
Interconnection Block
Also available is an interconnection block (B models). The
block connects the voltage selection terminals of an unfil-
tered CHAMELEON module with a switch and an IEC con-
nector to reduce external wiring. Installation of the unfil-
tered versions of the P series involves wiring of the IEC
socket to the switch and the switch to the fuseholder. Labor
can be eliminated by ordering the product with an intercon-
nection block. This feature, designated by a BX in the sev-
enth and eighth digits, pre wires the module for easier
installation. The wiring is protected with the plastic case to
better prevent access to the terminals and connections.
The dimensions of this alternative are the same as the
filtered versions.
Accessories
A full range of accessories are available for the P Series.
To simplify customer installation wiring can be simplified by
ordering a PA100 connector assembly which is pre-wired
with 6" of wire lead.
See page 143 for a complete list of all accessories
available for this series.
Interconnection Block installed in place of filer.
Fuseholder shown with 5x20mm fuse
Conversion clip included for use in single
fuse applications.
PA100 Assembly
136 Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
P Series
CORCOM Product Guide
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
Specifications
Maximum leakage current, each line-to-ground: †
H & LModels S & Z Models
@ 120 VAC 60 Hz: 2 µA.25 mA
@ 250 VAC 50 Hz: 5 µA.50 mA
†Applies to Filtered models only
Hipot rating (one minute):
line-to-ground 1500 VAC
line-to-line 1450 VAC
Operating frequency: 50/60 Hz
Rated voltage: 250 VAC
Operating voltages:
Selectable or Fixed 115/230 VAC
Rated current: Unfiltered – 10A
Filtered – 3, 6 or 10A
Switch: Double-insulated, rated
for 10,000 operations at full load at
51 Amp inrush current.
Fuseholder: Accepts one or two fuses
1/4 x 1-1/4 or 5 x 20 mm
Conversion clip provided on fuseholder
for single fuse models.
Terminals:
Standard versions: .187 x 0.032
[4.8 x .81] terminal tabs
High performance versions: .250 x 0.032
[6.4 x .81] terminal tabs
Recommended for use with mating connector - no solder
Minimum insertion loss in dB:
Line-to-ground in 50 ohm circuit
Current Frequency-MHz
Rating .03 .1 .15 .5 1 3 5 10 30
H Models
03A 7 17 21 27 30 29 26 23 15
06A - 8 11 15 17 19 18 16 13
10A 3 5 8 10 12 11 11 10 10
S Models
03A 7 17 21 27 33 40 44 50 32
06A - 8 12 17 23 32 36 44 30
10A - 3 5 10 13 23 27 35 27
Current Frequency-MHz
Rating .01 .05 .1 .15 .5 1 5 10 30
Z Models
06A 8 21 27 30 37 43 49 52 42
10A 5 17 22 24 27 32 52 47 40
L Models
06A 8 21 27 29 34 35 25 21 16
10A 5 17 22 23 24 25 21 18 14
Line-to-line in 50 ohm circuit
Current Frequency-MHz
Rating .10 .15 .5 1 3 5 10 30
H Models
03A 2 4 12 18 31 40 48 41
06A 2 4 12 16 26 35 40 35
10A 2 4 12 16 26 33 40 32
S Models
03A 2 4 12 15 30 48 50 45
06A 2 4 12 15 22 42 55 45
10A 2 4 12 15 22 42 55 45
Current Frequency-MHz
Rating .01 .05 .1 .15 .5 1 5 10 30
Z Models
06A 10 15 34 44 75 75 75 70 60
10A 10 20 20 35 67 75 75 70 60
L Models
06A 10 15 34 44 75 75 75 70 60
10A 10 20 20 35 67 75 75 70 60
S Model
H Model
LINE LOAD
L Model
LINE LOAD
Z Model
Electrical Schematics
137
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
Power Entry Modules
P Series
CORCOM Product Guide
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
Case Styles
PS/PSL
PE
B2
C
.225
5.72
A
.225
5.72 B1
C
Unltered Filtered
D
E
.06
1.52 R Max
.020
.508 R Min
(Note 1)
Panel Cutout
Note1: For snap-in applications, the D sides of the cutout must have a .02 [.508] radius on the installation side.
Snap-in models allow front mounting only. Not recommended for plastic panels.
B1
C
.225
5.72
A
F
D
Max. B2
C
.225
5.72
Max.
Unltered Filtered
D
E
.06
1.52 R Max
.020
.508 R Min
F
Panel Cutout
PM
Typical dimensions:
Terminals: .187 x 0.032 [4.8 x .81] terminal tabs Holes: .055 [1.5] Dia. ± .004 [.10]
Slot (Ground Terminal): .06 x .115 [1.52 x 2.92] ± .004 [.10] Mounting Holes (PE, PM only) : .135 [3.43] Dia. (2) countersunk
138 Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
P Series
CORCOM Product Guide
PE High Performance
Unltered Filtered
A
B1
C
.225
5.72
Max.
B2
.225
5.72
D
E
.06
1.52 R Max
.020
.508R Min
(Note 1)
Panel Cutout
A
C
3.93 Max.
B2
2.17 Max.
F.225
5.72 D
Rear View
2.39 Max.
Note 1: For snap-in applications, the D sides of the cutout must have a .02 [.508] radius on the installation side. Snap-in models, allow front mounting only.
Note 1: Use cutout for PE Style.
Case Styles(continued)
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
Typical dimensions:
Terminals: .187 x 0.032 [4.8 x .81] terminal tabs Holes: .055 [1.5] Dia. ± .004 [.10]
Slot (Ground Terminal): .06 x .115 [1.52 x 2.92] ± .004 [.10] Mounting Holes (PE, PM only) : .135 [3.43] Dia. (2) countersunk
Typical dimensions:
Terminals: .250 x 0.032 [
6.4 x .81
] terminal tabs Holes: .07 [
1.8
] Dia. (2)
Slot (Ground Terminal): .07 x .16 [
1.8 x 4.1
] Mounting Holes: .135 [
3.43
] Dia. (2) countersunk
PSC/PSJ
139
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
Power Entry Modules
P Series
CORCOM Product Guide
Rear View
Case Dimensions
Part No. A B1 B2 C D E F
(max) (max) (max) (max)
PS 1.24 1.93 2.13 2.31 1.06
2.201*
31.49 49.02 54.1 58.67 26.93 55.91
PSL 1.24 1.93 2.13 2.31 1.12 2.201*
31.49 49.02 54.1 58.67 28.45 55.91
PE 1.98 1.93 2.13 2.31 1.122 2.201* 1.575
50.29 49.02 54.1 58.67 28.5 55.91 40.0
PM 1.24 1.93 2.13 2.9 1.06 2.13 2.496
31.49 49.02 54.1 73.66 26.93 54.1 63.4
PSC 1.24 1.93 2.13 2.51 1.06 2.52
31.49 49.02 54.1 63.75 26.93 64.01
PSJ 1.24 1.93 2.13 2.72 1.06 2.6+
31.49 49.02 54.1 69.09 26.93 66.0
PE 1.98 4.42 2.31 1.12 2.201 1.575
High 50.29 112.27 58.67 28.5 55.91 40.0
Performance
* Panel cutout for thickness of .031 - .079 [0.8 - 2.0]. For panel thickness
at .083 - .114 [2.1 - 2.9] use 2.213 [56.21].
+ Panel cutout for thickness of 0.06 - 0.09 [0.76 - 2.29].
For shielded models use D=1.12 +.008/-.000.
+.008/-.000
+.20/-.00
+.008/-.000
+.20/-.00
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
Shielding
2.19 Max
0.225
.508
Max.
0.225
.508
Max.
2.19 Max
A Shield B Shield
ABCDABCD
GND GND
LN
Filtered Unltered
Shields can be used only with filtered models.
Shields add approximately 0.06" to depth.
B shield may not be used with J or C extender.