B-8 Switch Mode Power Supply S8VS
Specifications
■Ratings/Characteristics
Note: 1. Refer to the Engineering Data section on page B-21 for details.
2. If the V.ADJ adjuster is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models). When adjusting the output voltage,
confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
3. To reset the protection, turn OFF the power supply for three minutes or longer and then turn the power supply back ON.
4. Displayed on 7-segment LED. (character height: 8 mm)
5. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (percentage of output voltage value, ±1 digit)
6. Resolution of output current indication: 0.1 A; Precision of output current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage)
7. Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage);
Signal width required for peak-hold current: 20 ms
8. A Type and B Type: Sinking, AP Type and P Type: Sourcing
9. To ensure the emission rating, a ferrite ring core should be used in all cabling (TDK HF60T, HF70RH or equivalent model).
10. The typical values indicate the values for an input condition of 230 VAC. All items are measured at a frequency of 50 Hz.
Power ratings 60 W 90 W
Type
Item
Standard Maintenance
forecast monitor Total run time
monitor Standard Maintenance
forecast monitor Total run time
monitor
Efficiency (typical) 78% min. (86% typ.) 80% min. (87% typ.)
Input Voltage 100 to 240 VAC (85 to 264 VAC)
Frequency 50/60 Hz (47 to 450 Hz)
Current 100 V input 1.7 A max. 2.3 A max.
200 V input 1.0 A max. 1.4 A max.
230 V input (0.7 A typ.) (0.9 A typ.)
Power factor ---
Harmonic current emissions Conforms to EN61000-3-2
Leakage current 100 V input 0.5 mA max.
200 V input 1.0 mA max.
230 V input (0.40 mA typ.) (0.35 mA typ.)
Inrush current
(See note 1.) 100 V input 25 A max. (for a cold start at 25°C)
200 V input 50 A max. (for a cold start at 25°C)
230 V input (47 A typ.) (38 A typ.)
Output Voltage adjustment range (See note 2.) −10% to 15% (with V.ADJ) (guaranteed)
Ripple 2.0% (p-p) max. (at rated input/output voltage)
f=20MHz measuring (0.29% (p-p) typ.) (0.38% (p-p) typ.)
f=100MHz measuring (0.32% (p-p) typ.) (0.42% (p-p) typ.)
Input variation influence 0.5% max. (at 85 to 264 VAC input, 100% load)
Load variation influence (rated input voltage) 1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence 0.05%/°C max.
Start up time (See note 1.) 1,000 ms max. (at rated input/output voltage)
(270 ms typ.) (260 ms typ.)
Hold time (See note 1.) 20 ms min. (at rated input/output voltage)
at 100% load (220 ms typ.) (190 ms typ.)
Additional
functions Overload protection (See note 1.) 105% to 160% of rated load current, voltage drop, intermittent, automatic reset
Overvoltage protection (See notes 1 and 3.) Yes
Output voltage indication (See note 4.) No Yes (selectable) (See note 5.) No Yes (selectable) (See note 5.)
Output current indication (See note 4.) No Yes (selectable) (See note 6.) No Yes (selectable) (See note 6.)
Peak-hold current indication (See note 4.) No Yes (selectable) (See note 7.) No Yes (selectable) (See note 7.)
Maintenance forecast monitor indication (See note 4.) No Yes (selectable) No No Yes (selectable) No
Maintenance forecast monitor output No Yes (open collector out-
put), 30 VDC max., 50
mA max. (See note 8.)
No
Total run time monitor indication (See note 4.) No Yes (selectable) No Yes (selectable)
Total run time monitor output No Yes (open collector out-
put), 30 VDC max., 50
mA max. (See note 8.)
Undervoltage alarm indication (See note 4.) No Yes (selectable) No Yes (selectable)
Undervoltage alarm output terminals No Yes (open collector output)
30 VDC max., 50 mA max. (See note 8.)
Parallel operation No
Series operation Yes for up to 2 Power Supplies (with external diode)
Other Operating ambient temperature Refer to the derating curve in Engineering Data. (with no icing or condensation)
Storage temperature −25 to 65°C
Operating ambient humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength 3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance 100 MΩ min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in-X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (color: green)
EMI Conducted
Emissions Conforms to EN61204-3 EN55011 Class A and based on FCC Class A
Conforms to EN61204-3 EN55011 Class B (See note 9.)
Radiated
Emissions Conforms to EN61204-3 EN55011 Class A
Conforms to EN61204-3 EN55011 Class B (See note 9.)
EMS Conforms to EN61204-3 high severity levels
Approved standards UL: UL508 (Listing, Class 2: Per UL1310), UL60950
cUL: CSA C22.2 No.14 (Class 2), No.60950
EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0805)
SELV (EN60950/EN50178/UL60950-1)
According to VDE0106/P100, IP20
UL: UL508 (Listing), UL60950
cUL: CSA C22.2 No.14, No.60950
EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0805)
SELV (EN60950/EN50178/UL60950-1)
According to VDE0106/P100, IP20
Weight 330 g max. 490 g max.