Operation (H3DE-H)
An
interval of 3 s minimum is required to turn on the H3DE after the
H3DE is turned of
f. If the H3DE is turned on and of
f repeatedly with
an interval of shorter than 3 s, the internal parts of the H3DE may
deteriorate
and the H3DE may malfunction.
Power
Output
state
1
3 s min.
Output
state 2
If
it is required that the output be turned
on repeatedly with an inter
-
val
of shorter than 3 s, consider use of
the H3DE-M2/-M1 in mode D
(signal OFF-delay).
Precautions for VDE Conformance
The
H3DE as a built-in timer conforms to VDE 0435/P2021 provided
that
the following conditions are satisfied:
The
output section of the H3DE is provided only with basic isolation.
To
ensure reinforced
isolation required by the VDE standards, pro
-
vide supplementary basic isolation on the load side connected to
the
output.
The H3DE itself is designed according to the following:
•Overvoltage category III
•
Pollution degree 2
On the above basis:
Operation parts on the front and bottom: Reinforced isolation
– With clearance of 5.5 mm and creepage distance of 5.5 mm at
230 V
AC
Output:
Basic isolation
– With clearance of 3 mm and creepage distance of 3 mm at
230 V
AC
Environment
When
using the
T
imer in an area with excess electronic noise, sepa
-
rate
the T
imer
, wiring, and the equipment which generates the input
signals
as far as
possible from the noise sources. It is also recom
-
mended
to shield the input signal wiring to prevent electronic inter
-
ference.
Organic solvents (such as paint thinner), as well as very acidic or
basic
solutions can damage the outer casing of the T
imer.
Do
not use the T
imer in places where it is exposed to dust, corrosive
gas,
or direct sunlight.
When storing the Timer, make sure that the ambient temperature
and
humidity are within the rated values. Leave the
T
imer at room
temperature
for at least three hours before using the T
imer if it
has
been
stored at an ambient temperature of –10
°
C or below
.
Others
If
the T
imer is mounted on a control board, dismount the T
imer
from
the control board or short-circuit the circuitry of the power board be
-
fore carrying out a voltage withstand test between the electric cir-
cuitry and non current-carrying metal part of the Timer, in order to
prevent
the internal circuitry of the T
imer from damage.
It must be noted that although the electrical life expectancy of the
H3DE
T
imer shown in the catalog is the same as the H3DR T
imer
shown in the catalog, the actual performance varies because the
built-in
relays are different as follows:
Built-in relay for the H3DR:
G2R; 100,000 operations min.
(10 A for SPDT and 5 A for DPDT at
250 VAC, resistive load at
1,800 operations/h.)
Built-in
relay for the H3DE:
G6RN; 50,000 operations min.
(8 A at 250 VAC, resistive load at
360 operations/h.)