02/66
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
DUO series Contactors
SC-E series
Operation conditions
■ Standard operating conditions
The magnetic contactors are manufactured for use in the
standard operating conditions given in the table at the right.
Consult FUJI before using the magnetic contactors in different
conditions.
■ Wirings
• Connection wires and terminal processing
Be sure to perform wiring correctly with reference to the
connections diagram. Main terminals for models SC-E02 to
SC-E7 are wired using solid wires or stranded wires.
Stranded wires or flexible stranded wires can be connected
by twisting them together, crimping a sleeve (ferrule) onto
them before connecting.
• Tightening torque
If wires are not tightened sufficiently, they may become hot or
come loose and result in a fire, short-circuit, electric shock, or
some other potentially dangerous situation. Be sure to tighten
the wires to the torques specified in the tables below.
•Connectable wire sizes, tightening tools, tightening torques
Main circuit
Contactor type
Solid wire
(mm
2
)
Stranded wire
(mm
2
) *
1
AWG
Sheath stripping length
(mm)
Te r minal screw size
Tool
Tightening torque (N·m)
One
Two
One
Two
One
Two
SC-E02, SC-E03, SC-E04, SC-E05
0.75 to 6
1 to 4 or 1.5 to 6
0.75 to 6
1 to 4 or 1.5 to 6
18 to 10
18 to 12 or 16 to 10
M4
+
Phillips screwdriver, H-type, No. 2
(ISO 8764)
–
Flat-blade screwdriver, 1 5.5 L-type, B
(ISO 2830)
1.2 to 1.5
11
SC-E7
4 to 120
2.5 to 95
4 to 95
12 to 250MCM
28.5
4 to 120
2.5 to 95
4 to 95
12 to 250MCM
28.5
4 to 120
2.5 to 95
4 to 95
12 to 250MCM
10
Contactor type SC-E1, E2, E2S
0.75 to 35
0.75 to 25
0.75 to 25
18 to 2
15
0.75 to 25
0.75 to 16
0.75 to 16
18 to 3
12.5
0.75 to 25
0.75 to 16
0.75 to 16
18 to 3
+
Phillips screwdriver, H-type, No. 2
(ISO 8764)
–
Flat-blade screwdriver, 1 5.5 L-type, B
(ISO 2830)
2.5
1
SC-E3, E4
1 to 70
1 to 50
1 to 50
16 to 2/0
19.5
1 to 50
1 to 35
1 to 35
16 to 1/0
16
1 to 50
1 to 35
1 to 35
16 to 1/0
Hex. wrench 4 (ISO 2936)
8
2
Tool
Tightening torque (N·m)
Self-locking torque (N·m) *
2
SC-E5, E6
2.5 to 70
2.5 to 50
2.5 to 50
12 to 2/0
26.5
2.5 to 70
2.5 to 50
2.5 to 50
12 to 2/0
26.5
2.5 to 70
2.5 to 50
2.5 to 50
12 to 2/0
Top-only
connection
Bottom-only
connection
Top/bottom
connection
Solid or stranded wire (mm
2
) *
1
Flexible stranded wire with sleeve (mm
2
)
Flexible stranded wire without sleeve (mm
2
)
AWG
Sheath stripping length (mm)
Solid or stranded wire (mm
2
) *
1
Flexible stranded wire with sleeve (mm
2
)
Flexible stranded wire without sleeve (mm
2
)
AWG
Sheath stripping length (mm)
Solid or stranded wire (mm
2
) *
1
Flexible stranded wire
with sleeve (mm
2
)
Flexible stranded wire
without sleeve (mm
2
)
AWG
Top/bottom
Top/bottom
Top/bottom
Top/bottom
Operating: –5 to 55˚C
No sudden temperature changes resulting in
condensation or icing (The average temperature over
a 24-hour period must not exceed 35˚C)
Storage:
–40 to 65˚C
45 to 85%RH
2000m or lower
No excessive dust, smoke, corrosive gases,
flammable gases, steam, or salt
10 to 55Hz 15m/s
2
50m/s
2
Screw mounting, 35mm IEC top hat rail mounting
(SC-E02 to SC-E4)
IEC 60947-4-1, EN 60947-4-1, VDE 0660
JIS C 8201-4-1, UL 508, CSA C22.2
TÜV (EN60947-4-1)
Ambient
temperature
Humidity
Altitude
Atmosphere
Vibration
Shock
Mounting
Mounting
angle
Standard
30˚
30˚
30˚
30˚
Solid or stranded
wire (mm
2
)
AWG
Sheath stripping length
(mm)
Fork terminal
Te r minal screw size
Tool
Tightening torque (N·m)
0.75 to 2.5 (ø1 to 1.6)
0.75 to 1.5 or 1.5 to 2.5
18 to 14
18 to 14
Max. 7.7mm wide
M3.5
+
Phillips screwdriver, H-type, No. 2
(ISO 8764)
–
Flat-blade screwdriver, 1 5.5 L-type, B
(ISO 2830)
0.8 to 1
One
Two
One
Two
10
Notes: *1Stranded wire (0 to 35mm2) consists of 7 wires or less.
Stranded wire (38 to 120mm2) consists of 19 wires or less.
Flexible stranded wire consists of more number wires than the above.
*2The tightening bolt must be loosened in order to insert the wire. However, stop
loosening the bolt when the anti-drop attachment on the bottom of the bolt
reaches the top edge of the terminal. If a torque exceeding that given in the
table is applied in this state, the retaining plate may come loose.
Control circuit