2Specifications are subject to change without notice (21.11.2003)
Output Specifications
RN1S...30.. RN1S...50..
Rated operational load current
AC 51 @Ta= 30°C 30 Arms 50 Arms
@Ta= 40°C 30 Arms 50 Arms
@Ta= 50°C 23 Arms 38 Arms
@Ta= 60°C 20 Arms 30 Arms
AC 53a @Ta= 40°C 6 Arms 12 Arms
Zero crossing detection Yes Yes
Min. operational current 200 mA 200 mA
Non-rep. surge current t = 10 ms
(Tj init. = 25°C) ≤250 Ap≤600 Ap
Off-state leakage current @ rated voltage and frequency
(Tj. = 125°C, max.) < 6 mA < 6 mA
I2t for fusing t = 1 to 10 ms 310 A2s 1800 A2s
Critical dV/dt off-state 500 V/µs 500 V/µs
RN1S .......
General Specifications
Control Specifications
Supply voltage range 20 to 32 V
Supply current ≤40 mA
Response time pick-up @ 50 Hz
≤10 ms
Response time drop-out @ 50 Hz
≤10 ms
Active high control input
Pick-up voltage Typ. 7 VDC
Drop-out voltage Typ. 6.8 VDC
Input current (Vc = 32 V) ≤4 mA
Active low control input
Pick-up voltage Typ. Vcc - 10 VDC
Drop-out voltage Typ. Vcc - 10 VDC
Input current (Vcc = 32 V) ≤4 mA
PNP alarm output
Alarm output voltage open ≤0 VDC
Alarm output voltage @ 100 mA
Vcc - 2 VDC
Alarm output current ≤100 mA
NPN alarm output
Alarm output voltage open ≤32 VDC
Alarm output voltage @ 100 mA
2 VDC
Alarm output current ≤100 mA
Sense Specifications
RN1S23..... RN1S40..... RN1S48.....
Current
Sensed load current ≥50 mA ≥50 mA ≥50 mA
Non-sensed leakage current ≤20 mA ≤20 mA ≤20 mA
Voltage
Sensed line voltage ≥120 Vrms ≥150 Vrms ≥180 Vrms
Non-sensed line voltage ≤50 Vrms ≤80 Vrms ≤100 Vrms
Timing
Response time from fault
to alarm output ≤100 ms ≤100 ms ≤100 ms
Short-circuit of semiconductor Will be sensed Will be sensed Will be sensed
RN1S23..... RN1S40..... RN1S48.....
Operational voltage range 120 to 265 VAC 150 to 440 VAC 180 to 530 VAC
Non-rep. peak voltage 800 Vp1000 Vp1200 Vp
Varistor voltage 275 VAC 420 VAC 510 VAC
Zero voltage turn-on ≤15 V ≤15 V ≤25 V
Operational frequency range 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz
Power factor ≥0.5 @ 230 VAC ≥0.5 @ 400 VAC ≥0.5 @ 480 VAC
Approvals UL, cUL, CSA UL, cUL, CSA UL, cUL, CSA
CE-marking
Yes Yes Yes
Norms fulfilled EN 60947-1 Low-voltage switchgear and control gear. Part 1- General Rules.
EN 61000-6-2 Generic Immunity Standard. Industrial Environment