Low-Peak®CUBEFuse® With and Without Indication
Finger-Safe, Dual-Element, Time-Delay Class J Performance Fuse, 1-100A, 600Vac/300Vdc
0309 BU-SB09230 Page 1 of 2 Data Sheet 9000
Catalog Symbols: TCF_ Indicating fuse (6-100A)
TCF_RN Non-indicating fuse (1-100A)
Dual-Element, Time-Delay Fuse: 10 Seconds Minimum Operating Time at
500% Rated Current
Ampere Rating: 1 to 100A
Voltage Rating: 600Vac/300Vdc
Interrupting Rating: 300kA RMS Sym. (UL)
200kA RMS Sym. (CSA)
100kA DC (UL & CSA)
Agency Information:
• UL Listed Special Purpose Fuse: Guide JFHR, File E56412
• CSA Certified Fuse: Class 1422- 02, File 53787
• CE compliance for the European Union low voltage directive
Other Ratings/Specifications:
Watts Loss at rated current: TCF30: 3.99W
TCF60: 6.23W
TCF100: 9.51W
Operating and Storage Temperature Range: 14 to 149°F(-10 to 65°C)
Material Specifications:
• Case: Glass filled PES (Polyethersulfone)
• Terminals: Copper alloy
• Terminal plating: Electroless tin
• Indicator lens: PES (Polyethersulfone)
(indicating version only)
• Indicator: Energetic chemical
Carton Quantity and Weight
Catalog Numbers (amp rating)
Indicating CUBEFuse
TCF6 TCF10 TCF15 TCF17-1/2TCF20 TCF25
TCF30 TCF35 TCF40 TCF45 TCF50 TCF60
TCF70 TCF80 TCF90 TCF100
Non-Indicating CUBEFuse
TCF1RN TCF3RN TCF6RN TCF10RN TCF15RN TCF17-1/2RN
TCF20RN TCF25RN TCF30RN TCF35RN TCF40RN TCF45RN
TCF50RN TCF60RN TCF70RN TCF80RN TCF90RN TCF100RN
Features and Product Benefits
The world’s first finger-safe power fuse system.
Smallest footprint of any class fuse including Class J, CC, T and RK.
Meets Class J time-delay electrical performance requirements.
Available with and without open fuse indication to meet every customer
requirement.
The indicating version features
easyI
D™ open fuse technology for faster
troubleshooting and reduced downtime.
Faster response to damaging faults to help reduce destructive thermal and
magnetic forces.
True dual-element fuse construction with a minimum of 10 seconds time-
delay at 500% of rating.
Long time-delay minimizes nuisance circuit openings due to temporary
overloads and transient surges.
High interrupting rating to safely interrupt faults up to 300kA.
No venting of arc or molten metal and gases during opening.
Robust cycling and inrush current withstand.
Low let-through currents under fault conditions.
Provides Type 2 “No Damage” protection for IEC motors starters when
properly sized.
Easy selective coordination with any other Cooper Bussmann®Low-Peak®
Class L, J and RK1 fuse with simple 2:1 amp ration between upstream and
downstream fuses.
Amp Carton Weight Per Carton
Rating Qty. lbs kg
TCF1-30A 12 1.39 0.63
TCF35-60A 12 1.42 0.65
TCF70-100A 6 1.74 0.79
CCPB 1-, 2- & 3-Pole disconnects for
the Quik-Spec™ Coordination
Panelboard. Data Sheet 1160
CF_ Quik-Spec™ Safety
Switch disconnect (optional
window). Data Sheet 1156
TCFH_N 100, 60 & 30A Holders.
Data Sheet 9007
CCP_CF 1-, 2- & 3-Pole
switched disconnects
Data Sheet 1157
CUBEFuse Holders, Disconnects and Safety Switch
The CUBEfuse is used in the following Cooper Bussmann®products.
70-100A Case Size 35-60A Case Size 1-30A Case Size
© 2009 Cooper Bussmann
St. Louis, MO 63178
www.cooperbussmann.com
0309 BU-SB09230 Page 1 of 2 Data Sheet 9000
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information con-
tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
TCF_ and TCF_RN Dimensions – in (mm)
Time-Current Characteristic Curves–Average Melt Current Limitation Curves
Fuse Dimensions - in (mm)
Amps A B C D E F G
1-15 1.88 0.75 1.00 0.23 0.04 0.63 0.27
(47.75) (19.05) (25.40) (5.84) (1.02) (15.88) (6.86)
17.5-20 1.88 0.75) 1.00 0.27 0.04 0.63 0.27
(47.75) (19.05) (25.40) (6.86) (1.02) (15.88) (6.86)
25-30 1.88 0.75 1.00 0.31 0.04 0.63 0.27
(47.75) (19.05) (25.40) (7.94) (1.02) (15.88) (6.86)
35-40 2.13 1.00 1.13 0.36 0.04 0.63 0.38
(54.10) (25.40) (28.58) (9.14) (1.02) (15.88) (9.65)
45-50 2.13 1.00 1.13 0.40 0.04 0.63 0.38
(54.10) (25.40) (28.58) (10.16) (1.02) (15.88) (9.65)
60 2.13 1.00 1.13 0.44 0.04 0.63 0.38
(54.10) (25.40) (28.58) (11.11) (1.02) (15.88) (9.65)
70-100 3.01 1.00 1.26 0.57 0.06 0.63 0.39
(76.45) (25.40) (32.00) (14.4) (1.60) (15.88) (9.93)