General Purpose US Fuses
General Purpose US Fuses
GPUS17
American Power Fuses
AMP-TRAP 2000®
ATDR (Class CC TD)
The best protection for
today’s small motors
Amp-trap 2000® ATDR small-dimension fuses can provide
IEC Type 2 “no damage” protection to your facility’s
increasingly sensitive branch circuit components and
small motors – minimizing the risk of fault-related
damage. ATDR Class CC fuses deliver the best time delay
characteristics in their class with excellent cycling ability
for small motor loads.
Features/Benefits
• Time delay for motor starting inrush currents without
nuisance opening
• Highly current limiting for low peak let-thru current
• Improved cycling ability for frequent motor starts/stops
without nuisance fuse opening
• Rejection-style design prevents replacement errors
(when used with recommended fuse blocks)
• High-visibility orange label ensures instant recognition,
simplifies replacement
• Metal-embossed date and catalog number for
traceability and lasting identification
• Fiberglass body provides dimensional stability in harsh
industrial settings
• High-grade silica filler ensures fast arc quenching
and optimum current limitation
Ratings
AC: 1/4 to 30A 600VAC, 200kA I.R.
DC: 1/4 to 30A 300VDC, 100kA I.R.
Highlights
• Time Delay
• Best Choice for Small Motor Protection
• Highly Current-Limiting
• AC & DC Rated
Applications
• Small Motors
• Contactors
• Lighting, Heating and General Loads
• Branch Circuit Protector
Approvals
• UL Listed to Standard 248-4
CSA Certified to Standard
C22.2 No. 248.4
DC Listed to UL Standard 198L
12/04
ADDER 30310R 30320R 30350R W204857 Z217510 N213429
1 USCC1I 30311R 30321R 30351R X213943 R212397 M218534 G213929
2 USCC2I 30312R 30322R 30352R D217008 Z212910 Y219579 V214447
3 USCC3I 30313R 30323R 30353R Y218038 M213428 B222779 X214955
Number
of
Poles
Screw
Connector
w/ Double
Quick
Connects
Copper
Box
Connector
Screw
Connector
w/ Double
Quick
Connects
Pressure
Plate
Connector
w/ Double
Quick
Connects
Copper
Box
Connector
Ultrasafe
Indicating
Fuse
Holder
Ultrasafe
Indicating
Fuse
Holder
Catalog Number Reference number
Pessure
Plate
Connector
w/ Double
Quick
Connects
General Purpose US Fuses
General Purpose US Fuses
GPUS18
American Power Fuses
AMP-TRAP 2000®
ATDR (Class CC TD)
Motor ATDR Rating*
Full load Minimum Normal
Amperes Duty Duty
.71 - .89 1-1/4 1-6/10
.90 - 1.19 1-6/10 2
1.20 - 1.34 2 2-1/2
1.35 - 1.79 2-1/2 3
1.80 - 2.25 3 4
2.26 - 2.69 4 5
2.70 - 2.90 4 6
2.91 - 3.20 5 6
3.21 - 3.75 5 7
3.76 - 4.50 6 8
4.51 - 5.34 8 10
5.35 - 5.69 10 12
5.70 - 6.70 12 12
6.71 - 7.79 12 15
7.80 - 8.88 15 17-1/2
8.89 - 11.1 17-1/2 20
11.2 - 13.3 20 25
13.4 - 15.2 25 30
Recommended Fuse Blocks for Class CC Fuses
Small Motor Fuse Protection,
600 Volts AC or Less
Standard Fuse Ampere Ratings
Dimensions
* The 1996 National Electrical
Code allows time-delay Class CC fuses
to be sized at up to 400% (maximum)
of motor FLA, if needed.
12/04
1/4 ATDR1/4 W200855
1/2 ATDR1/2 Q223068
8/10 ATDR8/10 K201397
1 ATDR1 T217275
1-1/8 ATDR1-1/8 Y218820
1-1/4 ATDR1-1/4 J218301
1-4/10 ATDR1-4/10 K219337
1-1/2 ATDR1-1/2 Y217785
1-6/10 ATDR1-6/10 K219866
1-8/10 ATDR1-8/10 Z222547
2 ATDR2 S212168
2-1/4 ATDR2-1/4 T213204
2-1/2 ATDR2-1/2 J212689
2-8/10 ATDR2-8/10 L213703
3 ATDR3 Y215232
3-2/10 ATDR3-2/10 J216254
3-1/2 ATDR3-1/2 C215742
4 ATDR4 V217276
4-1/2 ATDR4-1/2 Z217786
5 ATDR5 K218302
5-6/10 ATDR5-6/10 Z218821
6 ATDR6 L219338
6-1/4 ATDR6-1/4 L219867
7 ATDR7 A222548
7-1/2 ATDR7-1/2 R223069
8 ATDR8 X200856
9 ATDR9 Y201915
10 ATDR10 J201396
12 ATDR12 X201914
15 ATDR15 V211135
7-1/2 ATDR17-1/2 L211656
20 ATDR20 R214214
25 ATDR25 V214723
30 ATDR30 G216758
Ampere Catalog Reference Ampere Catalog Reference
Rating Number Number Rating Number Number
General Purpose US Fuses
General Purpose US Fuses
GPUS19
American Power Fuses
AMP-TRAP 2000®
ATDR (Class CC TD)
12/04
TIME IN SECONDS
CURRENT IN AMPERES
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
ATDR 1/4 to 30
MELTING TIME – CURRENT DATA, 600V FUSES
Peak Let-Thru Current Data – ATDR 1/4 to 30, 600 Volts AC