Application
Edition
SINAMICS DCM as a DC voltage source
01/2014
SINAMICS drives
Answers for industry.
© Siemens AG 2014. All rights reserved
A5E33483768A, 01/2014 1
Application SINAMICS DCM as a DC voltage source
Compact User Manual
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The
notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage
have no safety alert symbol. These notices shown below are graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of
injury to persons with a safety alert symbol may also include a warning relating to property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by
personnel qualified
for the specific task in accordance with
the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their
training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products
and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage,
installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any
problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.
Application SINAMICS DCM as a DC voltage source
2 A5E33483768A, 01/2014
Table of contents
1
Instructions ............................................................................................................................................................ 2
2
Introduction ............................................................................................................................................................ 2
3
SINAMICS DCM for charging and discharging batteries .......................................................................................... 3
4
SINAMICS DCM as a constant voltage source for DC motors as load ...................................................................... 4
5
SINAMICS DCM for resistive load, e.g. resistance heating ...................................................................................... 5
6
SINAMICS DCM for electrolytic applications............................................................................................................ 6
7
SINAMICS DCM for the DC link infeed of pulse inverters ......................................................................................... 7
8
References ............................................................................................................................................................ 8
1
Instructions
Note
This application document does not claim to contain all details and versions of units, or to take into account all conceivabl
e
operational cases and applications.
The standard applications do not represent specific customer
solutions, but are only intended to provide support in the
implementation of typical applications. The operator is responsible for the correct operation of the products described.
Should you require further information or encounter specific problems which
have not been handled in enough detail, please
contact your local Siemens office.
The contents of this application document are not part of an earlier or existing contract, agreement or legal relationship, n
or
do they change such contracts, agreements or
legal relationships. The contract of sale in each case outlines all the
obligations of the I DT Drive Technologies Division of Siemens AG. The warranty conditions specified in the contract
between the parties are the only warranty conditions accepted by th
e I DT Drive Technologies Division. Any statements
contained herein neither create new warranties nor modify the existing warranty.
WARNING
Observe safety notices in the associated operating instructions
The units listed here contain dangerous electric voltages, dangerous rotating machine parts (fans) and control rotating
mechanical parts (drives). Failure to follow the relevant operating instructions may result in death, serious injury or
extensive material damage.
Technical Support
You can also find help for technical issues through our Technical Support:
www.siemens.de/automation/support-request (German)
www.siemens.com/automation/support-request (English)
2
Introduction
The SINAMICS DCM is primarily used to control DC motors.
The universal suitability of the SINAMICS DCM as a DC drive also allows it to be used as an adjustable voltage source.
Since the integrated field supply is not required in this case, the SINAMICS DCM can be used with option L10 (without field
power unit).
Several examples of how to use the SINAMICS DCM as a voltage regulator are described below.
Perform commissioning according to Chapter 8.2 of the SINAMICS DCM DC Converter operating instructions.
Application SINAMICS DCM as a DC voltage source
A5E33483768A, 01/2014 3
3
SINAMICS DCM for charging and discharging batteries
Schematic circuit diagram
Matching transformer, 4% uk
S[VA] = UV[V] × 1.35 × 1.05 × IDC[A]
Line contactor (optional) acc. to Catalog IC10
Semiconductor fuse acc. to Catalog D23.1
SINAMICS DCM acc. to Catalog D23.1
2Q: Charge battery, UDC max[V]: UV[V] × 1.2
4Q: Charge and discharge the battery: UDC max = UV × 1.05
DC fuse, (only for 4Q) acc. to Catalog D23.1
Smoothing reactor for 5% ripple
Isolation amplifier, output 0 - 10 V
Analog input SINAMICS DCM, e.g. tachometer input terminal 103 / 104
Load / battery
Smoothing reactor
Since the internal resistance of the battery is very low, there is a high current ripple. Using a smoothing reactor in the DC
circuit is therefore recommended.
Configuration of the smoothing reactor for 5 % current ripple
Rated direct c
urrent
30 A
100
A
mH
300 A
1000
A
mH
Commissioning
Carry out the wiring according to the schematic circuit diagram.
Use an isolation amplifier with evaluation via an analog input (e.g. tachometer input) to record the battery voltage: Terminal
103 / 104.
Setting p50083 = 1, p50741 normalization of maximum voltage for battery. p2000 must be set to a value that deviates from
the factory setting. The speed controller now operates as a voltage regulator.
Optimization
Disconnect the battery and replace with a jumper (possible only if a smoothing reactor is used).
Perform current controller optimization p50051 = 25.
Connect the battery and optimize the voltage regulator manually, refer to FAQ fault diagnosis (Internet). Set current limit to
maximum charging/discharging current.
Application SINAMICS DCM as a DC voltage source
4 A5E33483768A, 01/2014
4
SINAMICS DCM as a constant voltage source for DC motors
as load
Schematic circuit diagram
DCM SINAMICS DCM acc. to Catalog D23.1
Maximum output voltage:
2Q: UDC = UV × 1.2
4Q: UDC = UV × 1.05
F1
DC fuse acc. to Catalog D23.1; only for 4Q
RV Starter resistor for the DC motors to prevent impermissibly high motor current during startup of the motors, if
necessary, several resistors in series bypassed depending on the speed of the motors
S1
To activate and deactivate the motor groups
S2
Closed after startup of the motors to bypass the RV resistor
GM
DC motors, 4 motors in 2 groups in this example
Commissioning
Adjustment is carried out to match the output voltage of the SINAMICS DCM. The speed controller operates as a voltage
regulator.
Since activation and deactivation of the motor groups changes the controlled system, data set switching is used for different
configurations of the controller settings. The SINAMICS DCM has 4 DDS (Drive Data Sets) for this purpose. Depending on
the number of motors, a different DDS is selected to perform optimization of the current controller. During operation, the
corresponding data set is then selected depending on the particular configuration.
Selection of the actual voltage source: p50083 = 4, p50609 = 52292 (connector actual voltage).
Select DDS and perform current controller optimization p50051 = 25.
The voltage regulator is optimized manually, refer to FAQ fault diagnosis (Internet).
Application SINAMICS DCM as a DC voltage source
A5E33483768A, 01/2014 5
5
SINAMICS DCM for resistive load, e.g. resistance heating
Schematic circuit diagram
DCM SINAMICS DCM, 2Q device. acc. to Catalog D23.1
UDC max[V] = UV[V] × 1.2
R Load impedance
Use smoothing reactor as necessary
New connectors as of Firmware V1.4
r52126: rms value direct current
r52127: rms value direct voltage
r52128: Active power
Commissioning
The SINAMICS DCM can be operated with voltage or current control.
Selection of the actual voltage source: p50083 = 4, p50609 = 52292 (connector actual voltage)
The control parameters can be left at their factory settings.
Application SINAMICS DCM as a DC voltage source
6 A5E33483768A, 01/2014
6
SINAMICS DCM for electrolytic applications
Schematic circuit diagram
T Isolating; S[VA] = UVV[V] × 1.35 × 1.05 × IDC[A]; uk: 4%
Notice: To prevent impermissible balance currents, a separate isolating transformer is required for each
SINAMICS DCM
F
Semiconductor fuse acc. to Catalog D23.1
DCM SINAMICS DCM acc. to Catalog D23.1
2Q device, UDC max[V] = Uv[V] × 1.2
LV
Smoothing reactor recommended to reduce current ripple
B
Load; electrolytic bath
Rated direct current
Smoothing reactor for 5 % current ripple
30 A
40 mH
100 A
10 mH
300 A
4 mH
1000 A
1.2 mH
Commissioning
The SINAMICS DCM can be operated with voltage or current control.
Selection of the actual voltage source: p50083 = 4, p50609 = 52292 (connector actual voltage).
The control parameters can be left at their factory settings or optimized manually if required.
Application SINAMICS DCM as a DC voltage source
A5E33483768A, 01/2014 7
7
SINAMICS DCM for the DC link infeed of pulse inverters
Note
The SINAMICS DCM cannot be used as a direct replacement for the MASTERDRIVES I/R units. The SINAMICS DCM is not
suitable for highly dynamic applications. Use the SINAMICS Active Line Module (ALM) for dynamic applications.
Schematic circuit diagram
DCM SINAMICS DCM acc. to Catalog D23.1
2Q: UDC max[V] = UV[V] × 1.2
4Q: UDC max = UV × 1.05
F1
Semiconductor fuse acc. to Catalog D23.1; required for 4Q only
LV
A low smoothing inductance is recommended
RB
Set base load resistor to 0.5 A
C
Load: DC link capacitor of the pulse inverter
Rated direct current
Smoothing reactor
30 A
5 mH
100 A
1.5 mH
300 A
0.5 mH
1000 A
0.15 mH
3000 A
0.05 mH
Commissioning
Selection of the actual voltage source: p50083 = 4, p50609 = 52292 (connector actual voltage).
Short circuit the DC link capacitance and perform optimization for the current controller p5005 = 25
(permissible only if a smoothing reactor is used)
Set p50153 = 2
Further settings
p50159 = 0.01
p50601[5] = 52401
p50401 = 0.02
Optimize the voltage regulator manually, refer to FAQ fault diagnosis (Internet).
Note
The normaliza
tion of the actual voltage r52292 is 100% = p50078[0] × 1.35.
Normalization of the actual voltage for the control must be carried out in the setpoint channel.
p50433[C]: Set to the connector number for the setpoint.
p50320[D]
= xxx normalization parameter
For U
DC max = UV × 1.05: xxx = 1.05 / 1.35 = 78%
For U
DC max = UV × 1.2: xxx = 1.2 / 1.35 = 89%
Application SINAMICS DCM as a DC voltage source
8 A5E33483768A, 01/2014
8
References
Catalog D23.1 for SINAMICS DCM and its accessories
(http://www.automation.siemens.com/mcms/infocenter/content/en/Pages/order_form.aspx?nodeKey=key_516865&infotype=
catalogs&linkit=null)
FAQ fault diagnosis for configuration and control optimization
(http://support.automation.siemens.com/WW/view/en/40863847)
Catalog IC10 for contactors (http://www.automation.siemens.com/mcms/industrial-
controls/de/downloads/seiten/ic10_2013.aspx)
Trademarks
All names identified by ® are registered trademarks of
Siemens AG
. The remaining trademarks in this publication may be trademarks whose
use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have re
viewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot
be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regular
ly and any
necessary corrections are included in subsequent editions.
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
Application SINAMICS DCM as a DC voltage source
A5E33483768A, 01/2014
Siemens AG
Industry Sector
P.O. Box 48 48
90026 NUREMBERG
GERMANY
Subject to change
A5E33483768A
© Siemens AG 2014
DC Converters
SINAMICS DCM
www.siemens.com/automation