Specifications are subject to change without notice CPT-DINBDS190606 1
•Class 2 (active energy)
•Class 3 (reactive energy)
•Accuracy ±0.5 F.S. (current/voltage)
•Compact Power transducer
•Instantaneous variables data format: 4 digit
•Energies data format: 8+1 digit
•System variables and phase measurements: W, Wdmd,
Wdmd max,var, V A, VAdmd,PF, V, A, An, Admd, Amax, Admd max,Hz
•Energy measurements: kWh and kvarh
•Hour counter (5+2 DGT)
•TRMS meas. of distorted sine waves (voltages/currents)
•Power supply: 90 to 260VAC/DC and 18 to 60VAC/DC
•Protection degree (front): IP20
•Dimensions: 45x83.5x98.5mm
•RS422/485 serial port
Product Description
3-phase compact power
transducer. Particularly rec-
ommended for the measure-
ments of the main electrical
variables.
Housing for DIN-rail mount-
ing, protection degree IP20
as standard, and RS485 or
RS232 serial port.
Parameters programmable
by means of CptBSoft.
Energy Management
Compact Power Transducer
Type CPT-DIN “Basic version”
Model
Range code
System
Power supply
Outputs
Option
How to order
CPT-DIN AV5 3 H S1 BX
Type Selection
Power supply
L: 18 to 60VAC/DC
H: 90 to 260VAC/DC
(*) Pay attention: the 3-phase
measurement is carried out as
one current and one phase to
neutral voltage measurement.
Range codes
AV5: 400/(690)VL-L/5(6)AAC
VL-N: 185 V to 460 V
VL-L: 320 V to 800 V
AV6: 120/(208)VL-L/5(6)AAC
VL-N: 45 V to 145 V
VL-L: 78 V to 250 V
Phase current: 0.03A to 6A
Neutral current: 0.09 to 6A
Outputs
S1:
RS485 port
S2:
RS232 port
System
3 : 1, 2 or 3-phase,
unbalanced and
balanced load,
with or without
neutral
1 : 1-3-phase,
balanced load (*)
Rated inputs
C u r r e n t 3 (current transformers)
Voltage 4
Accuracy
(R S48 5/R S 232 ) with CT=1 and VT=1 AV5:
(@25°C ±5°C, R.H. ≤60%) 1150W-VA-var, FS:230VLN,
400VLL; AV6: 285W-V A-var,
FS: 57VLN, 100VLL
Current 0.25 to 6A: ±(0.5% FS +1DGT)
0.03A to 0.25A: ±(0.5% FS +7DGT)
Neutral current 0.25 to 6A: ±(1.5% FS +1DGT)
0.09A to 0.25A: ±(1.5% FS+7DGT)
Phase-phase voltage
±(1.5%
FS + 1DGT)
Phase-neutral voltage ±(0.5% FS +0.1DGT)
Active and Apparent power,0.25 to 6A: ±(1%FS +1DGT);
0.03A to 0.25A: ±(1%FS+5DGT)
Reactive power 0.25 to 6A: ±(2% FS +1DGT);
0.03A to 0.25A: ±(2% FS +5DGT)
Active energy Class 2 (I start up: 30mA)
Reactive energy Class 3 (I start up: 30mA)
Frequency ±0.1Hz (48 to 62Hz)
Additional errors
Humidity ≤0.3% FS, 60% to 90% RH
Temperaturedrift ≤200ppm/°C
Sampling rate 1400 samples/s @ 50Hz
1700 samples/s @ 60Hz
Measurement r efr esh time 700ms
Measurement format
Instantaneous variables 4 DGT (Max indication: 9999)
Ener gies 9 DGT (Max indication:
999 999 99.9)
Hour counter 7DGT (Max. indication:
9999 9.99)
Input specifications
•RS232 serial port on request
•Alarms (only from serial communication port) VLN,An
Options
BX:
Basic features
How to order
CptBSoft: software to program the working parameters of
the transducer and to read the energy and the instanta-
neous variables. The kit includes the communication cable.
CptBSoft-kit