Specifications are subject to change without notice CPT-DINBDS190606 1
Class 2 (active energy)
Class 3 (reactive energy)
Accuracy ±0.5 F.S. (current/voltage)
Compact Power transducer
Instantaneous variables data format: 4 digit
Energies data format: 8+1 digit
System variables and phase measurements: W, Wdmd,
Wdmd max,var, V A, VAdmd,PF, V, A, An, Admd, Amax, Admd max,Hz
Energy measurements: kWh and kvarh
Hour counter (5+2 DGT)
TRMS meas. of distorted sine waves (voltages/currents)
Power supply: 90 to 260VAC/DC and 18 to 60VAC/DC
Protection degree (front): IP20
Dimensions: 45x83.5x98.5mm
RS422/485 serial port
Product Description
3-phase compact power
transducer. Particularly rec-
ommended for the measure-
ments of the main electrical
variables.
Housing for DIN-rail mount-
ing, protection degree IP20
as standard, and RS485 or
RS232 serial port.
Parameters programmable
by means of CptBSoft.
Energy Management
Compact Power Transducer
Type CPT-DIN “Basic version”
Model
Range code
System
Power supply
Outputs
Option
How to order
CPT-DIN AV5 3 H S1 BX
Type Selection
Power supply
L: 18 to 60VAC/DC
H: 90 to 260VAC/DC
(*) Pay attention: the 3-phase
measurement is carried out as
one current and one phase to
neutral voltage measurement.
Range codes
AV5: 400/(690)VL-L/5(6)AAC
VL-N: 185 V to 460 V
VL-L: 320 V to 800 V
AV6: 120/(208)VL-L/5(6)AAC
VL-N: 45 V to 145 V
VL-L: 78 V to 250 V
Phase current: 0.03A to 6A
Neutral current: 0.09 to 6A
Outputs
S1:
RS485 port
S2:
RS232 port
System
3 : 1, 2 or 3-phase,
unbalanced and
balanced load,
with or without
neutral
1 : 1-3-phase,
balanced load (*)
Rated inputs
C u r r e n t 3 (current transformers)
Voltage 4
Accuracy
(R S48 5/R S 232 ) with CT=1 and VT=1 AV5:
(@25°C ±5°C, R.H. 60%) 1150W-VA-var, FS:230VLN,
400VLL; AV6: 285W-V A-var,
FS: 57VLN, 100VLL
Current 0.25 to 6A: ±(0.5% FS +1DGT)
0.03A to 0.25A: ±(0.5% FS +7DGT)
Neutral current 0.25 to 6A: ±(1.5% FS +1DGT)
0.09A to 0.25A: ±(1.5% FS+7DGT)
Phase-phase voltage
±(1.5%
FS + 1DGT)
Phase-neutral voltage ±(0.5% FS +0.1DGT)
Active and Apparent power,0.25 to 6A: ±(1%FS +1DGT);
0.03A to 0.25A: ±(1%FS+5DGT)
Reactive power 0.25 to 6A: ±(2% FS +1DGT);
0.03A to 0.25A: ±(2% FS +5DGT)
Active energy Class 2 (I start up: 30mA)
Reactive energy Class 3 (I start up: 30mA)
Frequency ±0.1Hz (48 to 62Hz)
Additional errors
Humidity 0.3% FS, 60% to 90% RH
Temperaturedrift 200ppm/°C
Sampling rate 1400 samples/s @ 50Hz
1700 samples/s @ 60Hz
Measurement r efr esh time 700ms
Measurement format
Instantaneous variables 4 DGT (Max indication: 9999)
Ener gies 9 DGT (Max indication:
999 999 99.9)
Hour counter 7DGT (Max. indication:
9999 9.99)
Input specifications
RS232 serial port on request
Alarms (only from serial communication port) VLN,An
Options
BX:
Basic features
How to order
CptBSoft: software to program the working parameters of
the transducer and to read the energy and the instanta-
neous variables. The kit includes the communication cable.
CptBSoft-kit
2Specifications aresubject to change without notice CPT-DINBDS190606
CPT-DIN
no parity, 1 stop bit
Baud-rate 9600 bit/s
Insulation By means of optocuplers,
2kVRMS output to
measuring input.
4kVRMS output to power supply
RS232 Halfduplex communication
Type Point to point connection
Connections 3-wire, max. distance 15m
Address 1 to 255 selectable via software
Protocol MODBUS/JBUS (R TU)
Baud-rate 9600bits/s
other characteristics like
R422/RS485 port
RS422/RS485 Halfduplex communication
Type Multidrop
bidirectional (static and
dynamic variables)
Connections 2 or 4 wires, max. distance
1200m, termination directly
on the instrument
Addresses 1 to 255 selectable via software
Protocol MODBUS/JBUS (R TU)
Data (bidirectional)
Dynamic (reading only) System, phase variables and
energies
Static (writing only) All configuration parameters
Data format 1start bit, 8 data bit,
Serial Port Specifications
Filter action Measurements, alarms,
serial out. (fundamental var: V,
A, Wand their derived ones).
Alarms Programmable, for the VLNand
An (neutral current).
Note: the alarm is only a
status transmitted via
communication port.
Reset Independent
alarm (VLN,An)
max: A dmd, W dmd
all ener gies (Wh, varh)
hour counter
System selection 3-ph. with or without N, unbal.
3-phase balanced “1CT + 1VT”
3-phase ARON, unbalanced
2-phase
Single phase
Transformer ratio
CT 1 to 999
VT/PT 1.0 to 99,9
Filter
Operating range 0 to 99.9% of the input
electrical scale
Filtering coefficient 1 to 16
Softwarefunctions
Input specifications (cont.)
Measurements Curr ent, voltage, power,
power factor, frequency,
ener gy, hour counter
Type TRMS measurement
of distorted waves.
Coupling type Direct
Crest factor < 3, max 10A peak
Input impedance
400/690VL-L (AV5) 1 M±5%
120/208VL-L (AV6) 453 K±5%
Current 0.02
Frequency 48 t o 62 Hz
Overload protection (max values)
Continuos voltage/current AV5: 460VLN,800VLL/6A
AV6: 145VLN,250VLL/6A
For 500ms: voltge/current AV5: 800VLN,1380VLL/36A
AV6: 240VLN,416VLL/36A
Connections RJ12 (3-wire) for special cable
Baud-rate 4800 bits/s
Data format 1 start bit, 8 data bit,
no parity, 1 stop bit
Insulation By means of optocuplers,
2kVRMS output to
measuring input.
4kVRMS output to power supply
RS232 Configuration Bus
CptBSoft: parameter programming and reading data software
W orking mode Two different working
modes can be selected:
- management of a local
RS485 network;
- management of
communication from a single
instrument to PC (RS232);
Data access By means of RS232 serial
port, RS485 serial port or
RS232 configuration port.
CptBSoft Multi language softwareto
program the working
parameters of the transducer
and to read the ener gies and
the instantaneous variables.
The program runs under
Windows 95/98/98SE/2000/
NT/XP.
Specifications are subject to change without notice CPT-DINBDS190606 3
CPT-DIN
General Specifications
Front LED’s
Power on Green
Diagnostics Green (TX data)
Red (RX data)
Operating to +50°C (32° to 122°F)
temperature (RH < 90% non condensing)
Storage -10° to +60°C (14° to 140°F)
temperature (RH < 90% non condensing)
Installation category Cat. III (IEC 60664, EN60664)
Insulation (for 1 minute) 4kVACRMS
between mesuring
inputs and power supply.
2kVAC/DC between
mesuring inputs and
RS485/RS232/programming
port (RJ12)
4kVACRMS between
power supply and
RS485/RS232/programming
port.
Dielectric strength 4kVACRMS (for 1 min)
EMC
Emissions EN61000-6-3, EN60688
residential envir onment,
commerce and light industry
Immunity EN61000-6-2
industrial environment.
Pulse voltage (1.2/50µs)
EN61000-4-5
Safety standards IEC60664, EN60664
Measurement standards IEC60688, EN60688
Approvals CE, cURus
Connections 5(6) A Screw-type
Max cable cross sect. area 2.5 mm2
Housing
Dimensions (WxHxD) 45 x 83.5 x 98.5 mm
Material ABS
self-extinguishing: UL 94 V-0
Mounting DIN-rail
Protection degree IP20
Weight Approx. 200 g (pack. incl.)
Variables that can be retrasmitted 3-phase system 4-wire connection
Variables Notes
VL1 V L2 V L3
VL12 V L23 V L31
AL1 A L2 A L3
AL1 dmd AL2 dmd AL3 dmd dmd = demand (integration time
selectable from 1 to 30 minutes)
An An alarm An alarm: neutral current alarm
WL1 WL2 WL3
PF L1 PF L2 PF L3
var L1 var L2 var L3
VA L1 VA L2 VA L3
VA system W system var system
VAdmd Wdmd Hz dmd = demand (integration time
(system) (system) selectable from 1 to 30 minutes)
Wdmd MAX Maximum sys power demand
Wh
varh
VLL system VLN alarm PF system VLN alarm: alarm status if VLN is not
within the two set limits.
AMAX
max. current among the three phases
Admd max max. dmd current among the thr ee phases
h working hour counter
Measurements available on the communication port
Auxiliary power supply 90 to 260VAC/DC
16to 60V AC/DC Power consumption AC: 4.5 V A
DC: 4W
Power Supply Specifications
Used calculation formulas
4Specifications aresubject to change without notice CPT-DINBDS190606
CPT-DIN
Waveform of the signals that can be measured
Figure A
Sine wave, undistorted
Fundamental content 100%
Harmonic content 0%
Arms =1.1107 | A |
Figure B
Sine wave, indented
Fundamental content 10...100%
Harmonic content 0...90%
Frequency spectrum: 3r d to 16th harmonic
Additional error: <1% FS
Figure C
Sine wave, distorted
Fundamental content 70...90%
Harmonic content 10...30%
Frequency spectrum: 3r d to 16th harmonic
Additional error: <0.5% FS
Accuracy
Wh,accuracy (RDG) depending on the current
Error
6A (Imax)
6A (Imax)
5A (Ib)
5A (Ib)
0.5A
(0.1Ib)
1A
(0.2Ib)
0.25A
(0.05Ib)
0.5A
(0.1Ib)
+2%
0%
+4%
-2%
Accuracy limits (Active energy)
5(6A) Start-up current: 30mA
-4%
varh,accuracy (RDG) depending on the current
Error
+3%
0%
+6%
-3%
Accuracy limits (Reactive energy)
5(6A) Start-up current: 30mA
-6%
PF=1
PF=L0.5
or C0.8
6A (Imax)
6A (Imax)
5A (Ib)
5A (Ib)
0.25A
(0.05Ib)
0.5A
(0.1Ib)
0.1A
(0.02Ib)
0.25A
(0.05Ib)
sinϕ=1
sinϕ=0.5
Phase variables
Instantaneous effective voltage
Instantaneous active power
Instantaneous power factor
Instantaneous effective current
Instantaneous apparent power
Instantaneous reactive power
System variables
Equivalent three-phase voltage
Three-phase reactive power
Neutral current
Three-phase active power
Three-phase apparent power
Three-phase power factor
(TPF)
Energy metering
Where:
i = considered phase (L1, L2 or L3)
P=active power
Q = reactive power
t1, t2=starting and ending time points
of consumption recording
n = time unit
t = time interval between two successive
power consumptions
n1,n2=starting and ending discrete time
points of consumption recording
An = AL1+AL2+AL3
Specifications are subject to change without notice CPT-DINBDS190606 5
CPT-DIN
L1
L2
N
L3
L
N-
+
F
A1 A2
711
810
23 25 27
L1 L2 L3
N
L1L3
L2
L1
24 L2
26 L3
28
Wiring diagrams “system type selection: 3”
L1
L2
N
L
N-
+
F
A1 A2
7
810
23 25
L1 L2
N
L1
L2
L1
24L2
26
L1
N
L
N-
+
F
A1 A2
7
8
23
L1
N
L1
L1
24
Direct connection
Direct connection
2-ph, 3-wire Fig. 3
L1
L2
L3
L
N-
+
F
A1 A2
711
10
23 25 27
L1 L2 L3
L1 L3
L2
L1
24 L2
26 L3
28
ARON and 2VT/PT connection
2CT connection
3-ph, 4 wire, unbalanced load Fig. 4
1-ph, 2-wire Fig. 1
3-ph, 3-wire, unbalanced load Fig. 6
Power Supply
Power Supply
Power Supply
Power Supply
F= 630 mA T (18 to 60VAC/DC)
125 mA T (90 to 260V AC/DC)
L1
N
L
N-
+
F
A1 A2
7
8
23
L1
N
L1
L1
24
1CT connection
1-ph, 2-wire Fig. 2
Power Supply
L1
L2
L3
L
N-
+
F
A1 A2
711
810
N
L1 L3
L2
23 25 27
L1 L2 L3
L1
24 L2
26 L3
28
ARON connection
3-ph, 3-wire, unbalanced load Fig. 5
Power Supply
6Specifications aresubject to change without notice CPT-DINBDS190606
CPT-DIN
Wiring diagrams “system type selection: 3” (cont.)
L1
L2
N
L3
L
N-
+
F
A1 A2
7
8
N
L1
23
L1
L1
24
3-ph, 4-wire, balanced load Fig. 12
1CT and 1VT/PT connection
Power Supply
F= 630 mA T (18 to 60V AC/DC)
125 mA T (90 to 260VAC/DC)
L1
L2
L3
L
N-
+
F
A1 A2
711
10
23
L1
L1 L3
L2
L1
24
3-ph, 3-wire, balanced load Fig. 11
1CT connection
Power Supply
3CT and 3VT/PT connection
L1
L2
N
L3
L
N-
+
F
A1A2
711
10
2325 27
L1 L2 L3
L1L3
L2
L1
24 L2
26 L3
28
8
N
3-ph, 4-wire, unbalanced load Fig. 8
Power Supply
L1
L2
N
L3
L
N-
+
F
A1A2
711
810
2325 27
L1 L2 L3
N
L1L3
L2
L1
24 L2
26 L3
28
3-ph, 4-wire, unbalanced load Fig. 7
3CT connection
Power Supply
3CT connection
L1
L2
L3
L
N-
+
F
A1A2
711
10
2325 27
L1 L2 L3
L1L3
L2
L1
24 L2
26 L3
28
3-ph, 3-wire, unbalanced load Fig. 9
Power Supply
3CT and 2VT/PT connection
L1
L2
L3
L
N-
+
F
A1 A2
23 25 27
L1 L2 L3
L1
24 L2
26 L3
28
711
10
L1 L3
L2
3-ph, 3-wire, unbalanced load Fig. 10
Power Supply
Specifications are subject to change without notice CPT-DINBDS190606 7
CPT-DIN
Wiring diagrams “system type selection: 1”
F= 630 mA T (18 to 60V AC/DC)
125 mA T (90 to 260VAC/DC)
1CT connection
L1
N
L
N-
+
F
A1A2
L1
L1
24
7N
L1
1-ph, 2-wire Fig. 14
Power Supply
L1
N
L
N-
+
F
A1A2
7
L1
N
L1
L1
24
1-ph, 2-wire Fig. 13
Direct connection
Power Supply
1CT connection
L1
L2
L3
L
N-
+
F
A1A2
7
L1 N
L1
L1
24
N
3-ph, 4-wire, balanced load Fig. 15
Power Supply
1CT and 1VT/PT connection
L1
L2
N
L3
L
N-
+
F
A1 A2
7N
L1
L1
L1
24
3-ph, 4-wire, balanced load Fig. 16
Power Supply
8Specifications aresubject to change without notice CPT-DINBDS190606
CPT-DIN
246
135
TX- RX- T
GND
RX+TX+
246
135
TX- RX- T
GND
RX+TX+
246
135
TX- RX- T
GND
RX+TX+
SIU-PC
RS485RS232
GND
RX+
TX+
TX-
RX-
1
5
69
5
3
2
GND
TXRX
246
135
RS485 Serial port connection
RS232 Serial port connection
4-wire connection of RS485 serial port, the terminalization must be carried out only on the last instrument of the network
Last instrument 1...n Instrument
246
135
TX- RX- T
GND
RX+TX+
246
135
TX- RX- T
GND
RX+TX+
246
135
TX- RX- T
GND
RX+TX+
SIU-PC
RS485RS232
GND
RX +
TX+
TX-
RX -
2-wire connection of RS485 serial port, the terminalization must be carried out only on the last instrument of the network
Last instrument 1...n Instrument
Easy programming
RJ12 communication port
for parameters program-
ming. The configuaration of
the transducer can be easi-
ly performed by means of
CptBSoft.
CptBSoft-kit includes also
aconnection cable (RJ12 6
pole + RS232 9 pole
female).
Specifications are subject to change without notice CPT-DINBDS190606 9
CPT-DIN
1
2
3
4
5
623
24
(L1) 25
26
(L2) 27
28
(L3)
A1 A2
8
(L1)
79
(N) (L2) (L3)
CPT-DIN
CompactPowerTransducer
Diagnostics
PowerON
11
10 12
I
V
Dimensions and Panel Cut-out
45mm 98.5mm
67.5mm
83.5mm
Front Panel Description
Outputs connections
A1A2
~+ - ~
GND
RX+TX+
TX- RX- T
1
2
3
4
5
623
24
(L1) 25
26
(L2) 27
28
(L3)
A1 A2
8
(L1)
79
(N) (L2) (L3)
CPT-DIN
CompactPowerTransducer
Diagnostics
PowerON
11
10 12
I
V
GND
TX
RX
1. Front panel
2. Power ON LED
3. Diagnostics LED
4. Configuration bus (RJ12 connector)
5. Connections screw terminals
1
2
3
4
5
623
24
(L1) 25
26
(L2) 27
28
(L3)
A1 A2
8
(L1)
79
(N) (L2) (L3)
CPT-DIN
CompactPowerTransducer
Diagnostics
PowerON
11
10 12
I
V
3
1
2
4
5
RS485 RS232