UL Class CF branch circuit time-delay CUBEFuse
2011/65/EU
Catalog symbols
• TCF_ (indicating fuse, 6-400 A)
• TCF_RN (non-indicating fuse, 1-400 A)
Description
The Bussmann™ series Low-Peak™ CUBEFuse™
is a UL® Class CF current-limiting, dual-element,
time-delay branch circuit fuse with Class J
electrical performance. Available in indicating and
non-indicating versions, this finger-safe fuse has
a very compact, space-saving size and is easily
applied using the CUBEFuse holder (TCFH_N), UL
98 Compact Circuit Protector switch (CCP2-_CF)
or Compact Circuit Protector Base (CCP2B up
to 100 A) used in the Quik-Spec™ Coordination
Panelboard).
Ratings
• Volts
• 600 Vac
• 300 Vdc
• Amps
• 6-400 A (indicating)
• 1-400 A (non-indicating)
• Interrupting rating
• 300 kA RMS Sym. (Up to 100 A UL)
• 200 kA RMS Sym. (110 to 400 A UL)
• 200 kA RMS Sym. (Up to 100 A CSA)
• 100 kA DC (Up to 400 A UL and up to 100 A
CSA)
Electrical characteristics
• 10 seconds minimum operating time at 500%
rated current
Agency information
• UL Listed Class CF fuse: Guide JDDZ, File
E4273 (up to 400 A)
• CSA® Certified fuse: Class 1422-02,
File 053787_C_000 (up to 100 A)
• CE (100 A and below)
• RoHS compliant
Watts loss at rated current
Fuse amps Watts
30 3.99
60 6.23
100 9.51
200 18.6
225 1 7. 6
400 35.2
Operating and storage temperature range
• -40 to 80°C (-40°F to 176°F)
Catalog numbers (amps)
Indicating CUBEFuse
TCF6 TCF35 TCF90 TCF225
TCF10 TCF40 TCF100 TCF250
TCF15 TCF45 TCF110 TCF300
TCF17-1/2 TCF50 TCF125 TCF350
TCF20 TCF60 TCF150 TCF400
TCF25 TCF70 TCF175
TCF30 TCF80 TCF200
Non-Indicating CUBEFuse
TCF1RN TCF25RN TCF70RN TCF175RN
TCF3RN TCF30RN TCF80RN TCF200RN
TCF6RN TCF35RN TCF90RN TCF225RN
TCF10RN TCF40RN TCF100RN TCF250RN
TCF15RN TCF45RN TCF110RN TCF300RN
TCF17-1/2RN TCF50RN TCF125RN TCF350RN
TCF20RN TCF60RN TCF150RN TCF400RN
Technical Data 9000 Effective March 2019
Supersedes January 2019
BUSSMANN
SERIES
2
Technical Data 9000
Effective March 2019
UL Class CF branch circuit time-delay CUBEFuse
Eaton.com/bussmannseries
Features
• Smallest installed footprint of any UL Class CC, J, or R fuse
solution
• Easy application using CUBEFuse holders (TCFH_N), UL 98
Compact Circuit Protector (CCP2) switches and Compact Circuit
Protector Base (CCP2B up to 100 A). See data sheet 9007 for
details on the CUBEFuse holder, 10801 for details on the CCP2-_
CF switch and 1161 for the CCP2B.
• Holders and switches have an amp rating rejection feature to help
prevent overfusing; 30, 60 and 100 A switches and holders will
hold any CUBEFuse up to its rating, 200 and 400 A switches and
200, 225 and 400 A holders will hold any CUBEFuse 110 A and
above up to its rating
• UL Class CF with Class J time-delay electrical performance
• Available in indicating and non-indicating versions
• The indicating version features local
easy
ID™ open fuse
technology for faster troubleshooting and reduced downtime
• Faster response to damaging faults helps reduce destructive
thermal and magnetic forces
• True dual-element fuse construction with a minimum 10 seconds
time-delay at 500% of rating
• Long time-delay minimizes nuisance openings caused by
temporary overloads and transient surges
• Up to 300 kA interrupting rating safely interrupts virtually any fault
• Robust cycling and inrush current withstand
• Low let-through currents under fault conditions
• Provides Type 2 “No Damage” protection for IEC motor starters
when properly sized
• Easy selective coordination with any other Bussmann series
Low-Peak Class CC, J, L or RK1 fuse with simple 2:1 amp ratio
between upstream and downstream fuses
* Finger-safe status depends on final, installed application, and will require using
accessory shrouds for 110 to 400 A ratings.
Up to 30 A 35 to 60 A 70 to 100 A 110-225 A 250-400 A
Carton quantity and weight
Amp range Carton qty. Weight per carton lb (kg)
Up to 30 12 1.39 (0.63)
35-60 12 1.42 (0.64)
70-100 6 1.74 (0.79)
110 to 225 10.71 (0.32)
250 to 400 11.23 (0.56)
B
ED
C
A
C
A
E
B
D
Fuse
amps A B C D E
1-15
1.88 (48) 0.75 (19) 1.0 (25)
0.23 (6)
0.67 (17)
17-1/2 0.27 (7)
20
25-30 0.31 (8)
35-40
2.13 (54)
1.0 (25)
1.13 (29)
0.36 (9)
45-50 0.44 (11)
60
70
3.01 (76) 1.26 (32) 0.49 (12) 0.64 (16)80-90
100 0.57 (14)
110
3.62 (92) 2.9 (74) 1.34 (34) 1.02 (26)
0.51 (13)
125 0.51 (13)
150 0.51 (13)
175 0.57 (14.5)
200 0.57 (14.5)
225 0.63 (16)
250
4.25 (108) 3.46 (88) 1.69 (43) 1.47 (36)
0.73 (18.5)
300 0.79 (20)
350 0.86 (21.5)
400 0.86 (21.5)
Dimensions — in (mm)
Up to 100 A
110 to 400 A
3
Technical Data 9000
Effective March 2019
UL Class CF branch circuit time-delay CUBEFuse
Eaton.com/bussmannseries
0.01
0.1
1
10
100
1000
TIME IN SECONDS
CURRENT IN AMPS
110A
200A
250A
225A
400A
100
1,000
10,000
100
1,000,
10,000
100,000
B
A
250A
400A
225A
200A
110A
100
1,000
100,000
INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS
PROSPECTIVE SHORT CIRCUIT CURRENT
SYMMETRICAL RMS AMPS
10,000
110 to 400 A time-current characteristics — average melt
110 to 400 A current let-through curves
Up to 100 A time-current characteristics — average melt
Up to 100 A current let-through curves
4
Technical Data 9000
Effective March 2019
UL Class CF branch circuit time-delay CUBEFuse
Eaton.com/bussmannseries
Voltage
Motor size
(Hp)
Motor FLA
(amps)
Min
(amps)
NEC
code max
(amps)
Heavy
start*
(amps)
115 Vac,
1-phase
0.167 4.4 10 10 10
0.25 5.8 10 15 15
0.333 7. 2 15 15 15
0.5 9.8 15 20 20
0.75 13.8 25 25 30
116 25 30 35
1. 5 20 30 35 45
2 24 40 45 50
3 34 50 60 70
5** 56 90 10 0 125
7. 5 80 125 150 175
10 100 150 175 225
230 Vac,
1-phase
0.167 2.2 6 6 6
0.25 2.9 6 6 6
0.333 3.6 6 10 10
0.5 4.9 10 10 10
0.75 6.9 15 15 15
1 8 15 15 1 7. 5
1. 5 10 15 20 20
212 20 25 25
317 25 30 35
5 28 45 50 60
7. 5 40 60 70 90
10** 50 80 90 110
200 Vac,
3-phase
0.5 2.5 6 6 6
0.75 3.7 6 10 10
1 4.8 10 10 10
1. 5 6.9 15 15 15
27. 8 15 15 1 7. 5
311 1 7. 5 20 20
51 7. 5 30 35 35
7. 5 25.3 40 45 50
20** 62.1 100 110 125
25 78.2 125 150 175
30 92 150 175 200
40 120 200 225 250
50 150 225 300 300
60 177 300 350 350
Note: Use NEC code max column for low to moderate reverse/jog/
plug applications.
* Heavy Start permitted only if NEC code max does not allow motor start-up.
** If equipment terminations are rated for 60°C conductors only, the 60°C
conductor ampacities must be utilized and therefore larger conductor sizes or
conduit sizes may be required.
Voltage
Motor size
(Hp)
Motor FLA
(amps)
Min
(amps)
NEC
code max
(amps)
Heavy
start*
(amps)
208 Vac,
3-phase
0.5 2.4 6 6 6
0.75 3.5 6 10 10
1 4.6 10 10 10
1. 5 6.6 10 15 15
27. 5 15 15 15
3 10.6 1 7. 5 20 20
5 16.7 25 30 35
7. 5 24.2 40 45 50
20** 59.4 90 110 125
25 74.8 125 150 150
30 88 150 175 175
40 114 175 200 250
50 143 225 300 300
60 169 300 300 350
230 Vac,
3-phase
0.5 2.2 6 6 6
0.75 3.2 6 6 6
1 4.2 10 10 10
1. 5 610 15 15
2 6.8 15 15 15
3 9.6 15 20 20
5 15.2 25 30 30
7. 5 22 35 40 45
20** 54 90 100 110
25 68 110 125 150
30 80 125 150 175
40 104 175 200 225
50 130 200 250 250
60 154 250 300 300
75 192 300 350 400
460 Vac,
3-phase
0.5 1. 1 3 3 3
0.75 1. 6 3 3 3
1 2.1 6 6 6
1. 5 3 6 6 6
2 3.4 6 6 6
3 4.8 10 10 10
57. 6 15 15 15
7. 5 11 1 7. 5 20 20
10 14 25 25 30
15 21 35 40 45
20 27 40 50 60
50** 65 100 125 125
60 77 125 150 150
75 96 150 175 200
100 124 200 225 250
125 156 250 300 350
150 180 300 350 400
Note: Use NEC code max column for low to moderate reverse/jog/
plug applications.
* Heavy Start permitted only if NEC code max does not allow motor start-up.
** If equipment terminations are rated for 60°C conductors only, the 60°C
conductor ampacities must be utilized and therefore larger conductor sizes or
conduit sizes may be required.
Motor sizing table (from NEC Tables 430.248 and 430.250)
Bussmann series TCF Low-Peak time-delay Class CF fuses
5
Technical Data 9000
Effective March 2019
UL Class CF branch circuit time-delay CUBEFuse
Eaton.com/bussmannseries
Motor sizing table (from NEC Tables 430.248 and 430.250)
Bussmann series TCF Low-Peak time-delay Class CF fuses
Voltage
Motor size
(Hp)
Motor FLA
(amps)
Min
(amps)
NEC
code max
(amps)
Heavy
start*
(amps)
575 Vac,
3-phase
0.5 0.9 3 3 3
0.75 1. 3 333
11. 7 333
1. 5 2.4 6 6 6
2 2.7 6 6 6
3 3.9 6 10 10
5 6.1 10 15 15
7. 5 915 20 20
10 11 1 7. 5 20 20
40** 41 70 80 80
50 52 80 100 110
60 62 100 110 125
75 77 125 150 150
100 99 150 175 200
125 125 200 225 250
150 144 225 300 300
200 192 300 350 400
Note: Use NEC code max column for low to moderate reverse/jog/
plug applications.
* Heavy Start permitted only if NEC code max does not allow motor start-up.
** If equipment terminations are rated for 60°C conductors only, the 60°C
conductor ampacities must be utilized and therefore larger conductor sizes or
conduit sizes may be required.
UL Class CF branch circuit time-delay CUBEFuseTechnical Data 9000
Effective March 2019
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document
are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help
the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue
or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this
bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Eaton, Bussmann, CUBEFuse, Low-Peak,
easyID and Quik-Spec are valuable trademarks
of Eaton in the US and other countries. You
are not permitted to use the Eaton trademarks
without prior written consent of Eaton.
CSA is a registered trademark of the Canadian
Standards Group
NEC is a registered trademark of the National
Fire Protection Association
UL is a registered trademark of the
Underwriters Laboratories, Inc.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2019 Eaton
All Rights Reserved
Printed in USA
Publication No. 9000 – BU-SB18086
March 2019
For Eatons Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Follow us on social media to get the
latest product and support information.
CUBEFuse (cat. no. TCFH_N) holders
The CUBEFuse is used in holders that can be dovetail together for
the smallest footprint possible of any Class J fuse solution (see data
sheet no. 9007 for details).
Finger-safe DIN-Rail or panel
mount holders up to 100 A.
• 30 A holder accepts any
CUBEFuse up to 30 A.
• 60 amp holder accepts any
CUBEFuse up to 60 A.
• 100 amp holder accepts any
CUBEFuse up to 100 A.
Panel mount holders from
200 to 400 A.
• 200 A holder accepts any
CUBEFuse from 110 to 200 A
• 225 A* holder accepts any
CUBEFuse from 110 to 225 A
• 400 A holder accepts any
CUBEFuse from 110 to 400 A
Finger-safe installation
achievable for three ganged
holders and lug kits with shroud
* 200 A and 225 A holders share the
same overall dimensions, but the
200 A holder will reject a 225 A fuse.
These 1-, 2- and 3-pole switches
are UL 98 horsepower rated
branch circuit disconnects.
Primarily used in the Quik-Spec
Coordination Panelboard, they’re
available in ratings up to 100 A.
The CCP2B has amp rejection
breaks that prevent installing
any CUBEFuse amp rating
greater than that of the switch.
These coincide with standard
conductor ampacities to help
prevent overfusing and are
available at 15, 20, 30, 40, 50,
60, 70, 90 and 100 amps for all
1-, 2- and 3-pole switches.
These DIN-Rail mounted 1-, 2-
and 3-pole switches are UL 98
horsepower rated disconnects
available with front or side
rotary operators. Each CCP2
will accept a fuse amp rating
equal to or less than its rating
(e.g., a 60 A CCP will accept
any CUBEFuse up to 60 A).
Accessories include multi-wire
lug kits with shrouds, auxiliary
contacts and PLC fuse monitor
(see data sheet no. 10801 for
details).
30, 60 and 100 A Compact Circuit Protector (cat. no.CCP2_CF)
switches
200 and 400 A Compact Circuit Protector (cat. no. CCP2-CF)
switches These panel mounted 1-, 2-
and 3-pole switches are UL 98
horsepower rated disconnects.
Each CCP2 will accept a fuse
amp rating equal to or less than
its rating (e.g., a 200 A CCP will
accept any CUBEFuse from 110
to 200 A). Complete installation
requires installing various
lugs to meet the application
requirement. Accessories
include side or front rotary
operators and auxiliary contacts
(see data sheet no. 10801 for
details).
Compact Circuit Protector Base (cat. no. CCP2B)