S8E1 S8E1
Specifications Table -- continued from previous page
Characteristics
Ambient temperature Operating See the derating curve in the
Engineering Data
section.
Ambient temperature Storage -- 20°Cto65
°C(--4
°F to 149°F)
Ambient humidity Operating 25% to 85%
Ambient humidity Storage 20% to 90%
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min. (between all inputs and outputs/GR terminal)
Insulation resistance 100 MΩmin. at 500 VDC (between all outputs and inputs/GR terminal)
Vibration resistance Malfunction: 10 to 55 Hz, 0.75-mm double amplitude (44.1 m/s2, approx. 4.5G) for
2 h each in X, Y, and Z directions
Shock resistance Malfunction: 294 m/s2(approx. 30G), 3 times each in ±X, ±Y, and ±Z directions
Output indicator Green LED
Electromagnetic interference Conforms to FCC class A standards and 1st group of VCCI
Approved standards UL 1012, CSA E.B.1402
Life expectancy 8yrs.min.(40
°C at the rated input with a 50% load)
Weight (covered-type) 200 g max. 240 g max. 320 g max. 440 g max.
Note: Ratings and characteristics are defined at the power supply output terminals.
DC inputs are not included in safety standard approvals.
n
neer
n
ata
Open-frame type
Load (%)
Ambient temperature (
C)
Covered-type
Load (%)
Ambient temperature (
C)
Horizontal Installation
Note: The derating curve depends on the mounting position
of the power supply. The left curve is obtained from a
model mounted in one of the standard positions.
Natural air-cooling
Forced-air cooling
Forced-air
cooling
Natural air-cooling
Mounting Position
Standard (Vertical) Installation
Models with a power rating of 10 or 15 W incorporate a Zener
diode clamp circuit. If the protection circuit is triggered, contact
your OMRON representative for repairs.
Models with a power rating of 25 or 50 W incorporate a shut-off
circuit. If the protection circuit is triggered, turn off the input power
and leave the power supply off for at least one minute before
turning it on again.
OVERVOLTAGE PROTECTION
(5-V OUTPUT MODELS ONLY)
DERATING CURVE