EMC filters
3-line filters
for converters and power electronics
Rated current 150 to 2500 A
Series/Type: B84143B*S020 … S024
Date: January 2006
EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the
information contained therein without EPCOS’ prior express consent is prohibited.
3-line filters B84143B*S020 … S024
for converters and power electronics
Power line filters for 3-phase systems
Rated voltages 530/310, 690/400, 760/440 V AC
Rated current 150 to 2500 A
Alternative version
Series B84143B*S080 and B84143B*S081
offers a low-cost solution.
Construction
3-line filter
Metal case
Features
Optimized leakage current
Easy to install
Very compact design
Optimized for operation under full load
Low weight
UL, cUL approval
Applications
B84143B*S024 for IT mains supply
Frequency converters for motor drives
Wind farms
Power supplies
Terminals
Busbars
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current, rated temperature,
climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 2
3-line filters B84143B*S020 … S024
for converters and power electronics
Typical circuit diagram
LINE LOAD
L1 L1’
L2 L2’
L3 L3’
SSB2130-I
Technical data and measuring conditions
Rated voltage VR Type S020:
Type S021:
Type S024:
530/310 V AC, 50/60 Hz
760/440 V AC, 50/60 Hz
690/400 V AC, 50/60 Hz (Filters for IT mains
supply. See also Chapter “General”, Section 7.4)
Rated current IR Referred to 40 °C ambient temperature
Test voltage Vtest Type S020:
2280 V DC, 2 s (line/line)
2690 V DC, 2 s (lines/case)
Type S024:
2980 V DC, 2 s (line/line)
2890 V DC, 2 s (lines/case)
Type S021:
3270 V DC, 2 s (line/line)
2890 V DC, 2 s (lines/case)
Overload capability (thermal) 1.5 · IR for 3 min per hour or
2.5 · IR for 30 s per hour
Leakage current Ileak At VR, 50 Hz
Climatic category (IEC 60068-1) 25/100/21 (– 25 °C/+100 °C/21 days damp heat test)
Approvals UL 1283; CSA C22.2 No.8
(Type S020: 500/290 V; Type S021 and S024: 600/350 V)
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 3
3-line filters B84143B*S020 … S024
for converters and power electronics
Characteristics and ordering codes
VR
AC
V
IR
A
Ileak
mA
Rtyp
µΩ
Approx.
weight
kg
Ordering code Approvals
Type S020 500/290 V
530/310 150 < 20 140 13 B84143B0150S020 ×
180 < 20 140 13 B84143B0180S020 ×
250 < 20 63 15 B84143B0250S020 ×
320 < 20 67 21 B84143B0320S020 ×
400 < 20 67 21 B84143B0400S020 ×
600 < 20 52 22 B84143B0600S020 ×
1000 < 20 33 28 B84143B1000S020 ×
1600 < 20 22 34 B84143B1600S020 ×
2500 < 20 15 105 B84143B2500S020 ×
Type S021 600/350 V
760/440 150 < 28 140 13 B84143B0150S021 ×
180 < 28 140 13 B84143B0180S021 ×
250 < 28 63 15 B84143B0250S021 ×
320 < 28 67 21 B84143B0320S021 ×
400 < 28 67 21 B84143B0400S021 ×
600 < 28 52 22 B84143B0600S021 ×
1000 < 28 33 28 B84143B1000S021 ×
1600 < 28 22 34 B84143B1600S021 ×
2500 < 28 15 105 B84143B2500S021 ×
Type S024 (Filters for IT mains supply1)) 600/350 V
690/400 150 < 905 140 13 B84143B0150S024 ×
180 < 905 140 13 B84143B0180S024 ×
250 < 905 63 15 B84143B0250S024 ×
320 < 905 67 21 B84143B0320S024 ×
400 < 905 67 21 B84143B0400S024 ×
600 < 905 52 22 B84143B0600S024 ×
1000 < 905 33 28 B84143B1000S024 ×
1600 < 905 22 34 B84143B1600S024 ×
2500 < 905 15 105 B84143B2500S024 ×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
× = approval granted
1) Filters for IT mains supply. (See also Chapter “General”, Section 7.4)
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 4
3-line filters B84143B*S020 ... S024
for converters and power electronics
Dimensional drawings
B84143B0150S02*, B84143B0180S02* (150 A, 180 A)
120±0.3
2 x M5 x 5
PE M10 x 30
ø9
36
30
80
140
2
81
141
310±2 10
20
91
10
Marking
L1
LINE LOAD
L2L3
L1’L2’L3’
115±0.2
32±1 32±1
260
155±0.2
170
6.6
5
3
SSB2142-7
B84143B0250S02* (250 A)
110±0.3
2 x M6 x 6 30
80
140
36
115
1
ø11 PE M10 x 30
15
360±7
25
90
15
Marking
L3 L2
LINE
L1
LOAD
L3’ L2’ L1’
60
300
240±1 60
ø12
165±1
190
40±1 40±1
SSB2143-F
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 5
3-line filters B84143B*S020 … S024
for converters and power electronics
B84143B0320S02*, B84143B0400S02* (320 A, 400 A)
B84143B0600S02* (600 A)
SSB2144-N
15 360±2 15
ø11 PE M10 x 30
25
91
36
4 x M6 x 6 30
2
85±0.5
16
116
180±0.5
210
120
60
300
240±1 60
5
42±2 42±2
ø12
260
235±1
Marking
LOADLINE
L1L2L3
L1’L2’L3’
SSB2145-W
ø11 PE M10 x 30
30
410±2.5
15 15
4 x M6 x 6 30
36
91
120
180±0.5
210
16
2
85±0.5
116
350
60 290±1 60
5
42±3 42±3
ø12
260
235±1
Marking
LINE LOAD
L1’L2’L3’
L3 L2 L1
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 6
3-line filters B84143B*S020 … S024
for converters and power electronics
B84143B1000S02* (1000 A)
4 x M6 x 6 40
ø14 PE M12 x 30
420±2.5 20
40
250
220±0.8
160
61
2.5
166
135±0.816
141
20
65 290±1
350
65
8
ø12
300
275±1
Marking
LOAD LINE
L1’ L2’ L3’
L3 L2 L1
52±3 52±3 SSB2146-5
B84143B1600S02* (1600 A)
340±1
400
ø12
300
275±1
105
10
92±3
L3 L2 L1
L2 L3 L1
105
Marking
LOAD LINE
92±3
141
2.5
16
50
550±3
ø14
PE M12 x 30
40 40
20 20
SSB1210-5
61
40
220±0.8
250
166
135±0.8
4 x M6 x 6
160
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 7
3-line filters B84143B*S020 … S024
for converters and power electronics
B84143B2500S02* (2500 A)
560±1.5
650
ø14
385
355±1
15
L3 L2 L1
L2 L3 L1
125
Marking
125
93±3
LOAD LINE
93±3
191.5
16.5
20 810±3.5 20
200
91.5
60
286±1
320
3.5
221.5
190±1
4 x M6 x 6
40
40
80
40
ø14 PE M16 x 50
SSB1211-D
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 8
3-line filters B84143B*S020 … S024
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 150 … 250 A (Type S020) Filters for 320 … 1000 A (Type S020)
100
SSB2131-R
100
SSB2132-Z
dB
dB
α
α
80
60
40
20
0
10
4
10
5
10
6
10
7
Hz 10
8
f
Filters for 1600 and 2500 A (Type S020)
100
B84143B1600S020
B84143B2500S020
SSB1800-Z
dB
α
80
60
40
20
0
B84143B0150 ... B0250S020
80
60
40
20
0
10
4
10
5
10
6
10
7
Hz 10
8
f
B84143B0320 ... B1000S020
10
4
10
5
10
6
10
7
Hz 10
8
f
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 9
3-line filters B84143B*S020 … S024
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 150 … 250 A (Type S021) Filters for 320 … 1000 A (Type S021)
B84143B0320 ... B1000S021
100
SSB2133-8
100 SSB2134-G
dB
dB
α
α
80
80
60
B84143B0150 ... B0250S021
60
40
40
20
20
0
0
10
4
10
5
10
6
10
7
Hz 10
8
104 10 5 106 107 Hz 108
f
f
Filters for 1600 and 2500 A (Type S021)
100
B84143B2500S021
B84143B1600S021
SSB1204-V
dB
α
80
60
40
20
0
10
4
10
5
10
6
10
7
Hz 10
8
f
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 10
3-line filters B84143B*S020 … S024
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 150 250 A (Type S024) Filters for 320 … 1000 A (Type S024)
100 SSB2135-P
100 SSB2136-X
dB
dB
α
α
80
60
40
20
0
104 10 5 106 107 Hz 10 8
f
Filters for 1600 and 2500 A (Type S024)
100
B84143B1600S024
B84143B2500S024
SSB1801-8
dB
α
80
60
40
20
0
B84143B0150 ... B0250S024
80
60
40
20
0
104 10 5 106 107 Hz 108
f
B84143B0320 ... B1000S024
104 105 106 107 Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 11
EMC filters
Cautions and warnings
Important information
Please read all safety and warning notes carefully before installing the EMC filter and putting it into
operation (see ). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appro-
priate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in low-
voltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warnings
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Danger-
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed and
the last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen-
cies that may cause resonances etc. can lead to destruction of the filter housing.
EMC filters must be protected in the application against impermissible exceeding of the rated
currents by suitable overcurrent protective.
12 01/06
EMC filters
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As
a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in which
the malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of
suitable design of the customer application or other action taken by the customer (e.g.
installation of protective circuitry or redundancy) that no injury or damage is sustained by third
parties in the event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as “hazardous”). Useful information on this will be found in our
Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more
detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products.
Consequently, we cannot guarantee that all products named in this publication will always be
available.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap,
PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are
trademarks registered or pending in Europe and in other countries. Further information will be
found on the Internet at www.epcos.com/trademarks.
13 01/06
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
EPCOS:
B84143B320S21 B84143B320S20 B84143B320S24 B84143B400S24 B84143B400S20 B84143B600S21
B84143B150S24 B84143B1600S21 B84143B150S20 B84143B150S21 B84143B1600S20 B84143B180S20
B84143B180S24 B84143B2500S20 B84143B1600S24 B84143B250S21 B84143B250S24 B84143B250S20
B84143B1000S20 B84143B1000S21 B84143B600S24 B84143B1000S24 B84143B180S21 B84143B2500S21
B84143B2500S24 B84143B400S21 B84143B600S020 B84143B0600S024