EMC filters 3-line filters for converters and power electronics Rated current 150 to 2500 A Series/Type: B84143B*S020 ... S024 Date: January 2006 EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the information contained therein without EPCOS' prior express consent is prohibited. 3-line filters B84143B*S020 ... S024 for converters and power electronics Power line filters for 3-phase systems Rated voltages 530/310, 690/400, 760/440 V AC Rated current 150 to 2500 A Alternative version Series B84143B*S080 and B84143B*S081 offers a low-cost solution. Construction 3-line filter Metal case Features Optimized leakage current Easy to install Very compact design Optimized for operation under full load Low weight UL, cUL approval Applications B84143B*S024 for IT mains supply Frequency converters for motor drives Wind farms Power supplies Terminals Busbars Marking Marking on component: Manufacturer's logo, ordering code, rated voltage, rated current, rated temperature, climatic category, date code Minimum marking on packaging: Manufacturer's logo, ordering code Please read Cautions and warnings and Important notes at the end of this document. 2 01/06 3-line filters B84143B*S020 ... S024 for converters and power electronics Typical circuit diagram LINE LOAD L1 L1' L2 L2' L3 L3' SSB2130-I Technical data and measuring conditions Rated voltage VR Type S020: 530/310 V AC, 50/60 Hz Type S021: 760/440 V AC, 50/60 Hz Type S024: 690/400 V AC, 50/60 Hz (Filters for IT mains supply. See also Chapter "General", Section 7.4) Rated current IR Referred to 40 C ambient temperature Test voltage Vtest Type S020: 2280 V DC, 2 s (line/line) 2690 V DC, 2 s (lines/case) Type S024: 2980 V DC, 2 s (line/line) 2890 V DC, 2 s (lines/case) Type S021: 3270 V DC, 2 s (line/line) 2890 V DC, 2 s (lines/case) Overload capability (thermal) 1.5 * IR for 3 min per hour or 2.5 * IR for 30 s per hour Leakage current Ileak At VR, 50 Hz Climatic category (IEC 60068-1) 25/100/21 (- 25 C/+100 C/21 days damp heat test) Approvals UL 1283; CSA C22.2 No.8 (Type S020: 500/290 V; Type S021 and S024: 600/350 V) Please read Cautions and warnings and Important notes at the end of this document. 3 01/06 3-line filters B84143B*S020 ... S024 for converters and power electronics Characteristics and ordering codes VR AC V IR Ileak Rtyp A mA 150 < 20 140 180 < 20 250 Approx. weight kg Ordering code Approvals 13 B84143B0150S020 x x 140 13 B84143B0180S020 x x < 20 63 15 B84143B0250S020 x x 320 < 20 67 21 B84143B0320S020 x x 400 < 20 67 21 B84143B0400S020 x x 600 < 20 52 22 B84143B0600S020 x x 1000 < 20 33 28 B84143B1000S020 x x 1600 < 20 22 34 B84143B1600S020 x x 2500 < 20 15 105 B84143B2500S020 x x Type S020 530/310 500/290 V Type S021 760/440 600/350 V 150 < 28 140 13 B84143B0150S021 x x 180 < 28 140 13 B84143B0180S021 x x 250 < 28 63 15 B84143B0250S021 x x 320 < 28 67 21 B84143B0320S021 x x 400 < 28 67 21 B84143B0400S021 x x 600 < 28 52 22 B84143B0600S021 x x 1000 < 28 33 28 B84143B1000S021 x x 1600 < 28 22 34 B84143B1600S021 x x 2500 < 28 15 105 B84143B2500S021 x x Type S024 (Filters for IT mains supply1)) 690/400 600/350 V 150 < 905 140 13 B84143B0150S024 x x 180 < 905 140 13 B84143B0180S024 x x 250 < 905 63 15 B84143B0250S024 x x 320 < 905 67 21 B84143B0320S024 x x 400 < 905 67 21 B84143B0400S024 x x 600 < 905 52 22 B84143B0600S024 x x 1000 < 905 33 28 B84143B1000S024 x x 1600 < 905 22 34 B84143B1600S024 x x 2500 < 905 15 105 B84143B2500S024 x x x = approval granted 1) Filters for IT mains supply. (See also Chapter "General", Section 7.4) Please read Cautions and warnings and Important notes at the end of this document. 4 01/06 3-line filters B84143B*S020 ... S024 for converters and power electronics Dimensional drawings B84143B0150S02*, B84143B0180S02* (150 A, 180 A) 2 x M5 x 5 1200.3 30 PE M10 x 30 10 10 3102 141 2 36 81 91 20 o9 80 140 260 1150.2 321 LINE LOAD 1550.2 170 Marking L3' L2' L1' 3 L3 L2 L1 321 6.6 SSB2142-7 B84143B0250S02* (250 A) 2 x M6 x 6 1100.3 30 PE M10 x 30 15 1 36 90 115 25 o11 15 3607 80 140 300 2401 LINE LOAD 1651 190 Marking 60 L3' L2' L1' 5 L3 L2 L1 60 o12 401 401 Please read Cautions and warnings and Important notes at the end of this document. SSB2143-F 5 01/06 3-line filters B84143B*S020 ... S024 for converters and power electronics B84143B0320S02*, B84143B0400S02* (320 A, 400 A) 4 x M6 x 6 30 15 15 3602 300 2401 LOAD L2' 2351 260 LINE L3' L1 L2 5 Marking L3 60 L1' 60 120 1800.5 210 2 16 36 91 25 850.5 116 PE M10 x 30 o11 o12 422 422 SSB2144-N B84143B0600S02* (600 A) 15 15 4102.5 350 2901 LOAD L2' 2351 260 LINE L3' L1 L2 5 Marking L3 60 L1' 60 120 1800.5 210 o12 423 423 Please read Cautions and warnings and Important notes at the end of this document. SSB2145-W 6 01/06 2 16 850.5 116 30 36 30 4 x M6 x 6 91 PE M10 x 30 o11 3-line filters B84143B*S020 ... S024 for converters and power electronics B84143B1000S02* (1000 A) 40 1350.8 166 4 x M6 x 6 20 20 4202.5 350 2901 160 2200.8 250 65 L2 L2' Marking LOAD L3 L3' LINE 2751 300 8 L1 L1' 65 2.5 16 61 40 141 PE M12 x 30 o14 o12 523 523 SSB2146-5 B84143B1600S02* (1600 A) 400 3401 105 141 105 61 20 160 L3 LOAD L3 LINE 923 2751 300 L2 L2 Marking 40 2200.8 250 L1 10 L1 4 x M6 x 6 923 o12 2.5 16 20 5503 1350.8 166 50 o14 40 40 PE M12 x 30 Please read Cautions and warnings and Important notes at the end of this document. 7 01/06 SSB1210-5 3-line filters B84143B*S020 ... S024 for converters and power electronics B84143B2500S02* (2500 A) 650 5601.5 125 191.5 91.5 125 20 200 L3 LOAD L3 LINE 933 3551 385 L2 L2 Marking 60 2861 320 L1 15 L1 4 x M6 x 6 933 o14 3.5 16.5 20 8103.5 40 80 40 40 1901 221.5 o14 Please read Cautions and warnings and Important notes at the end of this document. PE M16 x 50 8 01/06 SSB1211-D 3-line filters B84143B*S020 ... S024 for converters and power electronics Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) Filters for 150 ... 250 A (Type S020) Filters for 320 ... 1000 A (Type S020) 100 dB B84143B0150 ... B0250S020 SSB2131-R 100 dB B84143B0320 ... B1000S020 SSB2132-Z 80 80 60 60 40 40 20 20 0 4 10 10 5 10 6 10 7 0 4 10 Hz 10 8 f Filters for 1600 and 2500 A (Type S020) SSB1800-Z 100 B84143B1600S020 B84143B2500S020 dB 80 60 40 20 0 10 4 10 5 10 6 10 7 Hz 10 8 f Please read Cautions and warnings and Important notes at the end of this document. 9 01/06 10 5 10 6 10 7 Hz 10 8 f 3-line filters B84143B*S020 ... S024 for converters and power electronics Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) Filters for 150 ... 250 A (Type S021) Filters for 320 ... 1000 A (Type S021) SSB2133-8 100 dB 100 dB B84143B0320 ... B1000S021 SSB2134-G 80 80 60 60 40 40 20 20 B84143B0150 ... B0250S021 0 4 10 10 5 10 6 10 7 0 4 10 Hz 10 8 f Filters for 1600 and 2500 A (Type S021) SSB1204-V 100 B84143B1600S021 B84143B2500S021 dB 80 60 40 20 0 10 4 10 5 10 6 10 7 Hz 10 8 f Please read Cautions and warnings and Important notes at the end of this document. 10 01/06 10 5 10 6 10 7 Hz 10 8 f 3-line filters B84143B*S020 ... S024 for converters and power electronics Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) Filters for 150 ... 250 A (Type S024) Filters for 320 ... 1000 A (Type S024) 100 dB B84143B0150 ... B0250S024 SSB2135-P 100 dB SSB2136-X 80 80 60 60 40 40 20 20 0 4 10 10 5 10 6 10 7 B84143B0320 ... B1000S024 0 4 10 5 10 6 10 7 10 Hz 10 8 f Filters for 1600 and 2500 A (Type S024) SSB1801-8 100 B84143B1600S024 B84143B2500S024 dB 80 60 40 20 0 10 4 10 5 10 6 10 7 Hz 10 8 f Please read Cautions and warnings and Important notes at the end of this document. 11 01/06 Hz 10 8 f EMC filters Cautions and warnings Important information Please read all safety and warning notes carefully before installing the EMC filter and putting it into operation (see ). The same applies to the warning signs on the filter. Please ensure that the signs are not removed nor their legibility impaired by external influences. Death, serious bodily injury and substantial material damage to equipment may occur if the appro priate safety measures are not carried out or the warnings in the text are not observed. Using according to the terms The EMC filters may be used only for their intended application within the specified values in low voltage networks in compliance with the instructions given in the data sheets and the data book. The conditions at the place of application must comply with all specifications for the filter used. Warnings It shall be ensured that only qualified persons (electricity specialists) are engaged on work such as planning, assembly, installation, operation, repair and maintenance. They must be provided with the corresponding documentation. Danger of electric shock. EMC filters contain components that store an electric charge. Danger ous voltages can continue to exist at the filter terminals for longer than five minutes even after the power has been switched off. The protective earth connections shall be the first to be made when the EMC filter is installed and the last to be disconnected. Depending on the magnitude of the leakage currents, the particular specifications for making the protective-earth connection must be observed. Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen cies that may cause resonances etc. can lead to destruction of the filter housing. EMC filters must be protected in the application against impermissible exceeding of the rated currents by suitable overcurrent protective. 12 01/06 EMC filters Important notes The following applies to all products named in this publication: 1. Some parts of this publication contain statements about the suitability of our products for certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We nevertheless expressly point out that such statements cannot be regarded as binding statements about the suitability of our products for a particular customer application. As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS product with the properties described in the product specification is suitable for use in a particular customer application. 2. We also point out that in individual cases, a malfunction of passive electronic components or failure before the end of their usual service life cannot be completely ruled out in the current state of the art, even if they are operated as specified. In customer applications requiring a very high level of operational safety and especially in customer applications in which the malfunction or failure of a passive electronic component could endanger human life or health (e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of suitable design of the customer application or other action taken by the customer (e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or failure of a passive electronic component. 3. The warnings, cautions and product-specific notes must be observed. 4. In order to satisfy certain technical requirements, some of the products described in this publication may contain substances subject to restrictions in certain jurisdictions (e.g. because they are classed as "hazardous"). Useful information on this will be found in our Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed questions, please contact our sales offices. 5. We constantly strive to improve our products. Consequently, the products described in this publication may change from time to time. The same is true of the corresponding product specifications. Please check therefore to what extent product descriptions and specifications contained in this publication are still applicable before or when you place an order. We also reserve the right to discontinue production and delivery of products. Consequently, we cannot guarantee that all products named in this publication will always be available. 6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of the "General Terms of Delivery for Products and Services in the Electrical Industry" published by the German Electrical and Electronics Industry Association (ZVEI). 7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap, PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at www.epcos.com/trademarks. 13 01/06 Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: EPCOS: B84143B320S21 B84143B320S20 B84143B320S24 B84143B400S24 B84143B400S20 B84143B600S21 B84143B150S24 B84143B1600S21 B84143B150S20 B84143B150S21 B84143B1600S20 B84143B180S20 B84143B180S24 B84143B2500S20 B84143B1600S24 B84143B250S21 B84143B250S24 B84143B250S20 B84143B1000S20 B84143B1000S21 B84143B600S24 B84143B1000S24 B84143B180S21 B84143B2500S21 B84143B2500S24 B84143B400S21 B84143B600S020 B84143B0600S024