Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC-3 400 V Ie A Max. rating for three-phase motors, 50 - 60 Hz AC-3 230 V P kW 15.5 Max. rating for three-phase motors, 50 - 60 Hz AC-3 400 V P kW 22 Max. rating for three-phase motors, 50 - 60 Hz AC-3 690 V P kW 30 Max. rating for three-phase motors, 50 - 60 Hz AC-4 230 V P kW 6 Max. rating for three-phase motors, 50 - 60 Hz AC-4 400 V P kW 10 Max. rating for three-phase motors, 50 - 60 Hz AC-4 690 V P kW 14 Ith = Ie A 60 Conventional thermal current I th = I e AC-1 Open 50 DILM150-XHI(V).. DILM1000-XHI(V).. For use with General Standards IEC/EN 60947, VDE 0660, UL, CSA Lifespan, mechanical AC operated Operations x 106 10 DC operated Operations x 106 10 Operating frequency, mechanical AC operated Operations/h 5000 DC operated Operations/h 5000 Climatic proofing Ambient temperature 1 Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclical, to IEC 60068-2-30 Open C -25/60 Enclosed C -25/40 Storage C -40/80 Mechanical shock resistance (IEC/EN 60068-2-27) Half-sinusoidal shock, 20 ms Main contacts Make contact g 10 Make contact g 7 Break contact g 5 Auxiliary contacts Protection type IP00 Protection against direct contact when actuated from front (IEC 536) Finger- and back-of-hand proof Weight AC operated kg 0,9 DC operated kg 1,1 Terminal capacity Main cable Solid mm2 1 x (2.5 - 16) 2 x (2.5 - 16) Flexible with ferrule mm2 2 x (2.5 - 25) 1 x (2.5 - 35) Stranded mm2 1 x (16 - 50) 2 x (16 - 35) AWG 12 - 2 Solid or stranded flat conductor Number of segments x width x thickness mm Anschlussschraube Hauptleiter Tightening torque 2 x (6 x 9 x 0.8) M6 Nm 3 Solid mm2 1 x (0.75 - 4) 1 x (0.75 - 4) Flexible with ferrule mm2 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) Solid or stranded AWG 18 - 14 Terminal capacity Control circuit cables Anschlussschraube Hilfsleiter Tightening torque M3.5 Nm 1.2 Tool Main cable Pozidriv screwdriver Size 2 mm 0.8 x 5.5 1x6 Pozidriv screwdriver Size 2 Standard screwdriver mm 0.8 x 5.5 1x6 mm2 0.75 - 2.5 Standard screwdriver Control circuit cables Terminal capacity Control circuit cables Solid 2 Flexible mm2 0.75 - 2.5 Flexible with ferrule mm2 0.75 - 2.5 Solid or stranded AWG 18 - 14 Tool Stripping length mm 10 Screwdriver blade width mm 3,5 Main conducting paths Rated impulse withstand voltage Uimp V AC Overvoltage category/pollution degree 8000 III/3 Rated insulation voltage AC Ui V AC 690 Rated operational voltage Ue V AC 690 between coil and contacts V AC 440 between the contacts V AC 440 A 700 Safe isolation to VDE 0106 Part 101 and Part 101/A1 Making capacity (cos O to IEC/EN 60947) up to 690 V Breaking capacity 220/230 V A 500 380/400 V A 500 500 V A 500 660/690 V A 320 Component lifespan AC-3/AC-4 Tripping characteristics Maximum operating frequency AC-1; 400 V Ie Ops/h 800 AC-3; 400 V Ie Ops/h 800 AC-4; 400 V Ie Ops/h 300 400 V gG/gL 500 V A 80 690 V gG/gL 690 V A 63 400 V gG/gL 500 V A 160 690 V gG/gL 690 V A 80 at 40 C Ith A 70 at 50 C Ith A 65 at 55 C Ith A 63 at 60 C Ith A 60 Enclosed Ith A 54 Short-circuit rating Short-circuit protection Maximum fuse Type "2" coordination Type "1" coordination AC AC-1 duty conv. therm. current 3-pole 50 - 60 Hz open 3 Conventional free air thermal current, 1-pole open Ith A 150 Enclosed Ith A 135 220/230 V Ie A 50 240 V Ie A 50 380/400 V Ie A 50 415 V Ie A 50 440V Ie A 50 500 V Ie A 50 660/690 V Ie A 32 220/230 V P kW 15,5 240V P kW 17 380/400 V P kW 22 415 V P kW 30 440 V P kW 32 500 V P kW 36 660/690 V P kW 30 220/230 V Ie A 21 240 V Ie A 21 380/400 V Ie A 21 415 V Ie A 21 440 V Ie A 21 500 V Ie A 21 660/690 V Ie A 17 220/230 V P kW 6 240 V P kW 6,5 380/400 V P kW 10 415 V P kW 11 440 V P kW 12 500 V P kW 13 660/690 V P kW 14 60 V Ie A 60 110 V Ie A 50 220 V Ie A 45 440 V Ie A 2,9 AC-3 duty Rated operational current AC-3 open, 50 - 60 Hz, 3-pole Motor rating AC-4 duty Rated operational current AC-4 open, 50 - 60 Hz, 3-pole Motor rating DC of three-phase capacitors open DC-1 operation DC-3 operation 4 60 V Ie A 60 110 V Ie A 50 220 V Ie A 25 440 V Ie A 0,6 60 V Ie A 60 110 V Ie A 50 220 V Ie A 25 440 V Ie A 0,6 Current heat loss at Ith W 16,2 Current heat loss at Ie to AC-3/400 V W 11,3 Impedance per pole m& 1,5 Pick-up x Uc 0,8 - 1,1 Abfall x Uc 0,3 - 0,6 Pick-up x Uc 0,7 - 1,2 Abfall x Uc 0,15-0,6 50 Hz Pick-up VA 130 50 Hz Pick-up W 80 50 Hz Sealing VA 14 50 Hz Sealing W 4 DC operated Pick-up W 24 at 24 V DC operated Sealing W 0.5 at 24 V DC-5 operation Current heat loss (3-pole) Magnet systems Voltage tolerance AC operated AC operated Drop-out voltage AC operated Drop-out voltage AC operated DC operated DC operated DC operated DC operated Power consumption of the coil in a cold state and 1.0 x Uc Duty factor % DF 100 Closing delay ms 25 Opening delay ms 25 Switching times at 100 % Uc (approximate values) Main contacts AC operated DC operated Closing delay ms 60 Opening delay ms 20 Arcing time ms 10 Electromagnetic compatibility (EMC) Emitted interference to EN 60947-1 Interference immunity to EN 60947-1 Mounting position, AC- and DC operated 5 Moeller GmbH, Hein-Moeller-Str. 7-11, D-53115 Bonn E-Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net Copyright 2005 by Moeller GmbH. Subject to modifications. HPL-C2005GB-INT V3.0 6