For more information, please visit the product page | If your application requires forced air, view our Dc Fans date 12/12/2014 page 1 of 7 SERIES: PSF-100 DESCRIPTION: AC-DC POWER SUPPLY ED FEATURES up to 100 W continuous power universal input (90~264 Vac) built-in constant current limit circuitry alarm signal for AC OK and battery low short circuit, over load, over voltage, brown-out, battery low, and battery polarity protections * withstand 2G vibration test * efficiency up to 87% output voltage output current1 (Vdc) max (A) Vo1 Vo2 13.8 13.8 PSF-100-B Vo1 Vo2 Vo3 13.8 13.8 5 PSF-100-C Vo1 Vo2 27.6 27.6 PSF-100-D Vo1 Vo2 Vo3 27.6 27.6 5 efficiency max (W) max (mVp-p) typ (%) 7.3 2.875 100 100 150 86 6.2 2.875 3 100 100 150 100 85 3.65 1.725 100 100 150 87 3.1 1.725 3 100 100 150 100 85 O 1. Vo2 battery discharge current must not exceed 50% of the rated power. 2. Maximum total combined power (rated power). 3. At 20 MHz bandwidth using a 12" twisted pair-wire, each output terminated with a 47 F and 0.1 F parallel capacitors. IS C Notes: ripple and noise3 N PSF-100-A output power2 TI MODEL N U * * * * * D PART NUMBER KEY PSF-100 - X - XXX Base Number Output Voltage A = 13.8 Vdc, 13.8 Vdc B = 13.8 Vdc, 13.8 Vdc, 5 Vdc C = 27.6 Vdc, 27.6 Vdc D = 27.6 Vdc, 27.6 Vdc, 5 Vdc cui.com Chassis "blank" = open frame CNF = enclosed For more information, please visit the product page | If your application requires forced air, view our Dc Fans CUI Inc SERIES: PSF-100 DESCRIPTION: AC-DC POWER SUPPLY date 12/12/2014 page 2 of 7 INPUT parameter conditions/description min typ voltage surge voltage for maximum of 5 seconds frequency 47 current at 115 Vac at 230 Vac inrush current at 115 Vac, cold start at 230 Vac, cold start leakage current at 264 Vac conditions/description line regulation low line to high line, at rated load Vo1, Vo3 load regulation 10% to 100% rated load Vo1 Vo3 voltage accuracy Vo1 Vo3 hold-up time at 115 Vac, full load at 230 Vac, full load setup time at 115/230 Vac, full load, cold start rise time at 115/230 Vac, full load adjustability Vo1 temperature coefficient Vo1, 0C~50C AC OK PSF-100-A, PSF-100-C PSF-100-B, PSF-100-D TTL open collector output relay contact output battery low PSF-100-A, PSF-100-C PSF-100-B, PSF-100-D <12 V 3% <22 V 3% parameter Vac Vdc 300 Vac 63 Hz A A 35 70 A A TI typ 1 mA max units 0.5 % 0.5 1.5 % % 2 3 % % 8 50 ms ms 50 ms 800 N O PROTECTIONS min N parameter units 264 373 2.0 1.2 U OUTPUT max ED 90 127 ms 10 % 0.03 %/C conditions/description min Vo1, latch off mode 115 over current protection auto recovery, hiccup mode Vo1, Vo3 Vo2 110 100 battery cut off PSF-100-A, PSF-100-B PSF-100-C, PSF-100-D 9.5 19 10 20 10.5 21 Vdc Vdc min typ max units IS C over voltage protection typ max units 150 % % % SAFETY & COMPLIANCE conditions/description isolation voltage input to output input to ground output to ground isolation resistance input to output at 500 Vdc D parameter 3,000 1,500 500 Vac Vac Vac 100 M safety approvals UL 60950-1, EN 60950-1 EMI/EMC1 EN 55022, EN 61000-6-(1,3), EN 61000-3-(2,3), EN 55024, EN 50204, EN 61204-3, EN 61000-4-(2, 3, 4, 5, 6, 8, 11) MTBF PSF-100-A, PSF-100-B as per MIL-HDBK-217F PSF-100-C, PSF-100-D as per MIL-HDBK-217F RoHS Note: 103,400 92,100 hrs hrs 2011/65/EU 1. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. cui.com For more information, please visit the product page | If your application requires forced air, view our Dc Fans CUI Inc SERIES: PSF-100 DESCRIPTION: AC-DC POWER SUPPLY date 12/12/2014 page 3 of 7 ENVIRONMENTAL conditions/description min max units see derating curve -20 70 C -40 85 C storage temperature operating humidity non-condensing 20 storage humidity non-condensing 10 vibration at 10~500 Hz, 10 min per cycle for 60 minutes each test along the X, Y, and Z axis % G 100 Load (%) 60 50 Safe operating area 40 80 N PSF-100-B-CNF & PSF-100-D-CNF 20 60 40 20 0 10 20 30 40 50 MECHANICAL 0 70 N Ambient Temperature (C) 60 conditions/description dimensions open frame: 123 x 95 x 31 enclosed: 129.5 x 97.5 x 37.5 weight open frame enclosed D IS C O parameter cui.com 90 95 100 min 105 110 115 120 ~ ~ -10 TI Load (%) 90 U All other models 0 -20 % Load vs. Input Voltage (at 25C) 100 80 90 2 DERATING CURVES Load vs. Temperature typ ED parameter operating temperature 264 Input Voltage (Vac) 60 Hz typ max units mm mm 0.34 0.47 kg kg For more information, please visit the product page | If your application requires forced air, view our Dc Fans CUI Inc SERIES: PSF-100 DESCRIPTION: AC-DC POWER SUPPLY date 12/12/2014 page 4 of 7 MECHANICAL DRAWING OPEN FRAME CN1 Pin Connections CN2 Pin Connections PIN Function 1 AC/L 2 AC/N 1 AC OK 3 FG 2 BAT LOW PIN Function 3 PSF-100-A: (13.8 V/20 mA) PSF-100-C: (27.6 V/20 mA) PSF-100-A, PSF-100-C3 -Vo1 5 +Vo1 6 +Vo2 (+ BAT) 71 -Vo2 (- BAT) 8 +Vo3 (+5 V) PSF-100-B, PSF-100-D4 1 2 U 4 AC OK 3 4 BAT LOW N TI N 2 ED units: mm CNF units: mm 1 AC/L 2 AC/N 3 FG CN2 Pin Connections PIN Function PSF-100-A, PSF-100-C3 1 AC OK 2 BAT LOW IS C Function O CN1 Pin Connections PIN -Vo1 5 +Vo1 6 +Vo2 (+ BAT) 71 -Vo2 (- BAT) 82 +Vo3 (+5 V) 3 PSF-100-A: (13.8 V/20 mA) PSF-100-C: (27.6 V/20 mA) PSF-100-B, PSF-100-D4 1 2 3 4 AC OK BAT LOW D 4 Notes: 1. To protect product damage do not connect the GND port with -BAT port. 2. PSF-100-B and PSF-100-D only. 3. For PSF-100-A & PSF-100-C, CN2 mates with JST XHP-3 or equivalent and JST SXH-001 T-P0.6 or equivalent. 4. For PSF-100-B & PSF-100-D, CN2 mates with JST XHP-4 or equivalent and JST SXH-001 T-P0.6 or equivalent. cui.com For more information, please visit the product page | If your application requires forced air, view our Dc Fans CUI Inc SERIES: PSF-100 DESCRIPTION: AC-DC POWER SUPPLY date 12/12/2014 page 5 of 7 BATTERY CHARGING SPECIFICATIONS Block Diagram Alarm Circuit for PSF-100-B & PSF-100-D ED Alarm Circuit for PSF-100-A & PSF-100-C PSF-100-A & PSF-100-C TI N U y Alarm Signal for AC OK and Battery Low Description Alarm Output The signal is low when the power supply turns on Low (0.3 V max. at 30 mA) The signal is high when the power supply turns off High/open (external voltage < 50 V) The signal is low when the voltage of the battery is below: 12 V (PSF-100-A), 22 V (PSF-100-C) Low (0.3 V max. at 30 mA) The signal is high when the voltage of the battery is above: 12 V (PSF-100-A), 22 V (PSF-100-C) High/open (external voltage < 50 V) N Function O AC OK IS C Battery Low 1. Alarm signal is sent out through "AC OK" and "Battery Low" pins. 2. An external voltage source is required for this function. The maximum applied voltage is 50 V and the maximum sink current is 30 mA. Internal Circuit of AC OK and Battery Low PSF-100-A: PSF-100-C: D Notes: cui.com For more information, please visit the product page | If your application requires forced air, view our Dc Fans CUI Inc SERIES: PSF-100 DESCRIPTION: AC-DC POWER SUPPLY date 12/12/2014 page 6 of 7 BATTERY CHARGING SPECIFICATIONS (CONTINUED) Alarm Signal for AC OK and Battery Low AC OK Battery Low Alarm Output Low or short The signal is high when the power supply turns off High/open (external voltage < 30 V) The signal is low when the voltage of the battery is below: 12 V (PSF-100-B), 22 V (PSF-100-D) Low or short The signal is high when the voltage of the battery is above: 12 V (PSF-100-B), 22 V (PSF-100-D) High/open (external voltage < 30 V) 1. Alarm signal is sent out through "AC OK" and "Battery Low" pins (relay contact type). 2. An external voltage source is required for this function. The maximum applied voltage is 30 V and the maximum sink current is 1 A. N Notes: Description The signal is low when the power supply turns on U Function ED PSF-100-B & PSF-100-D D IS C O N TI Internal Circuit of AC OK and Battery Low Notes: 1. All specifications measured at 25C, 230Vac input voltage, and rated power unless otherwise noted. cui.com For more information, please visit the product page | If your application requires forced air, view our Dc Fans CUI Inc SERIES: PSF-100 DESCRIPTION: AC-DC POWER SUPPLY date 12/12/2014 page 7 of 7 REVISION HISTORY description date 1.0 initial release 11/25/2013 1.01 updated datasheet ED rev. 12/12/2014 D IS C O N TI N U The revision history provided is for informational purposes only and is believed to be accurate. Headquarters 20050 SW 112th Ave. Tualatin, OR 97062 800.275.4899 Fax 503.612.2383 cui.com techsupport@cui.com CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website. CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use. CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness. Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: CUI Inc.: PSF-100-D PSF-100-B PSF-100-D-CNF PSF-100-A-CNF PSF-100-C-CNF PSF-100-C PSF-100-B-CNF PSF100-A