cui.com
date 12/12/2014 page 2 of 7
CUI Inc │ SERIES: PSF-100 │ DESCRIPTION: AC-DC POWER SUPPLY
INPUT
parameter conditions/description min typ max units
voltage 90
127
264
373
Vac
Vdc
surge voltage for maximum of 5 seconds 300 Vac
frequency 47 63 Hz
current at 115 Vac
at 230 Vac
2.0
1.2
A
A
inrush current at 115 Vac, cold start
at 230 Vac, cold start
35
70
A
A
leakage current at 264 Vac 1 mA
OUTPUT
parameter conditions/description min typ max units
line regulation low line to high line, at rated load
Vo1, Vo3 ±0.5 %
load regulation
10% to 100% rated load
Vo1
Vo3
±0.5
±1.5
%
%
voltage accuracy Vo1
Vo3
±2
±3
%
%
hold-up time at 115 Vac, full load
at 230 Vac, full load
8
50
ms
ms
setup time at 115/230 Vac, full load, cold start 800 ms
rise time at 115/230 Vac, full load 50 ms
adjustability Vo1 ±10 %
temperature coefcient Vo1, 0°C~50°C ±0.03 %/°C
AC OK PSF-100-A, PSF-100-C
PSF-100-B, PSF-100-D
TTL open collector output
relay contact output
battery low PSF-100-A, PSF-100-C
PSF-100-B, PSF-100-D
<12 V ±3%
<22 V ±3%
PROTECTIONS
parameter conditions/description min typ max units
over voltage protection Vo1, latch off mode 115 150 %
over current protection
auto recovery, hiccup mode
Vo1, Vo3
Vo2
110
100
%
%
battery cut off PSF-100-A, PSF-100-B
PSF-100-C, PSF-100-D
9.5
19
10
20
10.5
21
Vdc
Vdc
SAFETY & COMPLIANCE
parameter conditions/description min typ max units
isolation voltage
input to output
input to ground
output to ground
3,000
1,500
500
Vac
Vac
Vac
isolation resistance input to output at 500 Vdc 100 MΩ
safety approvals UL 60950-1, EN 60950-1
EMI/EMC1EN 55022, EN 61000-6-(1,3), EN 61000-3-(2,3),
EN 55024, EN 50204, EN 61204-3, EN 61000-4-(2, 3, 4, 5, 6, 8, 11)
MTBF PSF-100-A, PSF-100-B as per MIL-HDBK-217F
PSF-100-C, PSF-100-D as per MIL-HDBK-217F
103,400
92,100
hrs
hrs
RoHS 2011/65/EU
Note: 1. The power supply is considered a component which will be installed into a nal equipment. The nal equipment must be re-conrmed that it still meets EMC directives.
For more information, please visit the product page | If your application requires forced air, view our Dc Fans