MINI MCR-SL-R-UI(-SP)
102807_en_05 PHOENIX CONTACT 7
Configuration
www.interface.phoenixcontact.com
MINI MCR-SL-R-UI
Ord.-No.: 28 64 09 5
Resistance - Transducer
0...100 k W
0(4)...20mA, 0(1)...5V , 0...10V
I£500 W/U³10 k W
1,5kV , 50 Hz, 1min.
-20°..+65°C / -4°...+149°F
Meas. range:
Out:
Load:
Test voltage:
Amb. Temp.:
Serial No. XXXXXXXX
1
2
3
4
5
6
7+
8-
POWER
OUT
IN
Out U,I
GND 1
19,2...30VDC
GND 2
on
off
S2
1
on
off
18S1
S1
S2
If the modules are not configured (all DIP switches set to
pos. 0), the module does not have a defined function until the
DIP switches have been set.
You can use the S1 DIP switch to prescribe the output signal
range, potentiometer/open circuit detection and fault evalua-
tion.
Activate automatic potentiometer detection to obtain opti-
mum measurement results.
You can use the S2 DIP switch to select the voltage and cur-
rent output.
CAUTION: Electrostatic discharge
The module contains components that can be
damaged or destroyed by electrostatic di-
scharge. When handling the module, observe
the necessary safety precautions against elec-
trostatic discharge (ESD) according to EN
61340-5-1 and EN 61340-5-2.
Diagnostics
The LED indicates the following error states:
– LED ON: In the event of a wire break on the sensor side,
measured value overrange or measured value under-
range
DIP switches
DIP S1 Output signal range
OUT
Automatic potentiometer
detection Open circuit detection slider Transmission Behavior
123 4 5 6
0...20 mA on on Fault evaluation in acc. with
• 20...0 mA • off • off DIP 1 (7+8)
• 4...20 mA
•
Output in acc. with NE 43
• • 20...4 mA Open circuit 0 mA (0 V)
• 0...10 V Linear behavior
• • 10...0 V 3.8 mA ... 20.5 mA
• • 0...5 V (0.95 V ... 5.12 V)
• • • 1...5 V Only active for 4...20 mA
(1...5 V) OUT
7 8 Open circuit Measuring range
overrange
Measuring range
underrange
AEnd of measuring range
+5 %
End of measuring range
+2.5 % Start of measuring range
B• End of measuring range
+5 %
End of measuring range
+2.5 %
Start of measuring range
-12.5 %
C•
End of measuring range
+5 % End of measuring range Start of measuring range
D• • Start of measuring range End of measuring range Start of measuring range
DIP S2 Output signal
OUT
12
•0...20 mA, 4...20 mA, 20...0 mA, 20...4 mA
•0...10 V, 10...0 V, 0...5 V, 1...5 V •=ON
•• Not allowed! =OFF