UK: +44 (0)1384 842211 France: +33 (0)1 4305 8680 Germany: +49 (0)6621 50570 Netherlands: +31 (0)24 372 3210
HELIOS
Mini System 3500
3500W 48VDC Compact Flexible Power System
SPECIAL FEATURES
• 3500W Constant Power Output System
• Available in 110VAC or 220VAC systems
• 110 VAC systems contain from one to eight,
250W Output Rectifiers providing up to
1750W with N+1 Redundancy
• 220 VAC systems contain from one to eight,
500W Output Rectifiers providing up to
3500W with N+1 Redundancy
• Adjustable DC Output Voltage: (48 to 55.5V)
• Adjustable Temperature Compensation
(Disabled to 144mV/DEG C)
• Adjustable Low Voltage Disconnect
(Disabled to 47 V DC)
•
Adjustable Battery Charge Control (2A to 20A)
•
Distribution: 10 Fuse Positions (0 to 15A each)
- Up to five breakers
• Power Factor Correction
• Current Sharing
• Soft Switching Technology
•
Full Output Power at Full Temperature Range
• Full Complement of LED and Output Alarms
Available
• Connections for up to Two Battery Strings
• EMI Filter Included
•
Compact Dimensions (21.5"W x 5.25"H x 14"D)
(550 x 133 x 300mm)
• Optional fan shelf for increased temperature
range, and installation in areas with low
volume or no air flow
ENVIRONMENTAL
• EMC/EMI: FCC Class B, CISPR Class B for
digital devices, Bellcore GR-1089-CORE
• ESD: Bellcore TR-NWT-001089
• Temperature: -40° to +50°C with natural
convection cooling, -40°C to +65°C with
forced air cooling
• Humidity: 0 to 95% RH (non-condensing)
• Acoustic Noise: <65dB for full system
including eight rectifiers, fan unit
• Cooling: natural convection / forced air
•
Shock and Vibration: Bellcore TR-NWT-000063
• Fire Resistance: UL94VO
• Voltage Surge Protection: meets IEEE
C62.41-1991
ELECTRICAL SPECIFICATIONS
Input
AC Input Voltage Range ....... 110/120VAC (96 - 132 VAC)(250 watt
rectifiers)
208/240VAC (176 - 264VAC)(500 watt
rectifiers)
Frequency ............................ 50 - 60 Hz (45 - 65 Hz)
Efficiency .............................. >86% (50 - 100% output load)
Power Factor ........................ 0.99 (50 - 100% output load)
Total Harmonic Distortion ..... <5%
Output
DC Output Voltage Range ... -48VDC (user selectable 48 - 55.5VDC)
Maximum Output Power ...... 1750 watt/system @110VAC (250 watt
rectifiers)
3500 watt/system @ 220VAC (500 watt
rectifiers)
Voltage Regulation ............... +/- 0.5% load/line and +/- 1.0% load/line/
temperature
Dynamic Response .............. from +/-5% for 10% to 90% or 90% to
10% load step changes
Protection and/or
Disconnect ........................... fuses/breakers
Parallel Operation ................ +/- 10% of rated current between
rectifiers
Power/Current Limit ............. 102.5% +/- 2.5% of rated power at
output voltages >42VDC
Capacitor Precharge ............ Automatic upon insertion
Hold-up Time ........................ Output voltage remains above -42V for
30 msec
Voice Frequency Noise ........ less than 55 dB mC
High Frequency Noise ......... less than 250 mV rms
SAFETY
UL 1950
UL1801
CSA C22.2 No. 950
IEC-950
Input Voltages
96 - 264VAC
# of Outputs
1 - 15
Total Power
3500 Watts
Size
21.5" W x 5.25" H x 14" D