23/04/2013 www.crouzet.com 17.5 mm DIN rail mounting MXR1 Part number 88827185 Relay or solid state output Multi-function or mono-function Multi-range Multi-voltage Screw or spring terminals LED status indicator (relay version) Option of connecting an external power supply to the control input 3-wire sensor control option Part numbers Functions Timing Output Nominal rating Connections Supply voltage Ad - Ah - N - O - P - Pt - TL - Tt - W 0,1s100h 1 changeover relay 8A Screw terminals 24 V DC / 24 240 V AC Type 88 827 185 MXR1 Specifications Timing Timing ranges (7 ranges) Repetition accuracy with constant parameters Drift Temperature Drift Voltage Display accuracy according to IEC/EN 61812-1 Minimum pulse duration typically (relay version) Minimum pulse duration typically (solid state version) Minimum pulse duration typically (relay version under load) Maximum reset time by de-energisation typically (relay version) Maximum reset time by de-energisation typically (solid state version) Immunity from micro power cuts : typical 1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h 0.5 % (IEC/EN 61812-1) 0,05 % / C 0,2 % / V 10 % / 25 C 30 ms 50 ms 100 ms 120 ms 350 ms < 10 ms Supply Multi-voltage power supply Frequency (Hz) Operating range Operator factor Max. absorbed power Depending on version 50 / 60 85 110 % Un 85 120 % Un for 12 V AC / DC 100 % 32 VA (240 VAC) 1,5 W (240 VDC) 0,6 W (24 VDC) 0,7 VA (12 VAC) 0,7 W (12 VDC) Output specification 1 or 2 changeover relays, AgNi (cadmium-free) Rated power Maximum breaking current Minimum breaking current Voltage breaking capacity 1 C/O 2000 VA/80 W 8 AAC 250 VAC resistive 8 ADC 30 VDC resistive 10 mA / 5 VDC 250 VAC / 8 AAC resistive 250 VDC / 0,3 A resistive Electrical life (operations) 105 8 A 250 VAC resistive Mechanical life (operations) 10 x 106 2,5 kV / 1 min / 1 mA / 50 Hz 5 kV wave 1.2 / 50 s Breakdown voltage acc. to IEC/EN 61812-1 Impulse voltage acc. to IEC/EN 60664-1, IEC/EN 61812-1 Solid state output Rated power Derating Maximum admissible current Minimum breaking current Leakage current Voltage breaking capacity Maximum voltage drop at terminals Electrical life (operations) 0,7 A AC / DC 20 C (0,5 A UL) 5 mA/ C 20 A 10 ms 10 mA < 5 mA 250 VAC / DC 3 wire 4V 2 wire 8V 108 Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected 23/04/2013 Breakdown voltage acc. to IEC/EN 60664-1, IEC/EN 60255-5 Input type www.crouzet.com 2.5 kV to 1 mA / 1 min Volt-free contact 3-wire PNP output control option residual voltage : 0.4V whatever the timer power supply General characteristics Conformity to standards IEC/EN 61812-1 IEC/EN 61000-6-1 IEC/EN 61000-6-2 IEC/EN 61000-6-3 IEC/EN 61000-6-4 CE, UL, cUL,CSA, GL -20 +60 -30 +60 Certifications Temperature limits use (C) Temperature limits stored (C) Installation category Voltage surge category III (acc. to IEC/EN 60664-1) Creepage distance and clearance acc. to IEC/EN 60664-1 4 kV / 3 mm Protection (IEC/EN 60529) IP20 IP40 Degree of protection acc. to IEC/EN 60529 Front face IP50 Vibration resistance 20 m/s2 10 Hz 150 Hz acc. to IEC/EN 60068-2-6 Relative humidity no condensation acc. to IEC/EN 6006893 % non-condensing 2-30 Electromagnetic compatibility - Immunity to electrostatic Level III (Air 8 kV / Contact 6 kV) discharges acc to IEC/EN 61000-4-2 Immunity to radiated, radio-frequency, electromagnetic Level I field acc. IEC/EN 61000-4-3 (1 V/m : 2,0 G Hz 2,7 G Hz) Level II (3 V/m : 1,4 G Hz 2,0 G Hz) Level III (10 V/m : 80 M Hz 1 G Hz) Immunity to rapid transient bursts acc. to IEC/EN 61000-4Level III (direct 2 kV / Capacitive coupling clamp 1 kV) 4 Immunity to shock waves on power supply acc. to IEC/EN Level III (2 kV / common mode 2 kV/residual current mode 1 kV) 61000-4-5 Immunity to radio frequency in common mode acc. to Level III (10V rms : 0.15 M Hz to 80 M Hz) IEC/EN 61000-4-6 Immunity to voltage dips and breaks acc. to IEC/EN 61000- 0 % residual voltage, 1 cycle 4-11 70 % residual voltage, 25/30 cycles Mains-borne and radiated emissions acc. to EN 55022 Class B (CISPR22), EN55011 (CISPR11) Fixing : Symmetrical DIN rail 35 mm Terminal capacity Single-wire without ferrule 1 x 0,5 3,3 mm2 (AWG 20 AWG 12) 2 x 0,5 2,5 mm2 (AWG 20 AWG 14) Terminal capacity Multi-wire with ferrule 1 x 0,5 2,5 mm2 (AWG 20 AWG 14) 2 x 0,5 1,5 mm2 (AWG 20 AWG 16) Spring terminals, 2 terminals per connection point flexible wire 2 x 0,5 1,5 mm2 (AWG 20 AWG 16) 2 x 0,5 1,5 mm2 (AWG 20 AWG 16) Housing material Self-extinguishing Weight : casing 17,5 mm 88827105 (MUR1) : 63 g 88827115 (MAR1) : 63 g 88827125 (MBR1) : 63 g 88827135 (MCR1) : 62 g 88827145 (MHR1) : 63 g 88827150 (MLR4) : 63 g 88827155 (MLR1) : 64 g 88827100 (MUR4) : 62 g 88827103 (MUR3) : 66 g 88827503 (MURc3) : 59 g 88827150 (MLR4) : 63 g 88827185 (MXR1) : 63 g 88827004 (MUS2) : 55 g 88827014 (MAS5) : 53 g 88827044 (MHS2) : 53 g 88827054 (MLS2) : 56 g Shock test IEC/EN 60068-2-27 15 g - 11 ms Short interruption on power line acc to IEC/EN 61000-4-11 0 % residual voltage, 250/300 cycles Insulation resistance according to IEC/EN 60664-1 100 M (500 VDC) Spring terminals, 2 terminals per connection point - rigid wire Dimensions (mm) Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected 23/04/2013 Curves Function Ad Function Ad Delay on energisation by switch (non resettable) 1 relay Curves Function Ah Function Ah Flashing single cycle by switch (non resettable) 1 relay Curves Function N Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected www.crouzet.com 23/04/2013 Function N Safe-guard Curves Function O Function O Delayed safe-guard Curves Function P Function P Delayed fixed-length pulse 1 relay Curves Function Pt Function Pt Impulse counter (delay on) 1 relay Curves Function Tl Function Tl Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected www.crouzet.com 23/04/2013 Impulse relay Curves Function Tt Function Tt Timed impulse relay Curves Function W Function W Timing after pulse on control contact 1 relay Connections 1 changeover relay output Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected www.crouzet.com Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Crouzet: 88827185