Type: DILM25-10(24V50HZ) Article No.: 277119 Ordering information Rated operational current AC-3 400 V Ie A 25 Max. rating for three-phase motors, 50 - 60 Hz AC-3 230 V P kW 7.5 Max. rating for three-phase motors, 50 - 60 Hz AC-3 400 V P kW 11 Max. rating for three-phase motors, 50 - 60 Hz AC-3 690 V P kW 14 Max. rating for three-phase motors, 50 - 60 Hz AC-4 230 V P kW 3.5 Max. rating for three-phase motors, 50 - 60 Hz AC-4 400 V P kW 6 Max. rating for three-phase motors, 50 - 60 Hz AC-4 690 V P kW 8.5 General Standards IEC/EN 60947, VDE 0660, UL, CSA Lifespan, mechanical AC operated DC operated Operations x 106 10 Operations 106 10 x Operating frequency, mechanical AC operated Operations/h 5000 DC operated Operations/h 5000 Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclical, to IEC 60068-2-30 Climatic proofing Ambient temperature Open C -25/60 Enclosed C -25/40 Storage C -40/80 1 Mechanical shock resistance (IEC/EN 60068-2-27) Half-sinusoidal shock, 20 ms Main contacts Make contact g 10 Auxiliary contacts Make contact g 7 Break contact g 5 Protection type IP00 Protection against direct contact when actuated from front (IEC 536) Finger- and back-of-hand proof Weight AC operated kg 0,42 DC operated kg 0,48 Terminal capacity Main cable Solid mm2 1 x (0.75 - 16) 2 x (0.75 - 10) Flexible with ferrule mm2 1 x (0.75 - 16) 2 x (0.75 - 10) Stranded mm2 1 x 16 Solid or stranded AWG 18 - 6 Anschlussschraube Hauptleiter Tightening torque M5 Nm 3 Solid mm2 1 x (0.75 - 4) 1 x (0.75 - 4) Flexible with ferrule mm2 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) Solid or stranded AWG 18 - 14 Terminal capacity Control circuit cables Anschlussschraube Hilfsleiter Tightening torque M3.5 Nm 1.2 Tool Main cable Pozidriv screwdriver Standard screwdriver Size 2 mm 0.8 x 5.5 1x6 Control circuit cables Pozidriv screwdriver Size 2 mm 0.8 x 5.5 1x6 Solid mm2 0.75 - 2.5 Flexible mm2 0.75 - 2.5 Flexible with ferrule mm2 0.75 - 2.5 Solid or stranded AWG 18 - 14 Standard screwdriver Terminal capacity Control circuit cables Tool Stripping length mm 10 Screwdriver blade width mm 3,5 2 Main conducting paths Rated impulse withstand voltage Uimp V AC Overvoltage category/pollution degree 8000 III/3 Rated insulation voltage AC Ui V AC 690 Rated operational voltage Ue V AC 690 between coil and contacts V AC 440 between the contacts V AC 440 A 350 A 250 Safe isolation to VDE 0106 Part 101 and Part 101/A1 Making capacity (cos O to IEC/EN 60947) up to 690 V Breaking capacity 220/230 V 380/400 V A 250 500 V A 250 660/690 V A 150 Component lifespan AC-3/AC-4 Tripping characteristics Maximum operating frequency AC-1; 400 V Ie Ops/h 800 AC-3; 400 V Ie Ops/h 800 AC-4; 400 V Ie Ops/h 300 400 V gG/gL 500 V A 35 690 V gG/gL 690 V A 35 400 V gG/gL 500 V A 100 690 V gG/gL 690 V A 50 at 40 C Ith A 45 at 50 C Ith A 43 at 55 C Ith A 42 at 60 C Ith A 40 Enclosed Ith A 36 open Ith A 85 Enclosed Ith A 80 Short-circuit rating Short-circuit protection Maximum fuse Type "2" coordination Type "1" coordination AC AC-1 duty conv. therm. current 3-pole 50 - 60 Hz open Conventional free air thermal current, 1-pole AC-3 duty Rated operational current AC-3 open, 50 - 60 Hz, 3-pole 3 220/230 V Ie A 25 240 V Ie A 25 380/400 V Ie A 25 415 V Ie A 25 440V Ie A 25 500 V Ie A 25 660/690 V Ie A 15 220/230 V P kW 7,5 240V P kW 8,5 380/400 V P kW 11 415 V P kW 14,5 440 V P kW 15,5 500 V P kW 17,5 660/690 V P kW 14 220/230 V Ie A 13 240 V Ie A 13 380/400 V Ie A 13 415 V Ie A 13 440 V Ie A 13 500 V Ie A 13 660/690 V Ie A 10 220/230 V P kW 3,5 240 V P kW 4 380/400 V P kW 6 415 V P kW 6,5 440 V P kW 7 500 V P kW 8 660/690 V P kW 8,5 60 V Ie A 40 110 V Ie A 40 220 V Ie A 40 440 V Ie A 2,9 60 V Ie A 35 110 V Ie A 35 220 V Ie A 10 440 V Ie A 0,6 Motor rating AC-4 duty Rated operational current AC-4 open, 50 - 60 Hz, 3-pole Motor rating DC of three-phase capacitors open DC-1 operation DC-3 operation DC-5 operation 4 60 V Ie A 35 110 V Ie A 35 220 V Ie A 10 440 V Ie A 0,6 Current heat loss at Ith W 9,6 Current heat loss at Ie to AC-3/400 V W 3,8 Impedance per pole m& 2 Pick-up x Uc 0,8 - 1,1 Abfall x Uc 0,3 - 0,6 Pick-up x Uc 0,7 - 1,2 Abfall x Uc 0,15-0,6 50 Hz Pick-up VA 50 50 Hz Pick-up W 40 50 Hz Sealing VA 8 50 Hz Sealing W 2,4 60 Hz Pick-up VA 62 60 Hz Pick-up W 50 60 Hz Sealing 60 Hz Sealing VA 2,7 50/60 Hz Pick-up VA 60 54 50/60 Hz Pick-up W 48 43 50/60 Hz Sealing VA 9,5 7,9 50/60 Hz Sealing W 2,8 2,4 DC operated Pick-up W 12 at 24 V DC operated Sealing W 0.5 at 24 V Current heat loss (3-pole) Magnet systems Voltage tolerance AC operated AC operated Drop-out voltage AC operated Drop-out voltage AC operated DC operated DC operated DC operated DC operated Power consumption of the coil in a cold state and 1.0 x Uc Duty factor 9,1 % DF 100 Switching times at 100 % Uc (approximate values) Main contacts AC operated Closing delay ms 25 Opening delay ms 25 Closing delay ms 60 Opening delay ms 15 DC operated 5 Arcing time ms 10 Electromagnetic compatibility (EMC) Emitted interference to EN 60947-1 Interference immunity to EN 60947-1 Mounting position, AC- and DC operated Moeller GmbH, Hein-Moeller-Str. 7-11, D-53115 Bonn E-Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net Copyright 2005 by Moeller GmbH. Subject to modifications. HPL-C2005GB-INT V3.0 6